Example: confidence

CROSS-CONNECTION CONTROL RISK ASSESSMENT …

CROSS-CONNECTION CONTROL RISK ASSESSMENT CHARTS A. General Fire Sprinkler/Standpipe System Are there any provisions for chemicals to be used in the fire system? (Ex. anti-freeze, foam systems, rust inhibitors) NO YES Install RPDA Is the Fire Siamese connection located within 700 feet of an uncertified water supply?

Rev.05/2017 CROSS-CONNECTION CONTROL RISK ASSESSMENT CHARTS A. General Fire Sprinkler/Standpipe System Are there any provisions for chemicals

Tags:

  Assessment, Chart, Cross, Control, Risks, Connection, Cross connection control risk assessment charts, Cross connection control risk assessment

Information

Domain:

Source:

Link to this page:

Please notify us if you found a problem with this document:

Other abuse

Advertisement

Transcription of CROSS-CONNECTION CONTROL RISK ASSESSMENT …

1 CROSS-CONNECTION CONTROL RISK ASSESSMENT CHARTS A. General Fire Sprinkler/Standpipe System Are there any provisions for chemicals to be used in the fire system? (Ex. anti-freeze, foam systems, rust inhibitors) NO YES Install RPDA Is the Fire Siamese connection located within 700 feet of an uncertified water supply?

2 (Ex. Lake, Creek, River, Bay, Fire Cistern, Pond) YES Install RPDA NO Does the Facility have a Fire Well? YES Install RPDA Is the fire service cross -connected to a hazardous domestic service on the house side of BFP assemblies? YES Install RPDA DCDA = approved Double Check Detector Assembly RPDA = approved Reduced Pressure Detector Assembly Install DCDA NO NO Premises Residential Mixed Use YES NO Is the Premise rated as Aesthetically Objectionable?

3 Is the Nature of Occupancy Categorically Hazardous? Ex.: Hospitals, Medical Offices, Laundry, Sewage Treatment Plants, Mortuaries and most Industrial Concerns. (See Typical Significant Risk of Hazards for more examples in the Handbook) Request an Exemption as per requirements Non-Residential Does the premise maintain any hazardous fixtures? Ex.: Bidet, Swimming Pool, Irrigation System, Cooling Tower, Large Boiler, Coin-Operated Laundry Machines, well?

4 (See ASSESSMENT of Residential Dwelling for more examples and details in the Handbook) NO YES Install RPZA Yes Install DCVA Install RPZA Install DCVA Yes DCVA = approved Double Check Valve Assembly RPZA = approved Reduced Pressure Zone Assembly Is the Premise rated as Non- Hazardous?


Related search queries