Example: stock market

CompactLogix 5380 and Compact GuardLogix 5380 …

Technical DataCompactLogix 5380 and Compact GuardLogix 5380 Controllers SpecificationsSummary of ChangesThis publication was revised to add operating temperature and spacing information for the Compact GuardLogix 5380 controllers. For more information, see page 12 and page 14, 5380 Controller Catalog Numbers5069-L306ER, 5069-L306 ERM, 5069-L310ER, 5069-L310 ERM, 5069-L310ER-NSE, 5069-L320ER, 5069-L320 ERM, 5069-L330ER, 5069-L330 ERM, 5069-L340ER, 5069-L340 ERM, 5069-L350 ERM, 5069-L380 ERM, 5069-L3100 ERMC ompact GuardLogix 5380 Controller Catalog Numbers5069-L306 ERS2, 5069-L306 ERMS2, 5069-L310 ERS2, 5069-L310 ERMS2,5069-L320 ERS2, 5069-L320 ERMS2, 5069-L330 ERS2, 5069-L330 ERMS2, 5069-L340 ERS2, 5069-L340 ERMS2, 5069-L350 ERS2.

2 Rockwell Automation Publication 5069-TD002G-EN-P - January 2019 CompactLogix 5380, Compact GuardLogix 5380, and CompactLogix 5480 Controllers Specifications CompactLogix 5380 Controllers CompactLogix 5380 controllers are part of the Logix 5000™ family of controllers.

Tags:

  5000, Logix, 5000 logix

Information

Domain:

Source:

Link to this page:

Please notify us if you found a problem with this document:

Other abuse

Transcription of CompactLogix 5380 and Compact GuardLogix 5380 …

1 Technical DataCompactLogix 5380 and Compact GuardLogix 5380 Controllers SpecificationsSummary of ChangesThis publication was revised to add operating temperature and spacing information for the Compact GuardLogix 5380 controllers. For more information, see page 12 and page 14, 5380 Controller Catalog Numbers5069-L306ER, 5069-L306 ERM, 5069-L310ER, 5069-L310 ERM, 5069-L310ER-NSE, 5069-L320ER, 5069-L320 ERM, 5069-L330ER, 5069-L330 ERM, 5069-L340ER, 5069-L340 ERM, 5069-L350 ERM, 5069-L380 ERM, 5069-L3100 ERMC ompact GuardLogix 5380 Controller Catalog Numbers5069-L306 ERS2, 5069-L306 ERMS2, 5069-L310 ERS2, 5069-L310 ERMS2,5069-L320 ERS2, 5069-L320 ERMS2, 5069-L330 ERS2, 5069-L330 ERMS2, 5069-L340 ERS2, 5069-L340 ERMS2, 5069-L350 ERS2.

2 5069-L350 ERMS2, 5069-L380 ERS2, 5069-L380 ERMS2, 5069-L3100 ERS2, 5069-L3100 ERMS2, 5069-L320 ERS2K, 5069-L320 ERMS2K, 5069-L330 ERS2K, 5069-L330 ERMS2K, 5069-L350 ERS2K, 5069-L350 ERMS2 KTopicPageSummary of Changes1 CompactLogix 5380 Controllers2 Compact GuardLogix 5380 Controllers8 Controller Use with Other Devices16 Ethernet Node Limits19 CompactLogix 5380 and Compact GuardLogix 5380 Controller Accessories20 Additional Resources232 Rockwell Automation Publication 5069-TD002F-EN-P - June 2018 CompactLogix 5380 and Compact GuardLogix 5380 Controllers SpecificationsCompactLogix 5380 ControllersCompactLogix 5380 controllers are part of the logix 5000 family of controllers.

3 The controllers provide a scalable controller solution to address a wide variety of applications. The applications range from standalone systems to more complex systems with devices that are connected to the controller via an EtherNet/IP network. The controllers are mounted on a DIN rail. They can monitor and control local and remote I/O modules, and other devices connected to an EtherNet/IP network. The CompactLogix 5380 controllers support this functionality: Use of Compact 5000 I/O module as local I/O and remote I/O modules.

4 Use Compact 5000 I/O modules, and other I/O modules, as remote I/O modules. Support for Integrated Motion over an EtherNet/IP network (not all controllers). Use of Dual-IP mode or Linear/DLR mode. Use of two Ethernet ports that let the controller connect to EtherNet/IP device-level and enterprise-level networks. Use of 1784-SD1 or 1784-SD2 Secure Digital (SD) card for nonvolatile memory. USB programming port for temporary Automation Publication 5069-TD002F-EN-P - June 20183 CompactLogix 5380 and Compact GuardLogix 5380 Controllers SpecificationsFeatures - CompactLogix 5380 ControllersFeature5069-L306ER, 5069-L306 ERM5069-L310ER, 5069-L310ER-NSE, 5069-L310 ERM5069-L320ER, 5069-L320 ERM5069-L330ER,5069-L330 ERM5069-L340ER.

5 5069-L340 ERM5069-L350 ERM5069-L380 ERM5069-L3100 ERMC ontroller tasks Continuous Periodic Event32 tasks1000 programs/taskAll event triggersBuilt-in communication ports1 USB port2 Ethernet portsIMPORTANT: Consider the following: When the controller operates in Dual-IP mode, each Ethernet port requires a unique IP address. When the controller operates in Linear/DLR mode, the controller uses only one IP port communicationUSB , Type BFull speed (12 Mbps)Programming, configuration, firmware update, and on-line edits onlyEthernet performance10 Mbps, 100 Mbps, 1 GbpsFull-duplex onlyEtherNet/IP modes supportedDual-IP mode (Available with the Studio 5000 logix Designer application, version or later)Linear/DLR modeEtherNet/IP network topologies supportedDLRStarLinearEtherNet/IP nodes supported, max(1)(1)

6 The maximum number of nodes that are listed represents when the controller is used with the logix Designer application, version 31 or later. Some controllers can be used with earlier logix Designer application versions. The maximum number of nodes that a controller supports can be fewer in logix Designer application, versions 30 or interfaces supported, max32 Integrated motionAs many as two axes(5069-L306 ERM controller only)As many as four axes(5069-L310 ERM controller onlyAs many as eight axes(5069-L320 ERM controller only)As many as 16 axes(5069-L330 ERM controller only)As many as 20 axes(5069-L340 ERM controller only)As many as 24 axesAs many as 28 axesAs many as 32 axesProgramming languagesLadder Diagram (LD)Structured Text (ST))

7 Function Block Diagram (FBD)Sequential Function Chart (SFC)4 Rockwell Automation Publication 5069-TD002F-EN-P - June 2018 CompactLogix 5380 and Compact GuardLogix 5380 Controllers SpecificationsTechnical Specifications - CompactLogix 5380 ControllersAttribute5069-L306ER, 5069-L306 ERM5069-L310ER, 5069-L310ER-NSE, 5069-L310 ERM5069-L320ER, 5069-L320 ERM5069-L330ER,5069-L330 ERM5069-L340ER,5069-L340 ERM5069-L350 ERM5069-L380 ERM5069-L3100 ERMUser MB1 MB2 MB3 MB4 MB5 MB8 MB10 MBOptional nonvolatile memory1784-SD1 card1784-SD2 card (shipped with the controller)

8 Local I/O modules, max881631(5)31313131 MOD Power voltage DCMOD Power current, max450 mAMOD Power inrush850 mA for 125 msMOD Power passthrough(1) A @ DCMOD Power current rating, max10 ADo not exceed 10 A current draw at the MOD Power Power voltage ranges(2) DC AC, HzATEX/IECEX, 125V AC maxSA Power current, max(2)10 mA (DC power)25 mA (AC power)SA Power passthrough(2), (3) A @ A @ AC, HzATEX/IECEX, 125V AC maxSA Power current rating, max (2)10 A (AC or DC power)Do not exceed 10 A current draw at the SA Power dissipation, WThermal dissipation, max29 BTU/hrIsolation voltage300V (continuous), Basic Insulation Type, SA, and MOD Power to Backplane300V (continuous), Basic Insulation Type, SA to MOD Power300V (continuous), Basic Insulation Type, Ethernet to Backplane300V (continuous), Double Insulation Type, Ethernet to MOD Power300V (continuous), Double Insulation Type, Ethernet to SA Power50V (continuous), Functional Insulation Type, Ethernet to USB300V (continuous)

9 , Basic Insulation Type, USB to Backplane300V (continuous), Double Insulation Type, USB to MOD Power300V (continuous), Double Insulation Type, USB to SA PowerNo isolation between Ethernet portsType tested at 1500V AC for 60 sWeight, kg ( lb)Dimensions (HxWxD), x x mm ( x x in.)LocationDIN rail mount (horizontal mount only)DIN railCompatible zinc-plated, chromate steel DIN - 35 x mm ( x in.)Rockwell Automation Publication 5069-TD002F-EN-P - June 20185 CompactLogix 5380 and Compact GuardLogix 5380 Controllers SpecificationsRemovable terminal blockRTBs are available in separately ordered 5069 RTB kits.

10 The MOD power connection uses a 4-point RTB, and the SA power connection uses a 6-point RTB. The following kits are available: Kit catalog number 5069-RTB64-SCREW contains RTB catalog numbers 5069-RTB6-SCREW and 5069-RTB4-SCREW. Kit catalog number 5069-RTB64-SPRING contains RTB catalog numbers 5069-RTB6-SPRING and block torque5069-RTB4-SCREW & 5069-RTB6-SCREW: N m ( lb in)5069-RTB4-SPRING & 5069-RTB6-SPRING: Torque does not applyWire size5069-RTB4-SCREW, 5069-RTB6-SCREW mm2 ( AWG) solid or stranded copper wire that is rated at 105 C (221 F), or greater, mm ( in.)