Example: tourism industry

cleVis hanGers - Anvil EPS

cleVis hanGers Tubing HangersPipeRingsClevis HangersSteel PipeClampsSocketClampsStructuralAttachme ntsBracketsCeiling Plates& FlangesConcrete Inserts& AttachmentsHangerRodsRod AttachmentsBeamClampsTable ofContentsCPVCPipe HangersGeneralNotesStainless SteelHangersBolts, Nuts,Pins & U-BoltsFIG. 260 ISS SIzING TABLEC opperTubeSizeInsulation Thickness1/2"3/4"1"11/2"2"(Size Number)3/8223 1/2223 5/8223 3/4223 1233 11/4333 11/2334 2444 21/24556 35556831/2556884668885888810681010101081 010121212 FIG. 260 ISS SIzING TABLEPipeSizeInsulation Thickness1/2"3/4"1"11/2"2"(Size Number)1/2223 3/4233 1233 11/2344 2445 21/25556835556831/2566884668885888101061 0101010108121212121210141414141612161616 16 Fig.

cleVis hanGers www.anvilintl.com 45 Copper Tubing Hangers Pipe Rings Clevis Hangers Steel Pipe Clamps Socket Clamps Structural Attachments Brackets

Tags:

  Copper, Pipe, Hanger, Clevis, Clevis hangers

Information

Domain:

Source:

Link to this page:

Please notify us if you found a problem with this document:

Other abuse

Advertisement

Transcription of cleVis hanGers - Anvil EPS

1 cleVis hanGers Tubing HangersPipeRingsClevis HangersSteel PipeClampsSocketClampsStructuralAttachme ntsBracketsCeiling Plates& FlangesConcrete Inserts& AttachmentsHangerRodsRod AttachmentsBeamClampsTable ofContentsCPVCPipe HangersGeneralNotesStainless SteelHangersBolts, Nuts,Pins & U-BoltsFIG. 260 ISS SIzING TABLEC opperTubeSizeInsulation Thickness1/2"3/4"1"11/2"2"(Size Number)3/8223 1/2223 5/8223 3/4223 1233 11/4333 11/2334 2444 21/24556 35556831/2556884668885888810681010101081 010121212 FIG. 260 ISS SIzING TABLEPipeSizeInsulation Thickness1/2"3/4"1"11/2"2"(Size Number)1/2223 3/4233 1233 11/2344 2445 21/25556835556831/2566884668885888101061 0101010108121212121210141414141612161616 16 Fig.

2 260 ISS cleVis hanger with Insulation Saddle SystemSize Range: 1/2" through 12" pipe and accommodates up to 2" of : Carbon steel with high impact glass reinforced polypropylene saddle andcarbon steel pipe : Plain or Galvanized cleVis HangerService: Recommended for the suspension of stationary insulated chilled or hotwater pipe Temperature: 40 F to 200 FApprovals: Dual Fire Ratings, UL E94 VO and ASTM E84 Class 1 25 : hanger load nut above cleVis must be tightened securely to assureproper performance. Position the pipe on the saddle. Notch insulation to fit aroundthe saddle. Square cut adjoining insulation and butt the insulation ends to eachother.

3 Insulation joint is coated, caulked and taped following standard insulationpractice used on flanges and : Vertical adjustment without removing the hanger may be made 7/8"through 23/8" varying with the size of the cleVis . Tighten all nuts after : V-Block design cradles pipethrough out the entire erection bolt spacer included as standardkeeps the cleVis lower strap from collapsing. Eliminates: Wood blocks and standard shields Costly calcium silicate inserts Re-leveling of piping at each individual hanger after insulation is : Specify size number, pipe size,insulation thickness, figure number nameand 260 ISS: LoADS (LBS) wEIGHTS (LBS) DIMENSIoNS (IN)260 ISS Size Number*MaxLoadWeightRod SizeAC**Rod Take Out * Max load exceeds dead weight load requirement of pipe at max span, except 14 and 16 where max load is based on industry standard spacing of 14.

4 Further information on typical pipe spans and piping weight per length can be found on pages 249 and 251, respectively.** Based on maximum insulation thickness, variations due to pipe size and insulation thickness may " through 16"Patent #7,281, hanGers 260 ISS cleVis hanger with Insulation Saddle System (cont.)Application: Anvil 's insulation saddle system clevises are fully tested and rated for a temperature range from 40 F to 200 F. Ideal for the sus-pension of stationary insulated chilled or hot water water Testing: Extensive field-testing and inspection has been performed to confirm that the integrity of the insulation vapor barrier for chilled water systems are sustained with the 260 Assure Proper Vapor Barrier: Each insulation joint should be properly coated, caulked and taped.

5 Applying standard insulation practice that is used on flanges and : The Anvil 260 (ISS) Insulation Saddle System reduces your overall installation time and greatly simplifies the way you insulate copper and steel pipe systems. Contractors can support insulated pipe with less parts and revolutionary design of the 260 ISS spreads the load evenly over the lower strap of the cleVis . The innovative V-Block design cradles the pipe at the design elevation throughout the erection process. The wide base V-Block design accommodates multiple pipe sizes, reducing the on-site inventory and the flexibility of pipe and insulation combinations with each size & UL Fire Ratings: The 260 ISS has been independently tested by ASTM and UL for: Flame Spread Index (FSI) Smoke Development (SD) and drip ratingsApprovals from both agencies with the highest ratings for the type of Thermal Conductivity: V-Block low thermal conductivity of.

6 77 FInsulation R-Values: The Figure 260 ISS polymer V-Block component has an R-value ranging from to , depending on the hanger size. Meets or exceeds most commercial insulation hanGers Tubing HangersPipeRingsClevis HangersSteel PipeClampsSocketClampsStructuralAttachme ntsBracketsCeiling Plates& FlangesConcrete Inserts& AttachmentsHangerRodsRod AttachmentsBeamClampsTable ofContentsCPVCPipe HangersGeneralNotesStainless SteelHangersBolts, Nuts,Pins & U-BoltsFig. 260 ISS cleVis hanger with Insulation Saddle System (cont.)Easy InstallationMake sure the double hex nuts installed with the upper hanger load nut above the cleVis are tightened securely.

7 Position pipe on 1 STEP 2 STEP 3 Square CutSTEP 4 Cope or notch insulation to fit around saddle. The notch should be deep enough to extend 1/8" to 1/4" beyond the the notched insulation section over cut adjoining insulation and butt the insulation ends to each joints and finish assure proper vapor barrier: Each insulation joint should be properly coated, caulked and taped. Applying standard insulation practice that is used on flanges and via standard taping chilled systems a mastic for thermal insulations or similar sealant is typically used:Systems (50 F or greater) apply sealant to: The coped and flat edges of the mating insulation sections.

8 The V-Block saddle at the insulation (Below 50 F) apply sealant as per 50 Degrees with additional sealant to: The V-Block saddle joint between the two saddle sealant applied to V-Block saddle joint between the two saddle halves. (Chilled water below 50 F)Mastic applied to V-Block saddle at insulation interface. (50 F or greater) hanGers 300 Adjustable cleVis for Insulated LinesSize Range: 3 4" through 12"Material: Carbon steelFinish: Plain, Galvanized or Epoxy coatedService: Recommended for suspension of insulated stationary pipe Temperature: Plain 650 F, Galvanized and Epoxy 450 FApprovals: Complies with Federal Specification A-A-1192A (Type 1) WW-H-171-E (Type 1), ANSI/MSS SP-69 and MSS SP-58 (Type 1).

9 Installation: hanger load nut above cleVis must be tightened securely to assure proper hanger : Vertical adjustment is provided, varying with the size of the cleVis . Tighten upper nut after : Designed for 2" of insulation on 3 4" through 1 1 2" pipe and 4" of insulation on 2" and larger pipe . When properly installed, cleVis bolt is outside the : Specify pipe size, figure number, name and 300: LoADS (LBS) wEIGHT (LBS) DIMENSIoNS (IN)PipeSizeMaxLoadWeightRod Size ABCEA djustmentFGHIW idth Lower3 835 841 427 81 21 1631 45 811 1651 435 87 811 453 441 1611 16811 1661 215 8421 21, 287 16915 1671 223 8105 1679 1613 441, 893 8115 883 16115 1611 8125 883 413 41 261, 4105 81493 817 811/282, 8163 41125 813/4103, 8133 4193 16121 421 83 4123, 8219 16135 827 hanGers Tubing HangersPipeRingsClevis HangersSteel PipeClampsSocketClampsStructuralAttachme ntsBracketsCeiling Plates& FlangesConcrete Inserts& AttachmentsHangerRodsRod AttachmentsBeamClampsTable ofContentsCPVCPipe HangersGeneralNotesStainless SteelHangersBolts, Nuts.

10 Pins & U-BoltsFig. 590 Adjustable cleVis for Ductile or Cast Iron PipeSize Range: 3" through 24" ductile or cast iron pipeMaterial: Carbon steelFinish: Plain or GalvanizedService: Recommended for the suspension of stationary ductile iron or cast iron : Complies with Federal Specification A-A-1192A (Type 1) WW-H-171-E (Type 1), ANSI/MSS SP-69 and MSS SP-58 (Type 1).Installation: hanger rod nut above cleVis must be tightened securely to assure proper hanger : Vertical adjustment without removing pipe may be made from 1 15 16" through 3 3 16", varying with the size of the cleVis . Tighten upper nut after : Specify pipe size, figure number, name and : Figure 590 sizes 12" and below typically feature a Figure 260 Top 590: LoADS (LBS) wEIGHT (LBS) DIMENSIoNS (IN) pipe pipe Size ABCEFG WidthLower31, 251 1671 1643 16 113 1611/441, 853 483 1643 4 115 1661, 471 8109 16515 1611/282, 8133 1671 221 413/4103, 8101 81511 1683 425 16123, 161811 161011 1627 82144, 4207 8115 1629 16164, 42215 16129 1627 1621/2184, 8265 8153 16313 16204, 4181 4291 16163 83244, 16331 4183 pipe clamps 261 Extension pipe or Riser Clamp Size Range.


Related search queries