Example: stock market

CP12170 - Vision Batt

CP12170 . Shenzhen Center Power 12V 17Ah(20hr). ,. Overview The rechargeable batteries are lead-lead dioxide systems. The dilute sulfuric acid electrolyte is absorbed by separators and plates and thus immobilized. Should the battery be accidentally overcharged producing hydrogen and oxygen, special oneway valves allow the gases to escape thus avoiding excessive pressure build-up. Otherwise, the battery is completely sealed and is, therefore, maintenance-free, leak proof and usable in any position. Battery Construction Component Positive plate Negative plate Container Cover Safety valve Terminal Separator Electrolyte Raw material Lead dioxide Lead ABS ABS Rubber Copper Fiberglass Sulfuric acid General Features Battery Specification Absorbent Glass Mat (AGM) technology for efficient gas Performance Characteristics recombination of up to 99% and freedom from Nominal Voltage 12V. electrolyte maintenance or water adding. Number of cell 6. Not restricted for air transport-complies with IATA/ICAO.

Shenzhen Center Power Tech.Co.Ltd,. Shenzhen Center Power Tech.Co.Ltd,. STOCK CODE: 002733 www.vision-batt.com CP12170 12V 17Ah(20hr) Self-discharge characteristic

Tags:

  Vision, Cp12170

Information

Domain:

Source:

Link to this page:

Please notify us if you found a problem with this document:

Other abuse

Transcription of CP12170 - Vision Batt

1 CP12170 . Shenzhen Center Power 12V 17Ah(20hr). ,. Overview The rechargeable batteries are lead-lead dioxide systems. The dilute sulfuric acid electrolyte is absorbed by separators and plates and thus immobilized. Should the battery be accidentally overcharged producing hydrogen and oxygen, special oneway valves allow the gases to escape thus avoiding excessive pressure build-up. Otherwise, the battery is completely sealed and is, therefore, maintenance-free, leak proof and usable in any position. Battery Construction Component Positive plate Negative plate Container Cover Safety valve Terminal Separator Electrolyte Raw material Lead dioxide Lead ABS ABS Rubber Copper Fiberglass Sulfuric acid General Features Battery Specification Absorbent Glass Mat (AGM) technology for efficient gas Performance Characteristics recombination of up to 99% and freedom from Nominal Voltage 12V. electrolyte maintenance or water adding. Number of cell 6. Not restricted for air transport-complies with IATA/ICAO.

2 Design Life 5 years Special Provision A67. Nominal Capacity 77 (25 ). UL-recognized component. 20 hour rate ( , ) 17Ah Can be mounted in any orientation. 10 hour rate ( , ) Computer designed lead, calcium tin alloy grid for high 5 hour rate ( , ) power density. 1 hour rate (12A, ) 12Ah Long service life, float or cyclic applications. Internal Resistance Maintenance-free operation. Fully Charged battery 77 (25 ) 14 mOhms Low self discharge. Self-Discharge Case and cover available in both standard and flame 3% of capacity declined per month at 20 (average). retardant ABS. Operating Temperature Range Discharge -20~60 . Charge -10~60 . Storage -20~60 . Dimensions and Weight Max. Discharge Current 77 (25 ) 225A(5s). Short Circuit Current 850A. Length(mm / inch) 181 / Charge Methods: Constant Voltage Charge 77 (25 ). Width(mm / inch) 77 / Cycle use Height(mm / inch) 167 / Maximum charging current Total Height(mm / inch) 167 / Temperature compensation -30mV/ . Approx.

3 Weight(Kg / lbs) / Standby use * Weight deviation: 5% Temperature compensation -20mV/ . Discharge Constant Current (Amperes at 77oF25oC). End Point Volts/Cell 5min 10min 15min 30min 1h 3h 5h 10h 20h Discharge Constant Power (Watts at 77oF25oC). End Point Volts/Cell 5min 10min 15min 30min 45min 1h 2h 3h 5h 117 113 110 106 102 (Note)The above characteristics data are average values obtained within three charge/discharge cycles not the mimimum data shall be changed without notice, Vision reserves the right to explain and update the information contained hereinto. Shenzhen Center Power ,. STOCK CODE: 002733 CP12170 . Shenzhen Center Power 12V 17Ah(20hr). ,. Discharge characteristic (25 C). O. Voltage(v). 35. 0. 0 1 2 3 5 10 20 30 60 2 3 5 0 1 20 30. min h Discharge time Relationship between Self-discharge characteristic charging voltage and temperature 110. 100. 90. Capacity(%). Cycl Voltage(V). e Us e 80. 70. Stan d b y Us e 60 o o o C C C. 50. 40. -10 0 10 20 30 40 50 60 0 2 4 6 8 10 12 14 16 18 20.

4 Ambient temperature( oC) Storage time: months Cycle service life in relation to Life characteristics of Standby use 120 depth of discharge 120. 100. 100. Capacity(%). 80. Capacity(%). 80. 60 60. Testing conditions:floating to Cell 100% . 50% . 30% Depth of discharge ambient temperature: 25oC(77oF). 40 40. 20 20. 0 200 400 600 800 1000 1200 1400. 0 1 2 3. Life(year) Number of cycles(cycles). Temperature effects on float life Temperature effects on capacity 10. 120. 100. C. 0 .0 5. Life(years). 0 .1 C. Capacity (%). 80. Cell C. 1 60. 1 .0 C. 40. 2 .0 C. 3 .0 C. 20. 0. 10 20 30 40 50 60. -20 -10 0 10 20 30 40 50( o C). o Temperature( C) Temperature( oC). Shenzhen Center Power ,. STOCK CODE: 002733