Technical DataCompactLogix Communication Modules Specifications1768 CompactLogix Catalog Numbers1768-ENBT, 1768-EWEB, 1768-CNB, 1768-CNBR1769 Compact I/O Catalog Numbers1769-SDN, 1769-ADN, 1769-AENTRTo picPageNetworks2 EtherNet/IP Network5 Stratix Switches7 ControlNet Network9 DeviceNet Network12 Serial Network14DH-485 Network152 Rockwell automation Publication 1769-TD007D-EN-P - May 2014 CompactLogix Communication Modules SpecificationsNetworksYou can configure your system for information exchange between a range of devices and computing platforms and operating systems.

CompactLogix 5370 L1 controllers CompactLogix 5370 L2 ... Rockwell Automation Publication 1769-TD007D-EN-P - May 2014 3 CompactLogix Communication Modules Specifications ... EN 61131-2; Programmable Controllers (Clause 8, Zone A & B) European Union 2004/108/EC EMC Directive, compliant with: ...

Tags:

  Controller, Automation, 1967, Rockwell automation, Rockwell, Programmable, 7350, Compactlogix, Programmable controllers, Compactlogix 5370 l1 controllers compactlogix 5370

Information

Domain:

Source:

Link to this page:

Please notify us if you found a problem with this document:

Other abuse

Transcription of CompactLogix Communication Modules ... - Rockwell …

1 Technical DataCompactLogix Communication Modules Specifications1768 CompactLogix Catalog Numbers1768-ENBT, 1768-EWEB, 1768-CNB, 1768-CNBR1769 Compact I/O Catalog Numbers1769-SDN, 1769-ADN, 1769-AENTRTo picPageNetworks2 EtherNet/IP Network5 Stratix Switches7 ControlNet Network9 DeviceNet Network12 Serial Network14DH-485 Network152 Rockwell automation Publication 1769-TD007D-EN-P - May 2014 CompactLogix Communication Modules SpecificationsNetworksYou can configure your system for information exchange between a range of devices and computing platforms and operating systems.

2 Select a CompactLogix controller with integrated Communication or the appropriate Communication device for the networks that meet your Controller1769-L3x Controller1768-L4x, 1768-L4xS ControllerCompactLogix 5370 L1 controllersCompactLogix 5370 L2 controllersCompactLogix 5370 L3 controllers Plant management (material handling) Configuration, data collection, safety, and control on a single, high-speed network Inclusion of commercial technologies (such as video over IP) Internet/Intranet connection EtherNet/IP network 1769-L23E-QB1B controller 1769-L23E-QBFC1B controller 1769-L32E controller 1769-L35E controller 1768-ENBT bridge 1768-EWEB web server 1769-L16ER controller 1769-L18ER controller 1769-L18 ERM controller 1769-L24ER controller 1769-L27 ERM controller 1769-L30ER controller 1769-L30 ERM controller 1769-L33ER controller 1769-L33 ERM controller 1769-L36 ERM controller High-speed transfer of time-critical data between controllers and I/O devices Deterministic and

3 Repeatable data delivery Media redundancy Intrinsic safety Redundant controller systems ControlNet networkNot available 1769-L32C controller (nonredundant media) 1769-L35CR controller (redundant media) 1768-CNB bridge (nonredundant media) 1768-CNBR bridge (redundant media)Not available Connections of low-level devices directly to plant floor controllers, without interfacing them through I/O Modules Data sent as needed More diagnostics for improved data collection and fault detection Less wiring and reduced start-up time than a traditional, hard-wired system DeviceNet network 1769-SDN scanner 1769-ADN adapterNot available1769-SDN scanner Modems Supervisory control and data acquisition (SCADA)

4 Serial network Built-in serial port on the controller 1769-ASCII moduleNot availableConnections to existing DH-485 networks DH-485 networkBuilt-in serial port with a 1761-NET-AIC linking deviceNot availableRockwell automation Publication 1769-TD007D-EN-P - May 20143 CompactLogix Communication Modules SpecificationsTable 1 - Environmental Specifications - 1768 Communication ModulesAttribute1768-ENBT, 1768-EWEB1768-CNB, 1768-CNBRT emperature, operatingIEC 60068-2-1 (Test Ad, Operating Cold),IEC 60068-2-2 (Test Bd, Operating Dry Heat),IEC 60068-2-14 (Test Nb, Operating Thermal Shock) C ( F) Temperature, surrounding air, max60 C (140 F) Temperature, nonoperatingIEC 60068-2-1 (Test Ab, Unpackaged Nonoperating Cold),IEC 60068-2-2 (Test Bb, Unpackaged Nonoperating Dry Heat),IEC 60068-2-14 (Test Na, Unpackaged Nonoperating Thermal Shock) C ( F) Relative humidityIEC 60068-2-30 (Test Db, Unpackaged Nonoperating Damp Heat) noncondensing VibrationIEC 60068-2-6 (Test Fc, Operating)

5 5 g @ Hz Shock, operatingIEC 60068-2-27 (Test Ea, Unpackaged Shock) 30 g Shock, nonoperatingIEC 60068-2-27 (Test Ea, Unpackaged Shock) 50 g EmissionsCISPR 11 (IEC 61000-6-4):Group 1, Class ACISPR 11 (IEC 61000-6-4):Class AESD ImmunityIEC 61000-4-2:6 kV contact discharges8 kV air dischargesIEC 61000-4-2:6 kV contact discharges8 kV air dischargesRadiated RF ImmunityIEC 61000-4-3:10V/m with 1 kHz sine-wave 80% AM from MHz10V/m with 200 Hz 50% Pulse 100% AM at 900 MHz10V/m with 200 Hz 50% Pulse 100% AM at 1890 MHz10V/m with 1 kHz sine-wave 80% AM from MHzEFT/B ImmunityIEC 61000-4-4: 2kV at 5 kHz on communications portsSurge Transient ImmunityIEC 61000-4-5: 2 kV line-earth(CM) on communications portsIEC 61000-4-5: 1 kV line-earth(CM) on communications portsConducted RF ImmunityIEC 61000-4-6.

6 10V rms with 1 kHz sine-wave 80% AM from 150 MHz4 Rockwell automation Publication 1769-TD007D-EN-P - May 2014 CompactLogix Communication Modules SpecificationsTable 2 - Environmental Specifications - 1769 Communication ModulesAttribute1769-AENTR1769-SDN, 1769-ADNT emperature, operatingIEC 60068-2-1 (Test Ad, Operating Cold),IEC 60068-2-2 (Test Bd, Operating Dry Heat),IEC 60068-2-14 (Test Nb, Operating Thermal Shock) C ( F) Temperature, surrounding air, C (140 F) Temperature, nonoperatingIEC 60068-2-1 (Test Ab, Unpackaged Nonoperating Cold),IEC 60068-2-2 (Test Bb, Unpackaged Nonoperating Dry Heat),IEC 60068-2-14 (Test Na, Unpackaged Nonoperating Thermal Shock) C ( F) Relative humidityIEC 60068-2-30 (Test Db, Unpackaged Nonoperating Damp Heat) noncondensing VibrationIEC 60068-2-6 (Test Fc, Operating) 2 g @ Hz Shock, operatingIEC 60068-2-27 (Test Ea, Unpackaged Shock) 15 g30 g Shock, nonoperatingIEC 60068-2-27 (Test Ea, Unpackaged Shock)

7 30 g50 g EmissionsCISPR 11 (IEC 61000-6-4):Class ACISPR 11 (IEC 61000-6-4):Group 1, Class AESD ImmunityIEC 61000-4-2:6 kV contact discharges8 kV air dischargesRadiated RF ImmunityIEC 61000-4-3:10V/m with 1 kHz sine-wave 80% AM from MHz10V/m with 200 Hz 50% Pulse 100% AM at 900 MHz10V/m with 200 Hz 50% Pulse 100% AM at 1890 MHz10V/m with 1 kHz sine-wave 80% AM from MHzIEC 61000-4-3:10V/m with 1 kHz sine-wave 80% AM from MHz10V/m with 200 Hz 50% Pulse 100% AM at 900 MHz1V/m with 1 kHz sine-wave 80% AM from MHzEFT/B ImmunityIEC 61000-4-4: 3 kV at 5 kHz on communications portsIEC 61000-4-4: 2 kV at 5 kHz on communications portsSurge Transient ImmunityIEC 61000-4-5: 2 kV line-earth(CM) on communications portsConducted RF ImmunityIEC 61000-4-6:10V rms with 1 kHz sine-wave 80% AM from 150 MHzIEC 61000-4-6.

8 10V rms with 1 kHz sine-wave 80% AM from 150 MHzRockwell automation Publication 1769-TD007D-EN-P - May 20145 CompactLogix Communication Modules SpecificationsCommunication ConnectionsA ControlLogix system uses connections to establish Communication links between devices. The types of connections include: controller -to-local I/O Modules or local Communication Modules . controller -to-remote I/O or remote Communication Modules . controller -to-remote I/O (rack-optimized) Modules . produced and consumed tags. messages.

9 controller access by RSLogix 5000 programming software. controller access by RSLinx software for HMI or other indirectly determine the number of connections the controller uses by configuring the controller to communicate with other devices in the system. The limit of connections may ultimately reside in the Communication module you use for the connection. If a message path routes through a Communication module, the connection related to the message also counts towards the connection limit of that Communication NetworkThe Ethernet Industrial network protocol (EtherNet/IP) is an open industrial-networking standard that supports both real-time I/O messaging and message exchange.

10 The EtherNet/IP network uses off-the-shelf Ethernet Communication chips and physical controller specifications, see CompactLogix Controllers Specifications, publication your applicationSelect for a 1769-L23x controllerSelect for a 1769-L3x controllerSelect for a 1769-L4x, 1769-L4xS controllerSelect for a CompactLogix 5370 controller Controls standard and safety I/O Modules and drives Requires an adapter for distributed 1756 I/O on EtherNet/IP links Communicates with other EtherNet/IP devices (messages and HMI) Bridges EtherNet/IP links to route messages to devices on other networks 1769-L23E-QB1B or 1769-L23E-QBFC1B controller with integrated EtherNet/IP port1769-L32E or 1769-L35


Related search queries