Example: quiz answers

CA202001EN Substation Transformers-Unit and …

Three-Phase transformers and substations COOPER POWER. SERIES. Effective January 2018. CA202001EN Supersedes October 2015. Substation Transformers-Unit and open types General Eaton designs its Cooper Power series Substation transformers to meet a wide variety of customer specifications. Flexibility in design, combined with the highest quality manufacturing processes, equipment, and testing procedures, enable Eaton to provide a product optimized to the customer's requirements. All units meet applicable American National Standards Institute (ANSI ), Institute of Electrical and Electronics Engineers, Inc.

Table 5. Insulation Test Levels kV Class Induced Test 180 or 400 Hz 7200 Cycle kV BIL Applied Test Distribution Power 60 Hz (kV) 1.2 TWICE RATED VOLTAGE

Tags:

  Unit, Insulation, Substations, Transformers, Ca202001en substation transformers unit and, Ca202001en

Information

Domain:

Source:

Link to this page:

Please notify us if you found a problem with this document:

Other abuse

Transcription of CA202001EN Substation Transformers-Unit and …

1 Three-Phase transformers and substations COOPER POWER. SERIES. Effective January 2018. CA202001EN Supersedes October 2015. Substation Transformers-Unit and open types General Eaton designs its Cooper Power series Substation transformers to meet a wide variety of customer specifications. Flexibility in design, combined with the highest quality manufacturing processes, equipment, and testing procedures, enable Eaton to provide a product optimized to the customer's requirements. All units meet applicable American National Standards Institute (ANSI ), Institute of Electrical and Electronics Engineers, Inc.

2 (IEEE ) and National Electrical Manufacturers Association (NEMA ) standards, as well as National Electric Code (NEC ), Department of Energy (DOE). and Canadian Standards Association (CSA ). specifications. Substation transformers are available with cover- mounted bushings or sidewall-mounted bushings for connections to primary and/or secondary switchgear. Substation transformers are made with a wide range of core steels and winding conductors to optimize efficiency versus cost. Flexible core/coil and tank construction enable your dimensional requirements to be met.

3 Eaton's Cooper Power series transformers are available with Envirotemp FR3 fluid, a less-flammable and bio-degradable fluid, or electrical grade mineral insulating oil. Substation transformers intended for indoor use are solely filled with Envirotemp FR3 fluid, which meets Occupational Safety and Health Administration (OSHA) and Section , 2014. NEC requirements. Electrical codes recognize the advantages of using Envirotemp FR3 . fluid both indoors and outdoors for fire-sensitive applications. Catalog Data CA202001EN Substation Transformers-Unit and open types Effective January 2018.

4 RAPID PRESSURE RISE. RELAY. FILLING/FILTER PRESS Monitors rapid rise of CONNECTION internal pressure. One inch upper filling and TANK LIFTING LUGS. filter press connection. Lift hooks welded to the tank at each corner for lifting. PRESSURE/VACUUM. GAUGE NAMEPLATE. Available with bleeder and/or Laser-scribed PRESSURE RELIEF DEVICE. alarm contacts anodized Activated by excessive tank pressure. aluminum or Available with alarm contacts. LIQUID LEVEL GAUGE stainless steel Monitors oil level. Available with alarm contacts.

5 LIQUID. TEMPERATURE. GAUGE. For easy monitoring of oil temperature. Available with multiple alarm contacts. DE-ENERGIZED. TAP CHANGER. Tap changer is externally operable. THROAT. Allows FULL LENGTH connection CABINET to low- voltage gear. CONTROL BOX COOLING. Weather-resistant, RADIATORS. dust-proof, NEMA - rated control box for controls and alarm contacts. GROUND PADS. Non-corrosive, stainless steel or copper faced ground pads on the front and rear. BASE. DRAIN FILTERING VALVE Suitable for skidding, rolling The combination drain and and jacking.

6 Filtering valve contains a fluid sampling device. Low-voltage bushings Sidewall-mounted low-voltage molded epoxy or porcelain bushings with NEMA . spades. Figure 1. unit type Substation transformer with standard features and optional accessories. 2 Substation Transformers-Unit and open types Catalog Data CA202001EN . Effective January 2018. Product Scope Type Three-Phase or Single-Phase, 50 or 60 Hz, 65 C. 55 C and 55/65 C available. See CA202004EN for 75 C. options. Fluid Type Envirotemp FR3 fluid or Mineral Oil Size Three-Phase: 300 12,000 kVA.

7 Single-Phase: 250-5000 kVA. Primary Voltage 2400 46,000 V. Secondary Voltage 208-15,000 V (25 kV available upon special request). Specialty Designs Hardened Data Centers Grounding transformers K-factor ( up to K-20). Hazardous Location (Class I, Division 2, Groups B, C, and/or D). Internal Vacuum Fault Interrupter (VFI). UL Listed & Labeled/ Classified Factory Mutual (FM) Approved Solar/Wind Designs Variable Speed Drives or Rectifier Duty Mining/Skid-Mounted Applications Multi-tap designs for electric submersible pump (ESP) applications Table 1.

8 Three-Phase, Single Temperature kVA Ratings Table 3. Three-Phase, Dual Temperature kVA Ratings Three-Phase kVA Three-Phase kVA Self-Cooled and Forced-Air Cooled with Dual Rated 55. Self-Cooled and Forced-Air Cooled with 65 C Temperature Rise C/65 C Temperature Rise 65 C Rise KNAN 65 C Rise KNAN/KNAF 55 C Rise 65 C Rise 55 C Rise 65 C Rise KNAN/. KNAN KNAN KNAN/KNAF KNAF. 500 N/A. 500 560 N/A N/A. 750 863. 750 840 863 966. 1000 +15% 1150. 1000 1120 1150 1288. 1500 1725. 1500 1680 1725 1932. 2000 2300. 2000 2240 2300 2576.

9 2500 3125. 3750 4688. 2500 +12% 2800 3125 3500. 3750 4200 4688 5250. 5000 +25% 6250. 5000 5600 6250 7000. 7500 9375. 7500 8400 9375 10500. 10000 12500. 10000 11200 12500 14000. 12000 +33% 16000 12000 13440 16000 17920. NNote: For transformers with a 75 degree C rating, please refer to Catalog CA202004EN, PEAK Substation transformers . Table 2. Impedance Voltage Impedance Voltage1. kVA Rating HV BIL LV 600 V and (1PH and 3PH) (kV) below LV above 600 V. 200 750-4999 110 750-4999 150 750-4999 200 7. 750-4999 250 5000-10000 150 - 5000-10000 200 - 7.

10 5000-10000 250 - 1 The standard tolerance is NNote: Impedances listed above are per IEEE Std -2007 standard. Impedances per IEEE Std -2010 standard are also available. 3. Catalog Data CA202001EN Substation Transformers-Unit and open types Effective January 2018. Table 4. Audible Sound Levels NEMA Average Self-Cooled, Two Winding kVA Rating dB, KNAN dB, KNAF. 500 56 N/A. 501-700 57 67. 701-1000 58 67. 1001-1500 60 67. 1501-2000 61 67. 2001-2500 62 67. 2501-3000 63 67. 3001-4000 64 67. 4001-5000 65 67. 5001-6000 66 68.


Related search queries