Cooling/Heat Pump Convertible Air Handlers

PUB. NO. 22-1774-01-0905 (EN) Cooling/Heat PumpConvertibleAir Handlers2/4 TEC3F18-60A1000A1 5 Ton 2005 American Standard Inc. All Rights Reserved222-1774-01-0905 (EN) system TYPE2 = R-224 = R-410 APPLICATIONTE = Fully ConvertibleTG = Semi ConvertibleTF = Front ReturnTV = VerticalPRODUCT FAMILYE = Leadership Variable SpeedP = LeadershipC = Replacement/RetailB = BasicFLOW CONTROL3 = Non-Bleed TXV4 = FCCVFEATURE IDENTIFIER0 = Standard UnitF = Air-TiteFeaturesand Benefits SEER Ships horizontal converts to verticalby standing unit on end. Six-way convertibility horizontal (leftand right), front and rear access;upflow, downflow 1-man installation opportunity Electrical, refrigerant, condensate andblower access Convertible to either side Compact 21" depth for easy installation Corrosion resistant galvanized metalwith attractive finish Superior condensate performance Factory installed non-bleed TXV Enhanced internally finned coil tubes Direct drive motor Multi-speed blower Versatile duct flange allows flush fit3/4", 1" or " duct insulation Filter panel stamped with word filter 200

1 These Air Handlers are ARI certified with various Split System Air Conditioners and Heat Pumps (ARI STANDARD 210/240). Refer to the Split System Outdoor Unit Product Data Guides for performance data. 2 3/4" Male Plastic Pipe (Ref.: ASTM 1785-76) 3 Minimum filter size for horizontal applications will be based on airflow selection and will be ...

Tags:

  System, Pumps, Heat, Handlers, Split, Cooling, Convertible, Split system air, Split system, Cooling heat pump convertible air handlers

Information

Domain:

Source:

Link to this page:

Please notify us if you found a problem with this document:

Other abuse

Transcription of Cooling/Heat Pump Convertible Air Handlers

1 PUB. NO. 22-1774-01-0905 (EN) Cooling/Heat PumpConvertibleAir Handlers2/4 TEC3F18-60A1000A1 5 Ton 2005 American Standard Inc. All Rights Reserved222-1774-01-0905 (EN) system TYPE2 = R-224 = R-410 APPLICATIONTE = Fully ConvertibleTG = Semi ConvertibleTF = Front ReturnTV = VerticalPRODUCT FAMILYE = Leadership Variable SpeedP = LeadershipC = Replacement/RetailB = BasicFLOW CONTROL3 = Non-Bleed TXV4 = FCCVFEATURE IDENTIFIER0 = Standard UnitF = Air-TiteFeaturesand Benefits SEER Ships horizontal converts to verticalby standing unit on end. Six-way convertibility horizontal (leftand right), front and rear access;upflow, downflow 1-man installation opportunity Electrical, refrigerant, condensate andblower access Convertible to either side Compact 21" depth for easy installation Corrosion resistant galvanized metalwith attractive finish Superior condensate performance Factory installed non-bleed TXV Enhanced internally finned coil tubes Direct drive motor Multi-speed blower Versatile duct flange allows flush fit3/4".

2 1" or " duct insulation Filter panel stamped with word filter 200/230 volt primary and24 volt secondary transformerSelectionProcedure Low voltage wire nut connections Insulated cabinet Uses 1400 series heaters External access to heater circuitbreakers Polarized plugs for making electricalconnections from air handler controlbox to heaters Approved for modular or manufacturedhomesUNIT PARTSIDENTIFIERMINOR DESIGNMODIFICATIONFUTURE OPTION Factory Installed HeaterNominal KW ValueELECTRICAL CONNECTION0 = Pig TailsB = Circuit BreakerD = Pull DisconnectPOWER SUPPLY1 = Single PhaseMAJOR DESIGN MODIFICATIONNOMINAL NET cooling CAPACITY (MBTUH)1234567891011121314152 TEC3F18A1000 AAModel Number Nomenclature22-1774-01-0905 (EN)3 ContentsFeatures and Benefits2 Selection Procedure2 Model Number Nomenclature2 General Data42/4 TEC3F18A1000A42/4 TEC3F24A1000A42/4 TEC3F30A1000A42/4 TEC3F36A1000A42/4 TEC3F42A1000A42/4 TEC3F48A1000A52/4 TEC3F60A1000A5 Performance Data6 Electrical Data11 Field Wiring162/4 TEC3F18-60A1000A Convertibility18 Dimensions19 Mechanical Specification Options20422-1774-01-0905 (EN)MODELRATED VOLTS/ 1 INDOOR COIL TypeRows Area (sq.)

3 Ft.)Tube Size (in.)Refrigerant ControlDrain Conn. Size (in.) 2 INDOOR FAN TypeDiameter Width (in.)No. UsedDrive No. SpeedsCFM vs. in Motors Speed Amps AmpsFILTERV ertical ApplicationsFilter Furnished?Type ApplicationsFilter Furnished?Recommended Size 3 REFRIGERANTRef. Line ConnectionsCoupling or Conn. Size in. GasCoupling or Conn. Size in (in.)UncratedWEIGHTS hipping (Lbs.) / Net (Lbs.)GeneralDataMODELRATED VOLTS/ 1 INDOOR COIL TypeRows Area (sq. ft.)Tube Size (in.)Refrigerant ControlDrain Conn. Size (in.) 2 INDOOR FAN TypeDiameter Width (in.)No. UsedDrive No. SpeedsCFM vs. in Motors Speed Amps AmpsFILTERV ertical ApplicationsFilter Furnished?Type ApplicationsFilter Furnished?Recommended Size 3 REFRIGERANTRef.

4 Line ConnectionsCoupling or Conn. Size in. GasCoupling or Conn. Size in (in.)UncratedWEIGHTS hipping (Lbs.) / Net (Lbs.)2/4 TEC3F18A1000A208-230/1/60 See SpecificationsPlate Fin3 - - CopperTXV-NB3/4 NPTC entrifugal9 x 81 Direct - 3 See Fan Performance Table1 - 1/41075200-230/1 - - 20 x 20 x 1 Note 3R-22R-410 ABrazedBrazed5/81/21/41/4H x W x D44 1/2 x 24 x 23-1/2 See Outline Drawing121/1112/4 TEC3F24A1000A208-230/1/60 See SpecificationsPlate Fin3 - - CopperTXV-NB3/4 NPTC entrifugal9 x 81 Direct - 3 See Fan Performance Table1 - 1/41075200-230/1 - - 20 x 20 x 1 Note 3R-22R-410 ABrazedBrazed3/45/85/165/16H x W x D44 1/2 x 24 x 23-1/2 See Outline Drawing121/1112/4 TEC3F30A1000A200-230/1/60 See SpecificationsPlate Fin3 - - CopperTXV-NB3/4 NPTC entrifugal9 x 81 Direct - 3 See Fan Performance Table1 - 1/31075200-230/1 - - 20 x 20 x 1 Note

5 3R-22R-410 ABrazedBrazed3/43/45/165/16H x W x D46-1/2 x 24 x 23-1/2 See Outline Drawing135/1252/4 TEC3F36A1000A200-230/1/60 See SpecificationsPlate Fin3 - - CopperTXV-NB3/4 NPTC entrifugal10 x 71 Direct - 3 See Fan Performance Table1 - 1/31080200-230/1 - - 20 x 20 x 1 Note 3R-22R-410 ABrazedBrazed7/83/43/83/8H x W x D46-1/2 x 24 x 23-1/2 See Outline Drawing135/1252/4 TEC3F42A1000A200-230/1/60 See SpecificationsPlate Fin3 - - CopperTXV-NB3/4 NPTC entrifugal10 x 101 Direct - 3 See Fan Performance Table1 - 1/21075200-230/1 - - 20 x 20 x 1 Note 3R-22R-410 ABrazedBrazed7/83/43/83/8H x W x D53-1/4 x 26 x 23-1/2 See Outline Drawing165/1501 These Air Handlers are ARIcertified with various split SystemAir Conditioners and heat pumps (ARI STANDARD 210/240).

6 Refer tothe split system Outdoor Unit ProductData Guides for performance " Male Plastic Pipe(Ref.: ASTM 1785-76)3 Minimum filter size for horizontalapplications will be based on airflowselection and will be calculated asfollows:Low Velocity Filter:Face area (Sq. Ft.) = CFM / 300 High Velocity Filter:Face area (Sq. Ft.) = CFM / 5002/4 TEC3F36A1000A2/4 TEC3F42A1000A22-1774-01-0905 (EN)5 GeneralDataMODELRATED VOLTS/ 1 INDOOR COIL TypeRows Area (sq. ft.)Tube Size (in.)Refrigerant ControlDrain Conn. Size (in.) 2 INDOOR FAN TypeDiameter Width (in.)No. UsedDrive No. SpeedsCFM vs. in Motors Speed Amps AmpsFILTERV ertical ApplicationsFilter Furnished?Type ApplicationsFilter Furnished?Recommended Size 3 REFRIGERANTRef. Line ConnectionsCoupling or Conn.

7 Size in. GasCoupling or Conn. Size in (in.)UncratedWEIGHTS hipping (Lbs.) / Net (Lbs.)2/4 TEC3F48A1000A200-230/1/60 See SpecificationsPlate Fin3 - - CopperTXV-NB3/4 NPTC entrifugal11 x 101 Direct - 3 See Fan Performance Table1 - 1/21000200-230/1 - - 20 x 20 x 1 Note 3R-22R-410 ABrazedBrazed1-1/87/83/83/8H x W x D53-1/2 x 26 x 23-1/2 See Outline Drawing166/1512/4 TEC3F60A1000A200-230/1/60 See SpecificationsPlate Fin3 - 14 (3-16, 4 TEC) - CopperTXV-NB3/4 NPTC entrifugal11 x 101 Direct - 4 See Fan Performance Table1 - 11050200-230/1 - 20 x 22 x 1 Note 3R-22R-410 ABrazedBrazed1-1/87/83/83/8H x W x D59-1/2 x 26 x 23-1/2 See Outline Drawing170/1551 These Air Handlers are ARI certified with various split system Air Conditionersand heat pumps (ARI STANDARD 210/240).

8 Refer to the split system OutdoorUnit Product Data Guides for performance " Male Plastic Pipe (Ref.: ASTM 1785-76)3 Minimum filter size for horizontal applications will be based on airflow selectionand will be calculated as follows:Low Velocity Filter: Face area (Sq. Ft.) = CFM / 300 High Velocity Filter: Face area (Sq. Ft.) = CFM / 500622-1774-01-0905 (EN)PerformanceDataAirflow Performance2/4 TEC3F24A: Wet Coil, No HeatersEXTERNALSTATICPRESSURE( )AIRFLOW (CFM)VERTICALHORIZONTAL230 VOLTS208 VOLTS230 VOLTS208 :With filter, no horizontal drip traySmall apex baffleSubtract " for downflowAs shipped except without filterSubtract " for horizontal leftAirflow Performance2/4 TEC3F18A: Wet Coil, No HeatersEXTERNALSTATICPRESSURE( )AIRFLOW (CFM)VERTICALHORIZONTAL230 VOLTS208 VOLTS230 VOLTS208 :With filter, no horizontal drip traySmall apex baffleSubtract " for downflowAs shipped except without filterSubtract " for horizontal left22-1774-01-0905 (EN)7 PerformanceDataAirflow Performance2/4 TEC3F36A.

9 Wet coil, No HeatersEXTERNALSTATICPRESSURE( )AIRFLOW (CFM)VERTICALHORIZONTAL230 VOLTS208 VOLTS230 VOLTS208 :With filter, no horizontal drip traySmall apex baffleSubtract " for downflowAs shipped except without filterSubtract " for horizontal leftAirflow Performance2/4 TEC3F30A: Wet Coil, No HeatersEXTERNALSTATICPRESSURE( )AIRFLOW (CFM)VERTICALHORIZONTAL230 VOLTS208 VOLTS230 VOLTS208 :With filter, no horizontal drip traySmall apex baffleSubtract " for downflowAs shipped except without filterSubtract " for horizontal left822-1774-01-0905 (EN)PerformanceDataAirflow Performance2/4 TEC3F42A: Wet Coil, No HeatersEXTERNALSTATICPRESSURE( )AIRFLOW (CFM)VERTICALHORIZONTAL230 VOLTS208 VOLTS230 VOLTS208 VOLTSHI MEDLO HI MEDLO HI MEDLO HI :With filter, no horizontal drip traySmall apex baffleSubtract " for downflowAs shipped except without filterSubtract " for horizontal leftAirflow Performance2/4 TEC3F48A: Wet Coil, No HeatersEXTERNALSTATICPRESSURE( )AIRFLOW (CFM)VERTICALHORIZONTAL230 VOLTS208 VOLTS230 VOLTS208 VOLTSHI MEDLO HI MEDLO HI MEDLO HI :With filter, no horizontal drip traySmall apex baffleSubtract " for downflowAs shipped except without filterSubtract " for horizontal left22-1774-01-0905 (EN)9 PerformanceDataPRESSURE DROP FOR ELECTRIC HEATERSIN AIR HANDLER MODELSNOTES:1.

10 See Product Data or Air Handler nameplatefor approved combinations of Air Handlersand Heaters2. Heater model numbers may have additionalsuffix Performance2/4 TEC3F60A: Wet Coil, No HeatersEXTERNALSTATICPRESSURE( )AIRFLOW (CFM)VERTICALHORIZONTAL230 VOLTS208 VOLTS230 VOLTS208 VOLTSHIMED-H M-LOLOWHIMED-H M-LOLOWHIMED-H M-LOLOWHIMED-H :With filter, no horizontal drip traySmall apex baffleSubtract " for downflowAs shipped except without filterSubtract " for horizontal leftNUMBER OF RACKS12345 AIRFLOWCFMAIR PRESSURE DROPINCHES RACKSHEATERMODEL OFRACKSBAYHTR14051 BAYHTR14082 BAYHTR14102 BAYHTR34102 BAYHTR14153 BAYHTR34153 BAYHTR14194 BAYHTR142551022-1774-01-0905 (EN)PerformanceDataHEATER MODEL NUMBER BAYHTRAir Handler Unit14051408*410*41514191425* = 1 or or Elec.