Example: quiz answers

Copper Cable Limiters (600Vac) Copper/Aluminum …

Current Limiting UL/CSA Fuses Copper Cable Limiters (600 Vac). Copper / aluminum Cable Limiters (250 Vac). Circuit Protection General Purpose UL/CSA Fuses Catalog Number UCL (25XX 75XX) 600 Vac or Less Purpose Fuses Special Catalog Number UCLA 250 Vac or Less Catalog AC Volts Copper Number* Rating Cable Size Cable Terminals Available UCL25XX(1) 600 250 MCM T = Copper crimp tube UCL35XX(1) 600 350 MCM O = Bolt-on blade offset from center UCL50XX(1) 600 500 MCM B = Bolt-on blade, centered UCL75XX(1) 600 750 MCM. UCLA 250 2/0 or 3/0(2) Bolt-on blade, one end offset from center *Contact Edison Customer Satisfaction for availability, Limiters not shown, latest data or information. Fuses & Holders Canadian (1). Choose terminals from " Cable Terminals Available" column to complete catalog number, EXAMPLE: "UCL-25TO" is rated for a "25" 250 MCM Copper Cable and has a "T" tube for crimping and an "O" bolt-on blade, offset from center. Any combination of the three terminals may be selected.

50 Medium Voltage Fuses UL/CSA Fuses Current Limiting UL/CSA Fuses General Purpose Special Purpose Fuses Canadian Fuses & Holders Application Section

Tags:

  Copper, Cable, Aluminum, Limiters, 600vac, Cable limiters, Copper aluminum

Information

Domain:

Source:

Link to this page:

Please notify us if you found a problem with this document:

Other abuse

Transcription of Copper Cable Limiters (600Vac) Copper/Aluminum …

1 Current Limiting UL/CSA Fuses Copper Cable Limiters (600 Vac). Copper / aluminum Cable Limiters (250 Vac). Circuit Protection General Purpose UL/CSA Fuses Catalog Number UCL (25XX 75XX) 600 Vac or Less Purpose Fuses Special Catalog Number UCLA 250 Vac or Less Catalog AC Volts Copper Number* Rating Cable Size Cable Terminals Available UCL25XX(1) 600 250 MCM T = Copper crimp tube UCL35XX(1) 600 350 MCM O = Bolt-on blade offset from center UCL50XX(1) 600 500 MCM B = Bolt-on blade, centered UCL75XX(1) 600 750 MCM. UCLA 250 2/0 or 3/0(2) Bolt-on blade, one end offset from center *Contact Edison Customer Satisfaction for availability, Limiters not shown, latest data or information. Fuses & Holders Canadian (1). Choose terminals from " Cable Terminals Available" column to complete catalog number, EXAMPLE: "UCL-25TO" is rated for a "25" 250 MCM Copper Cable and has a "T" tube for crimping and an "O" bolt-on blade, offset from center. Any combination of the three terminals may be selected.

2 (2). A 4/0 aluminum Cable may be used with a Copper blade-to- aluminum Cable connector. Benefits: Cable Limiter Specifications Cable Limiters help to a maintain electrical service by minimizing Cable damage due to short circuit currents. Voltage Rating: UCL25XX 75XX, 600 Vac Isolates faulted Cable (s) in multiple cables per phase UCLA, 250 Vac Voltage Fuses Medium installations. Several Cable termination types available. Cable Ratings: 250 MCM to 750 MCM Cu - 600 Vac 2/0 or 3/0 Cu - 250 Vac Applications: 4/0 Al - 250 Vac (Cu/Al terminal Residential: 250 Vac Limiters can be used to protect required). individual service cables tapped from a single transformer. Interrupting Rating: 600V - 200,000 Amps RMS. Non-Residential: 600 Vac Cable Limiters should be 250V - 100,000 Amps RMS. specified to protect parallel service cables in 120/208 Vac, 277/480 Vac etc. systems. Current Limiting Holders & Misc. Fuse Blocks, Agency Approvals: Self-certified to UL requirements.

3 Section Application For additional information, visit 49. Copper Cable Limiters (600 Vac). Copper / aluminum Cable Limiters (250 Vac). Current Limiting UL/CSA Fuses General Purpose UL/CSA Fuses Application of Cable Limiters : By industry definition, Cable Limiters do not provide overload For applications having three or more parallel cables- Purpose Fuses protection. Class J and Class L fuses for three or more per-phase, Cable Limiters are installed at each end of each cables-per-phase applications should be considered if Cable . For nonparallel or multiple radial cables, Limiters may overload protection is a concern. This may also be a successfully be applied at the source end of each Cable for Special desirable consideration for aluminum Cable using suitable fault isolation. connectors. When analyzing Cable limiter potential applications, it is not Cable Limiters applied in utility networks and building power unusual to forget that normal and abnormal current through system main parallel service cables are primarily intended Cable Limiters is divided just as it is between cables.

4 To isolate faults in multiple-cables-per-phase installations. Selectivity with upstream overcurrent protection devices is This prevents total power outages until maintenance of seldom of concern. When designing for Cable limiter fault faulted Cable (s) can be scheduled. During the process of isolation to prevent a burn down or unscheduled blackout by Fuses & Holders opening under fault conditions to isolate faulted Cable (s), one faulted Cable , it is desirable to determine the continuous Limiters current limiting action reduces potential for excess rating load (3 hours or more) that the remaining cables must heat damage to unfaulted cables. handle without overheating. Canadian Dimensions - inches Cable Limiters 250 Volts or Less AC. Voltage Fuses Medium Holders & Misc. Fuse Blocks, Cat. No. UCLA. Application Section For additional information, visit 50. Current Limiting UL/CSA Fuses Copper Cable Limiters (600 Vac). Copper / aluminum Cable Limiters (250 Vac). Circuit Protection Cable Limiters 600 Volts or Less AC.

5 Dimensions are shown in inches.*. Tube-Offset Blade (TO)**. General Purpose UL/CSA Fuses Copper Purpose Fuses Special Catalog Cable Number Size* A B C D E F G H J. UCL25TO 250 MCM 1-7/8 1-7/16 3/4 19/32 31/32. 1-1/8. UCL35TO 350 MCM 2 3-5/8 3-3/8 1-5/8 7/8 45/64 1-1/16. 1/4. UCL50TO 500 MCM 2-7/8 1-7/8 1-1/16 53/64 1-3/16 1-5/8. UCL75TO 750 MCM 3-1/2 3-3/4 3-1/2 2-1/2 1-5/16 1-1/16 1-1/2 2. Center Blade-Offset Blade (BO)**. Fuses & Holders Canadian Copper Voltage Fuses Medium Catalog Cable Number Size* A B C D E F G. UCL25BO 250 MCM 1-7/16 31/32. 1-1/8 1-1/8. UCL35BO 350 MCM 3-3/8 3-5/8 1-5/8 1-1/16. 1/4. UCL50BO 500 MCM 1-7/8 1-1/2 1-5/8 1-3/16. UCL75BO 750 MCM 3-1/2 3-3/4 2-1/2 2 2 1-1/2. Tube-Tube (TT). C A B A. Holders & Misc. Fuse Blocks, E. D. Copper Catalog Cable Number Size* A B C D E. UCL25TT 250 MCM 1-7/8 1-7/16 3/4 19/32. Section Application UCL35TT 350 MCM 2 3-5/8 1-5/8 7/8 45/64. UCL50TT 500 MCM 2-7/8 1-7/8 1-1/16 53/64. UCL75TT 750 MCM 3-1/2 2-7/8 2-1/2 1-5/16 1-1/16.

6 *Limiter terminals are silver plated Copper . **Dimensions of "TT", "OO", "TB", etc., terminals are determined by matching appropriate dimensions shown. For additional information, visit 51. Copper Cable Limiters (600 Vac). Copper / aluminum Cable Limiters (250 Vac). Current Limiting UL/CSA Fuses Average Time-Current Curve Cat. No. UCL-(XXXX)-600 Vac General Purpose UL/CSA Fuses Purpose Fuses Special Fuses & Holders Canadian Voltage Fuses Medium Holders & Misc. Fuse Blocks, Application Section For additional information, visit 52. Current Limiting UL/CSA Fuses Copper Cable Limiters (600 Vac). Copper / aluminum Cable Limiters (250 Vac). Circuit Protection Average Time-Current Curve Peak Let-Through Current Curve Cat. No. UCLA and 250V. UCLC. UCLA. AMP. AND. RATING B. 100 100,000. 80,000. INSTANTANEOUS PEAK LET-THRU CURRENTIN AMPS. General Purpose UL/CSA Fuses 60,000. 40,000. 30,000. 20,000. 10. 10,000. 8,000. 6,000. TIME IN SECONDS. 4,000. Purpose Fuses Special 3,000.

7 1 A. 2,000. 1,000. 1,000. 2,000. 4,000. 6,000. 8,000. 10,000. 20,000. 30,000. 40,000. 60,000. 80,000. 100,000. 200,000. RMS SYMMETRICAL CURRENTS IN AMPS. A B=ASYMMETRICAL AVAILABLE PEAK ( x SYMM RMS AMPS)..1. Fuses & Holders Canadian .01. 10,000. 10. 100. 1,000. RMS SYMMETRICAL CURRENT IN AMPS. Voltage Fuses Medium Holders & Misc. Fuse Blocks, Section Application For additional information, visit 53.