Example: marketing

CSIRO Verification Services Highett, Victoria, Australia ...

CSIRO Verification Services highett , victoria , Australia +61 (0)3 9252 6000. Certificate of Conformity Certificate num. Registration date Version Valid until Number Issue date Page 1 of 4. afp - 2131 1-Aug-2007 7 16-Dec-2012 30-Apr-2013. This certification is issued within Product designation the scope of CSIRO Verification Services Rules governing Ansul, Sapphire 25 Bar, Unbalanced-engineered total flooding, using 3M ActivFire Scheme and is valid only Novec 1230 extinguishing agent, fixed fire extinguishing system for the product(s) as submitted for evaluation and Verification of (Refer to the Schedule/enclosures for further specified details) conformity, subject to the following conditions.

Schedule to Certificate of Conformity Certificate num. Registration date Version Valid until afp - 2131 1-Aug-2007 Page 3 of 4 Number Issue date 7 16-Dec-2012 30-Apr-2013

Tags:

  Services, Verification, Australia, Victoria, Corsi, Csiro verification services highett, Highett

Information

Domain:

Source:

Link to this page:

Please notify us if you found a problem with this document:

Other abuse

Transcription of CSIRO Verification Services Highett, Victoria, Australia ...

1 CSIRO Verification Services highett , victoria , Australia +61 (0)3 9252 6000. Certificate of Conformity Certificate num. Registration date Version Valid until Number Issue date Page 1 of 4. afp - 2131 1-Aug-2007 7 16-Dec-2012 30-Apr-2013. This certification is issued within Product designation the scope of CSIRO Verification Services Rules governing Ansul, Sapphire 25 Bar, Unbalanced-engineered total flooding, using 3M ActivFire Scheme and is valid only Novec 1230 extinguishing agent, fixed fire extinguishing system for the product(s) as submitted for evaluation and Verification of (Refer to the Schedule/enclosures for further specified details) conformity, subject to the following conditions.

2 Agent/distributor Reference to details, limitations and requirements, where Tyco Fire Protection Products documented as a 567 Somerville Road, SUNSHINE, VIC, Australia , 3020 schedule/enclosure with this certificate. Registrant The Registrant is responsible for their attestation of Ansul Incorporated conformity and ensuring that on-going production complies One Stanton Street, MARINETTE, WI, UNITED STATES, 54143-2542 with the conformance criteria Producer defined in this certificate. This certificate will not be valid Ansul Incorporated if any changes or modifications One Stanton Street, MARINETTE, WI, UNITED STATES, 54143-2542 are made to the product which have not been notified and validated by CSIRO Verification Conformance criteria and evaluation Services .

3 The Ansul, Sapphire 25 Bar, Unbalanced-engineered total flooding, using 3M Novec This certificate is subject to 1230 extinguishing agent, fixed fire extinguishing system has been evaluated and verified periodical re-validation upon Verification that all as conforming with the relevant requirements of the following criteria. requirements, as determined by the conformity assessment 1. Australian Standard AS 4214-2002, 'Gaseous fire extinguishing systems'. body, continue to be 2. Factory Mutual - Evaluation, surveillance and approval, 'FM approval'.

4 Satisfactorily met by the Registrant. 3. SSL Appraisal Specification FAS-102, Version , 'Gaseous Extinguishing Systems'. This certificate may only be reproduced in its published Limitations/conditions of conformance form, without modification and inclusive of all Limitations/conditions of conformance, where identified on this certificate, are derived from qualifications schedules/enclosures. from evaluation(s) for conformity and/or other related technical documentation. All details with respect to Any changes, errors or design, assembly and installation instructions and restrictions should be checked against the producer's omissions, must be submitted current technical manual/data sheets and the requirements of the Authority having Jurisdiction.

5 In writing and if necessary or Specified limitations/conditions, determined from the evaluation for conformity, include the requested, substantiated with relevant evidence. following. Any representations, such as i. Systems shall be designed, installed, operated, and maintained, in accordance with advertising or other marketing the ANSUL's Sapphire Program and Sapphire Engineered Clean Agent System related activities or articles shall reflect the correct design, Installation, Recharge and maintenance manual, Part number 570590, dated contents of this certificate and December 1, 2003.

6 Conform with all relevant trade practices .and consumer ii. System operating temperatures: -18 C to 54 C. protection legislation and iii. Boiling point of Novec 1230 gaseous agent is 49 C (liquid at room temperature). regulations. Any terms or conditions of use (Limitations/conditions of conformance continue) as applicable to content and documentation as published or accessed through web sites administered by the CSIRO . Issued by Verification Services . David Whittaker Executive Officer ActivFire Scheme CSIRO Australia , 2011.

7 This certificate remains the property of CSIRO and may be subject to amendment, suspension or withdrawal at any time. The validity and authenticity of this certificate can be verified by the certification register located at Schedule to Certificate of Conformity Certificate num. Registration date Version Valid until Number Issue date Page 2 of 4. afp - 2131 1-Aug-2007 7 16-Dec-2012 30-Apr-2013. iv. The Novec 1230 storage containers shall not be transported or handled in situations where the temperature will be less than minus 20 C or more than 50 C.

8 V. Discharge time: maximum 10 sec, minimum 6 sec. vi. Maximum filling density is 75 lbs/ft3 and the minimum is 31 lbs/ft3. vii. The Novec 1230 concentration achieved in the enclosure shall be not less than for any risk. viii. Maximum run-out imbalance: 2 seconds. ix. Maximum pipe volume to cylinder liquid volume: 80%. x. Maximum pipe volume ratio before first tee: 10%. xi. Maximum nozzle height above floor level for a single row of nozzles is m. For ceiling heights over m, additional rows of nozzles may be added.

9 Xii. Maximum linear nozzle coverage: x m. xiii. Minimum ceiling height: cm. xiv. Minimum Class A design concentration: xv. Maximum design concentration for occupied spaces: 10%. Ansul, Sapphire 25 Bar, Unbalanced-engineered total flooding, using 3M Novec 1230 extinguishing agent, fixed fire extinguishing systems installed in Australia and New Zealand are subject to the following additional requirements: i. Sapphire containers shall only be filled and serviced by accredited refill stations. ii. Installation and service of the ANSUL Sapphire 25 Bar Engineered, Unbalanced Fire Extinguishing System, using 3M Novec 1230 Fire Protection Fluid, shall be carried out by technicians/staff accredited by Ansul Inc.

10 In the handling of pressurized containers and the system installation and service manuals. iii. Design of the the ANSUL Sapphire 25 Bar Engineered, Unbalanced Fire Extinguishing System, using 3M . Novec 1230 Fire Protection Fluid, shall be carried out by staff accredited by Ansul Inc. using the Ansul's Sapphire Designer Program. Producer's description The Ansul, Sapphire 25 Bar, Unbalanced-engineered total flooding, using 3M Novec 1230 extinguishing agent, fixed fire extinguishing system is used to protect hazards, which may be either normally occupied or unoccupied.