Publication 1769-IN031A-EN-P - April 2003 Installation InstructionsCompact 32-point Solid-state 24V dc Source Output ModuleCatalog Number 1769-OB32 Use this document as a guide when installing a Compact 32-point Solid-state 24V dc Source Output User Information2 Module Description3 Module Installation4 System Assembly5 Mounting Expansion I/O6 Replacing a Single Module within a System8 Field Wiring Connections9I/O Memory Mapping121769-OB32 Configuration File13 Spare/Replacement Module Parts15 Specifications16 Hazardous Location Considerations21 For More Information222 Compact 32-point Solid-state 24V dc Source Output Module Publication 1769-IN031A-EN-P - April 2003 Important User InformationBecause of the variety of uses for the products

Compact 32-point Solid-state 24V dc Source Output Module 5 Publication 1769-IN031A-EN-P - April 2003 System Assembly The module can be attached to the controller or an adjacent I/O module before or after mounting. For mounting instructions, …

Tags:

  States, 1967, Solid

Information

Domain:

Source:

Link to this page:

Please notify us if you found a problem with this document:

Other abuse

Transcription of Compact 32-point Solid-state 24V dc Source Output Module

1 Publication 1769-IN031A-EN-P - April 2003 Installation InstructionsCompact 32-point Solid-state 24V dc Source Output ModuleCatalog Number 1769-OB32 Use this document as a guide when installing a Compact 32-point Solid-state 24V dc Source Output User Information2 Module Description3 Module Installation4 System Assembly5 Mounting Expansion I/O6 Replacing a Single Module within a System8 Field Wiring Connections9I/O Memory Mapping121769-OB32 Configuration File13 Spare/Replacement Module Parts15 Specifications16 Hazardous Location Considerations21 For More Information222 Compact 32-point Solid-state 24V dc Source Output Module Publication 1769-IN031A-EN-P - April 2003 Important User InformationBecause of the variety of uses for the products described in this publication, those responsible for the application and use of these products must satisfy themselves that all necessary steps have been taken to assure that each application and use meets all performance and safety requirements.

2 Including any applicable laws, regulations, codes and standards. In no event will Rockwell Automation be responsible or liable for indirect or consequential damage resulting from the use or application of these illustrations, charts, sample programs, and layout examples shown in this publication are intended solely for purposes of example. Since there are many variables and requirements associated with any particular installation, Rockwell Automation does not assume responsibility or liability (to include intellectual property liability) for actual use based upon the examples shown in this publication , Safety Guidelines for the Application, Installation and Maintenance of Solid-state Control (available from your local Rockwell Automation office)

3 , describes some important differences between Solid-state equipment and electromechanical devices that should be taken into consideration when applying products such as those described in this of the contents of this copyrighted publication, in whole or part, without written permission of Rockwell Automation, is this publication, notes may be used to make you aware of safety considerations. The following annotations and their accompanying statements help you to identify a potential hazard, avoid a potential hazard, and recognize the consequences of a potential hazard:WARNING!

4 Identifies information about practices or circumstances that can cause an explosion in a hazardous environment, which may lead to personal injury or death, property damage, or economic !Identifies information about practices or circumstances that can lead to personal injury or death, property damage, or economic information that is critical for successful application and understanding of the 32-point Solid-state 24V dc Source Output Module 3 Publication 1769-IN031A-EN-P - April 2003 Module DescriptionItemDescription1bus lever (with locking function)

5 2aupper panel mounting tab2blower panel mounting tab3I/O diagnostic LEDs4module door with terminal identification label5amovable bus connector with female pins5bstationary bus connector with male pins6nameplate label7aupper tongue-and-groove slots7blower tongue-and-groove slots8aupper DIN rail latch8blower DIN rail latch9write-on label (user ID tag)10removable terminal block (RTB) with finger-safe cover10aRTB upper retaining screw10bRTB lower retaining screw10a10b41032a12b5a97a7b8b7b8a7a5b617 69-OB32 WARNING -Do NotRemove RTB UnlessArea is Non-Hazardous30537-MDC COM 1 OUT 14 OUT 12 OUT 10 OUT 8 OUT 6 OUT 4 OUT 2 OUT 0 OUT 15 OUT 13 OUT 11 OUT 9 OUT 7 OUT 5 OUT 3 OUT 1+VDC 1DC COM 2 OUT 30 OUT 28 OUT 26 OUT 24 OUT 22 OUT 20 OUT 18 OUT 16 OUT 31 OUT 29 OUT 27 OUT 25 OUT 23 OUT 21 OUT 19 OUT 17+VDC 24 Compact 32-point Solid-state 24V dc Source Output Module Publication

6 1769-IN031A-EN-P - April 2003 Module InstallationCompact I/O is suitable for use in an industrial environment when installed in accordance with these instructions. Specifically, this equipment is intended for use in clean, dry environments (Pollution degree 2(1)) and to circuits not exceeding Over Voltage Category II(2) (IEC 60664-1).(3)Prevent Electrostatic DischargeRemove Power(1)Pollution Degree 2 is an environment where, normally, only non-conductive pollution occurs except that occasionally a temporary conductivity caused by condensation shall be expected.

7 (2)Over Voltage Category II is the load level section of the electrical distribution system. At this level transient voltages are controlled and do not exceed the impulse voltage capability of the product s insulation.(3)Pollution Degree 2 and Over Voltage Category II are International Electrotechnical Commission (IEC) !Electrostatic discharge can damage integrated circuits or semiconductors if you touch bus connector pins. Follow these guidelines when you handle the Module : Touch a grounded object to discharge static potential.

8 Wear an approved wrist-strap grounding device. Do not touch the bus connector or connector pins. Do not touch circuit components inside the Module . If available, use a static-safe work station. When not in use, keep the Module in its static-shield !Remove power before removing or inserting this Module . When you remove or insert a Module with power applied, an electrical arc may occur. An electrical arc can cause personal injury or property damage by: sending an erroneous signal to your system s field devices, causing unintended machine motion causing an explosion in a hazardous environmentElectrical arcing causes excessive wear to contacts on both the Module and its mating connector.

9 Worn contacts may create electrical 32-point Solid-state 24V dc Source Output Module 5 Publication 1769-IN031A-EN-P - April 2003 System AssemblyThe Module can be attached to the controller or an adjacent I/O Module before or after mounting. For mounting instructions, see Panel Mounting on page 6, or DIN Rail Mounting on page 8. To work with a system that is already mounted, see Replacing a Single Module within a System on page following procedure shows you how to assemble the Compact I/O that the bus lever of the Module to be installed is in the unlocked (fully right) the upper and lower tongue-and-groove slots (1) to secure the modules together (or to a controller).

10 The Module back along the tongue-and-groove slots until the bus connectors (2) line up with each the bus lever back slightly to clear the positioning tab (3). Use your fingers or a small screw allow communication between the controller and Module , move the bus lever fully to the left (4) until it clicks. Ensure it is locked firmly in !When attaching I/O modules, it is very important that the bus connectors are securely locked together to ensure proper electrical Compact 32-point Solid-state 24V dc Source Output Module Publication 1769-IN031A-EN-P - April an end cap terminator (5) to the last Module in the system by using the tongue-and-groove slots as the end cap bus terminator (6).