CF3000 Control Panel - Safeguard Fire & Security Ltd

CF3000 Control PanelUser ManualFireAssessed to: ISO 9001:2000 Certification number: 714h/01 Approved to: EN54-2 1997 2006EN54-4:1997 2002 A2:2006 Document Drg Ref: PR200-04-514-11 Marketing Ref: CC1820a0832 CPD 1060CF3000 - USER MANUAL2 Introduction to the ManualThis manual provides information on the installation, operation and maintenance of the Cooper operating system of the CF3000 may be revised as a result of enhancements to the system softwareor hardware. Revisions to this manual will be issued and supplied on request and should be loggedin the table supplied on the contents of explosion if battery is replaced by an incorrect type disposeof the used batteries according to the instructionsContactTechnical: 01302 303350 Service: 01302 303352 Sales: 01302 303303CF3000 - USER MANUAL3 ContentsSection 1 - System Installati

CF3000 - USER MANUAL 2 Introduction to the Manual This manual provides information on the installation, operation and maintenance of the Cooper CF3000

Tags:

  Control, Panels, Cf3000 control panel, Cf3000

Information

Domain:

Source:

Link to this page:

Please notify us if you found a problem with this document:

Other abuse

Advertisement

Transcription of CF3000 Control Panel - Safeguard Fire & Security Ltd

1 CF3000 Control PanelUser ManualFireAssessed to: ISO 9001:2000 Certification number: 714h/01 Approved to: EN54-2 1997 2006EN54-4:1997 2002 A2:2006 Document Drg Ref: PR200-04-514-11 Marketing Ref: CC1820a0832 CPD 1060CF3000 - USER MANUAL2 Introduction to the ManualThis manual provides information on the installation, operation and maintenance of the Cooper operating system of the CF3000 may be revised as a result of enhancements to the system softwareor hardware. Revisions to this manual will be issued and supplied on request and should be loggedin the table supplied on the contents of explosion if battery is replaced by an incorrect type disposeof the used batteries according to the instructionsContactTechnical: 01302 303350 Service: 01302 303352 Sales.

2 01302 303303CF3000 - USER MANUAL3 ContentsSection 1 - System Installation and DesignIntroduction5 Project Planning 6 System Design Guidelines 7 Compatible Equipment 8 Detectors 9 Callpoints 10 Beacons and Sounders 11 Base Sounder11 Stand Alone Sounders12 Loop Powered Beacon12 Compatible Interfaces 133 Channel I/O 131 Channel I/O 14 Zone Monitor Unit 14 Shop Monitor Unit 15 Spur Isolator 164 Way Sounder Circuit Controller 16 Micro Interfaces17 Fan Controller Interfaces (FC18 / FC6)

3 18 Equipment Compatiblity 19 System Overview 20 Technical Specification 22 Optional Functions as per EN54 Pt 2 & 4 24 Optional Functions Not Approved to EN54 Pt 2 & 4 28 Cable and Wiring 29 Installation 30 Fixing Details 31 External Connections 32 Networking 33 Inputs/Outputs 34 Maintainance 36 Section 2 - Panel Assembly InformationAttaching Panel Door 38 Installing Optional Screen Door 39 Replacing Printer Paper Roll 40 Section 3 - Commissioning Commissioning Mode 42 Configuration 43 Panel Fault Finding 44 Protocol 45PC Comissioning Software46 Section 4 - Panel Controls And Indicators System Indicators 50 Panel Layout 51 Touch Screen Display 52 Panel Operation 53 Public (Access Level 1) 54 Evacuate (Access Level 2)

4 55 Silence Alarms 56 Mute Buzzer 57 Reset 57 Pre Alarms 58 Disabled Devices 58yView Faults 59 Enable / Disable (Others Menu) 59 Print 61 Lamp Test 62 Weekly Test 63 View Events 64 Check Auto Config 65 Replace Device66 Test Device 67 Test Zone 68 Sounder Level Test Mode 69 Global LED Flashing On/Off 70 One Man Walk Test 71 Load CDR From Laptop 72 Download CDR To Laptop 73 Auto Learn 74 Erase Log 75 System Details 76 Analogue Levels 77 Printer Settings 78 Change Panel Number 79 Number of panels In Network 80 Screen Cover 81 Programming I/O and Sounders 82 Sound Settings 83 Change Date/Time 84 Change Address Text

5 85 Change Zone Text 86 Change Panel Text 87 Configure Zones 88 Change User Code 89 Add Zone 90 Delete Zone91 Add Device92 Delete Device93 Configure Heat Detectors94 Network95 Password Protection96 Section 5 - AppendixSpur Isolator984 Way Sounder Controller99 Zone Monitor Unit100 Shop Monitor Unit1011 Way Input Output Unit102 Detector Base Wiring103 System Wiring104IP66 Wall Sounder105 Internal Wall Sounder106 Base Sounder1073 Way Input Output Unit108 Loop Powered Beacon109 Callpoint110EN54 Product Spec Label111 Battery Disposal Instructions112CE Marking113CF3000 - USER MANUAL4 Section 1 System Installation and DesignSection 1 - System Installation and DesignCF3000 - USER MANUAL5 IntroductionCF3000 provides all of the sophisticated features required of a leading edge analogue addressable firesystem along with the simple operation and neat installation demanded by installers and building Panel can be flush or surface mounted and the generously sized metal back box allows amplefacilities for rear or top cable entries.

6 It is available in single two and four loop versions, with or without anintegral addition both passive and fully functional repeater panels are available. A comprehensive range of ancillary devices is available to operate with CF3000 , including optical,ionisation, photo-thermal and heat detectors, base mounted and stand alone sounders (including an IP67version) a loop powered beacon and a wide range of input and output of the CF3000 system components has been specifically designed to operate as part of a CF3000system, this provides an assurance that the Panel , the detectors, the interfaces and the ancillaries are allfully compatible with each other and that the full range of system functionality is supported by loop of a CF3000 Panel can accommodate up to 200 addresses.

7 To comply with EN54requirements no more than 512 addresses should be connected to a single Panel . Each Panel canindicate upto 96 zones. panels are available with upto 4 detection loops, up to 126 panels can benetworked together to form a single system capable of operating with over 32,000 devices. Note: Network systems fall outside the scope of 1 - System Installation and DesignCF3000 - USER MANUAL6 Project PlanningThe following is a typical program and timetable for a CF3000 installation project, once the initial orderhas been received:1. Project MeetingInstaller and user to be present; system specifications, schematic diagram and proposed circuit drawingto be available.

8 CF3000 Installation and Commissioning Guide to be Equipment FixTypically 2 week's notice is required for equipment to be delivered. Cable to be installed and bases/backboxes to be fitted. Then fire detectors, callpoints, alarm sounders, isolator units and interface units to Address ScheduleSchedule of sensor locations to be completed by installer and returned to enable system Auto LearnFire Panel /repeater panels to be installed and terminated. System to be powered up by installer and autolearn mode activated (see Auto Learn section). System to be tested and verified by installer, prior to Final CommissioningMinimum 2 weeks notice is required from receipt of Address Schedule and Commission request Fire Service Engineer to attend site implement/oversee the final commissioning procedures (seeCommissioning section), in conjunction with the 1 - System Installation and DesignCF3000 - USER MANUAL7 System Design GuidelinesGuidelinesSystems should to the relevant local standards and codes of practice, for the UK this is BS5839 Pt meets all the relevant requirements of BS5839 Pt 1: 2002.

9 Installation planning is simplified bythe fact that every addressable CF3000 device contains an integral short circuit isolator. Care must betaken to ensure that local standards requirements regarding aspects such as loop coverage, areacovered by a single spur and cable specification are may be certain applications in which deviations from the code may be necessary and these mustbe listed on the commissioning certificate. (See commissioning section).Loop LengthsThe maximum permitted loop length is 2 km measured from the near to the far terminals on the CF3000motherboard PCB.

10 There is no minimum limit to loop length. Any wiring spurs off the loop must beincluded within the 2 km limit. On long loop runs, the lengths of wiring rises and falls (between floors,down to manual callpoints) must be included. Remember to include these especially when taking looplengths from plan Loading - Total Number of AddressesThe total number of addresses per loop is 200. this includes detectors, callpoints and all otheraddressable items ( MPU, MIO, loop repeaters etc.) When designing systems its recommended thatallowances are made for future expansion, Short circuit isolators are incorporated into every CF3000 loopdevice, including Smoke detectors, heat detectors, sounders, callpoints and interfaces.