COMPACT NSF and NSJ150 to 600 A circuit breakersClass 615 CONTENTSD escriptionPageGeneral circuit and limiting 489 and IEC 947-2 test and maintenance NS circuit breakerCOMPACT NSF and NSJ150 to 600 A circuit breakerspageThe COMPACT circuit breaker line2 General characteristics3 Circuit breakers6 Trip units8 Switches14 Motor circuit protectors16 Installation and connections18 Connections20 Accessories22 Fixed-mounted32 Plug-in and drawout mounting34 Motor operators36 Rotary operating handles38 Front accessories40 Interlocking systems41 Connections42 Auxiliary circuits44 Trip curves46 Let-through curves at 480 V52 Let-through curves at 600 V53 Current limiting curves at 380/415 V54 Current limiting curves at 690 V55UL 489 test

COMPACT¨ NSF and NSJ 150 to 600 A circuit breakers Class 615 CONTENTS Description Page General characteristics .....3

Information

Domain:

Source:

Link to this page:

Please notify us if you found a problem with this document:

Other abuse

Advertisement

Transcription of COMPACT NSF and NSJ - theelectrostore.com

1 COMPACT NSF and NSJ150 to 600 A circuit breakersClass 615 CONTENTSD escriptionPageGeneral circuit and limiting 489 and IEC 947-2 test and maintenance NS circuit breakerCOMPACT NSF and NSJ150 to 600 A circuit breakerspageThe COMPACT circuit breaker line2 General characteristics3 Circuit breakers6 Trip units8 Switches14 Motor circuit protectors16 Installation and connections18 Connections20 Accessories22 Fixed-mounted32 Plug-in and drawout mounting34 Motor operators36 Rotary operating handles38 Front accessories40 Interlocking systems41 Connections42 Auxiliary circuits44 Trip curves46 Let-through curves at 480 V52 Let-through curves at 600 V53 Current limiting curves at 380/415 V54 Current limiting curves at 690 V55UL 489 test procedure56 IEC 947-2 test procedure58 Routine and maintenance guidelines602 COMPACT NS circuit breakerMotor circuit protectors page 16 COMPACT NS circuit breaker.

2 Functions and characteristicsThe COMPACT circuit breaker lineCircuit breakers page 6 Switches page 14pushtotripNSE, CK and CM circuit breakers: see appropriate 10015 250150 600400 12001250 2500current (A) COMPACT NSE100 NSF150 NSJ400CK400 CM1250 NSF250 NSJ600CK1200CM2500 InterruptingN18 353550 ratingH 65656585at 480 VL 100150 Rated70150, 250400, 600800, 1200 1600 2500current (A) COMPACT NSE100 ANSF150 ANSJ400 ACK800 NACM1600 HANSF250 ANSJ600 ACM2000 HACM2500 HARated3 75100 250400 600800 1200current (A) COMPACT NSE75 HCNSF150 HCNSJ400 HCCK800N/HNSF250 HCNSJ600 HCCK1000HL/LCK1200N/H3 COMPACT NS circuit breakerCOMPACT NS circuit breaker.

3 Functions and characteristicsGeneral characteristicsCompliance with standardsE28472 Compliance with North American standardsCOMPACT NS circuit breakers are built in accordance with UnderwritersLaboratories Inc. UL 489 Standard and Canadian Standards Association CSA Standard. Circuit breakers, switches and their accessories, except wherenoted, are Listed under UL files E63335, E103740, E103955, and Certified underCSA files LR69561 and with international standardsCOMPACT NS circuit breakers and their accessories comply also with the followinginternational standards:nIEC 947-1: general rules;nIEC 947-2: circuit breakers.

4 NIEC 947-3: switches, disconnectors, switch disconnectors, that these standards are applied in most countries, COMPACT circuit breakersand their accessories comply with European (EN 60947-1 and EN 60947-2) and thecorresponding national standards:nFrance NF;nGermany VDE; BS;nAustralia AS;nItaly with the specifications of marineclassification organizationsCOMPACT NS circuit breakers have been approved for marine application by theAmerican Bureau of Shipping, Bureau Veritas, Lloyd s Register of Shipping, RegistroItaliano Navale, Germanischer Lloyd s and Det Norske comply with the following standards:nUL 489 Supplement SA.

5 Marine use on vessels over 65 feet in length;nUS Coast Guard specifications;nIEC 92-504 and marine specifications: inclination, vibrations, insulation resistance;nIEC 803 Electromagnetic Disturbance NS circuit breakers comply with NF C 63-100 standard level 2conditions (95% relative humidity at 45 C or 80% at 55 C, hot and humid climateconditions).They also comply with the following standards:nIEC 68-2-30 damp heat;nIEC 68-2-2 dry heat;nIEC 68-2-11 salt spray;nIEC 68-2-1 low degreeCOMPACT NS circuit breakers are certified for operation in pollution degree IIIenvironments as defined by IEC standard 947 (industrial environments).

6 Environmental protectionCOMPACT NS circuit breakers take into account concerns for environmentalprotection. Most components are recyclable and parts are marked as specified inapplicable 50 ~380/415V~Ics=100% IcuUi 750V240V ac480V ac600Y/347V accurrent limiting(see curves in catalog)65k35k18kUTE VDE BS CEI UNE NEMAMERLIN GERINNSF 250 NUL/CSAinterrupting ratingsRMS sym. AmpsIcu85kA36kAUimp 8kVcat A4 COMPACT NS circuit breakerGeneral characteristicsAll COMPACT NS circuit breakers and switches are suitable for isolation as definedin the IEC 947-2 Standard:nThe isolation position corresponds to the O (OFF position);nThe operating handle cannot indicate the OFF position unless the contactsare open.

7 NPadlocks may not be installed unless the contacts are of a rotary handle or a motor mechanism does not alter the functionalityof the position indication isolation function is certified by tests guaranteeing:nThe mechanical reliability of the position indication system;nThe absence of leakage currents;nOvervoltage withstand capacity between upstream and downstream for isolation (positive contact indication)Installation in Class II switchboardsAll COMPACT NS circuit breakers, even when fitted with a rotary handle or a motormechanism, can be installed through the door of Class II IEC switchboards (as perIEC 664 Standard).

8 Refer to circuit breaker installation instructions prior to installingcircuit requires no special insulation because COMPACT NS circuit breakersprovide Class II insulation between the front face and all internal markingCOMPACT NS circuit breaker: functions and characteristicsCircuit breaker marking5 COMPACT NS circuit breakerCircuit breaker current limiting capacityThe limiting capacity of a circuit breaker is its ability tolimit short-circuit current limiting capacityThe exceptional limiting capacity of the COMPACT NS line is due to the doublebreak technique (very rapid natural repulsion of contacts and the appearance of twoarc voltages in series with a very steep wavefront).

9 The exceptional limiting capacity of the COMPACT NS line greatly reduces theforces created by fault currents in devices. The result is a major increase in breakingperformance. In particular, the service breaking capacity Ics is equal to 100% of Ics value, defined by IEC 947-2, is guaranteed by tests comprising the followingoperations:nBreaking a fault current equal to 100% of Icu three times consecutively;nChecking that the device continues to function normally:qConduction of rated current without abnormal temperature rise,qProtection functions perform within the limits specified by the standard,qSuitability for isolation is not service life of electrical installationsE28801 Current limiting circuit breakers greatly reduce the negative effects of short circuitson effectsLess temperature rise in conductors, therefore longer service life for effectsReduced electrodynamic forces.

10 Therefore less risk of electrical contacts or busbarsbeing distorted or effectsLess disturbance for measuring devices located near electrical characteristicsCOMPACT NS circuit breaker: functions and characteristicsprospectiveIscIsctlimited Isc peaklimitedIsctscprospectiveIsc peakactualcurrentprospectivecurrent6 COMPACT NS circuit breakerCOMPACT NS circuit breaker: functions and characteristicsCircuit breakersCOMPACT NSF250H circuit breakerCOMPACT NSJ600L circuit breakerE28017045345048286 Circuit breakers are listed under UL file E63335 and Certified under CSA file LR and interrupting ratingspushtotripUL 489 Listed ratingsCOMPACT circuit breakersNumber of polesRated voltage (V) AC 50/60 HzRated current (A)In40 CInterrupting ratings (kA rms)