Transcription of Datasheet 205-6 Eclipse ThermJet Burners
1 1. See Design Guide 205 for more information about typical fuel composition and properties All information is based on laboratory testing in neutral (0 " , 0 mbar) pressure chamber. Different chamber conditions may affectthe data. All information is based on standard combustor design. Changes in combustor will alter performance and pressures. All inputs based upon gross calorific values and standard conditions; 1 atmosphere, 70 F (21 C). Eclipse reserves the right to change the construction and/or configuration of our products at any timewithout being obliged to adjust earlier supplies accordingly. Plumbing of air and gas will affect accuracy of orifice readings. All information is based ongenerally acceptable air and gas piping VelocityModel TJ0150 Maximum Input, Btu/h (kW)Medium & High Velocity1,500,000 (440)Minimum Input On-Ratio, Btu/h (kW)Medium & High Velocity150,000 (44)Minimum Input Fixed Air, Btu/h (kW)Medium & High Velocity30,000 (9)Gas Inlet Pressure Required, " (mbar)Tap B (see page 3)High VelocityNatural ( ) ( ) ( )Medium VelocityNatural ( ) ( ) ( )Air Inlet Pressure Required, " (mbar)15% Excess Air at Maximum InputTap A (see page 3)High VelocityNatural ( ) ( ) ( )Medium VelocityNatural ( ) ( ) ( )High Fire Flame Length, inches (mm)Measured from the outlet end of the combustorHigh VelocityNatural Gas38 (965)Propane42 (1065)Butane43 (1090)Medium VelocityNatural Gas43 (1090)Propane42 (1065)Butane44 (1120)Approximate Flame Velocity, ft/s (m/s)15% Excess Air at Maximum InputHigh Velocity680 (207)Medium Velocity350 (107)Maximum Combustion Air Temperature300 (149 C).
2 For higher temperatures use TJPCA ( Datasheet 206).Flame DetectionFlame rods can be used with all alloy and SiC combustors, natural gas and operating temperatures up to 2,200 F (1,204 C). UV scanners can be used with all combustors, any fuel listed below, and up to the maximum operating temperature. Certain piping configurations prohibit the use of a flamerod, see page 3 for any other mixed gas, contact Eclipse , gas, propane or butane1 ApprovalsEclipse ThermJetBurnersModel TJ0150 Version 205-62 Eclipse ThermJet TJ0150, , Datasheet 205-6 , 2/11/2013 Performance Graphs101001,00010,000015001800300600900 1200 Input (x 1,000 Btu/h)Ignition & Operational Zones% Excess Air0250 30050100 150 200 Input (kW)500 550350 400 450020406080100120140 NOX ppm (at 3% O2)NOX Emissions(High Velocity Combustor)03006009001,2001,500 Input (x 1,000 Btu/h)022575150 Input (kW)3000450375 NOX - Natural GasNOX - Propane/Butane12345603006009001,200 1,5001,800 Fuel Orifice P vs.
3 Input( P Measured Between Taps B and D) P (" 5%)0 Natural Gas P - 20 mm orificePropane P - 18 mm orificeButane P - 16 mm orifice 0250 30050 100 150 200 Input (kW)500 550350 400 P (mbar 5%) ,200 1,500 1,800 Air Orifice P vs. Input( P Measured Between Taps A and C)15% Excess Air at Maximum Input0250 30050 100 150 200 Input (kW)500 550350 400 P (mbar 5%) P (" 5%) (x 1,000 Btu/h)Input (x 1,000 Btu/h)Ignition and Operational ZoneAir Orifice (66 mm)Emissions correction factor for medium velocity combustoris Emissions data based on, on-ratio control firing at 15%excess air corrected to 3% from the burner are influenced by: Fuel type Combustion air temperature Firing rate Chamber conditions Percent of excess airFor estimates of other emissions, contact ThermJet TJ0150, , Datasheet 205-6 , 2/11/2013 Dimensions and SpecificationsDimensions in mm (inches) 220 ( )4 x 12 ( ) 190 ( )1-1/2" NPT or BSP3" NPTor BSP81( )140( )105( )95( )240( )Tap DTap BTap ATap C10 ( ) burner weight less combustor.
4 42 lbs (19 kg) burner HousingTap Locations1/2" NPT Flame Rod orUV Scanner AdapterSpark PlugM14 Gas InletAir Inlet90 If using a flame rod, do not installthe burner with the gas inlet at0 or rotated 90 clockwise withrespect to the air inletDatasheet 205-6 , 2/11/2013 Dimensions and SpecificationsDimensions in mm (inches)165( )219( )4 x 14 ( )267( )305(12)50 (2)10 ( ) 141( )4 x 12 ( ) 190( )220( ) 148( )Silicon Carbide Combustor Weight: lbs ( kg)Maximum Chamber Temp: 2,500 F (1,371 C)Refractory Combustor with AISI 330 wrapperWeight: lbs ( kg)Maximum Chamber Temp: 2,800 F (1,538 C)Alloy Combustor (AISI 310)Weight: lbs ( kg)Maximum Chamber Temp: 1,750 F (950 C)CombustorsExhaust outlet diameter:High Velocity: 64 ( )Medium Velocity: 89 ( )229( ) 222( )4 x 12 ( ) 190( )6( )4 x 14( ) 380(15) 330(13) 230( ) 272( )166( )220( )10( )Down Firing Block with AISI 330 wrapperWeight: 75 lbs (34 kg)Maximum Chamber Temp: 2,800 F (1,535 C)