Example: air traffic controller

DC/AC Inverters, AC/AC Frequency Converters and Static ...

DC/AC Inverters with single phase output from 200 VA to 10 kVAPage 80 Series CI is a combination of a switch mode converter and inverter (internal circuit see page 97). The converter provides the isolation between input and output and transforms the voltage to the level needed by the inverter for supplying the specifi ed AC output outputDC inputConverter InverterSeries IT is a combination of a switch mode inverter (internal circuit see page 97) and a Transformer at the output. The transformer provides the isolation between input and output and transforms the voltage to the required outputDC inputInverter TransformerFor lower input voltages the CI version is more compact than the IT Inverters with 3-phase output from 600 VA to 30 kVAPage 82 Series IVis a combination of 3 individual switch mode inverters with output transformers synchronized for a symmetrical 3-phase output.

For example: 1 input voltage = 3 x 200 VAC, 60 Hz 2 output voltage = 3 x 400 VAC, 400 Hz @ 6 kVA 3 results in a IV 5868 V 4 for 400 Hz add .4, i.e. IV 5868 V.4 Assistance in table use: 1 Select the column for input voltage range. 2 Select the row for the appropriate output voltage and power. 3 The intersection of both results in the module required. 4 Add the required frequency designation to ...

Tags:

  Converter, Frequency, Static, Inverter, Ac ac frequency converters and static

Information

Domain:

Source:

Link to this page:

Please notify us if you found a problem with this document:

Other abuse

Transcription of DC/AC Inverters, AC/AC Frequency Converters and Static ...

1 DC/AC Inverters with single phase output from 200 VA to 10 kVAPage 80 Series CI is a combination of a switch mode converter and inverter (internal circuit see page 97). The converter provides the isolation between input and output and transforms the voltage to the level needed by the inverter for supplying the specifi ed AC output outputDC inputConverter InverterSeries IT is a combination of a switch mode inverter (internal circuit see page 97) and a Transformer at the output. The transformer provides the isolation between input and output and transforms the voltage to the required outputDC inputInverter TransformerFor lower input voltages the CI version is more compact than the IT Inverters with 3-phase output from 600 VA to 30 kVAPage 82 Series IVis a combination of 3 individual switch mode inverters with output transformers synchronized for a symmetrical 3-phase output.

2 The transformers provide the isolation between input and output and transform the voltages to the required outputDC3 x Inverter3-phase3 x TransformerinputFrequency Converters with single phase output from 500 VA to 12 kVAPage 84 Series CI is a combination of a switch mode converter and inverter (internal circuit see page 97). The converter provides the isolation between input and output and transforms the voltage to the level needed by the inverter for supplying the specifi ed AC output outputAC inputConverter InverterSeries IT is a combination of a switch mode inverter (internal circuit see page 97) with a rectifi er at the input and a Transformer at the output. The transformer provides the isolation between input and output and transforms the voltage to the required outputAC inputInverter TransformerFrequency Converters with 3-phase output from to 36 kVAPage 86 Series IVis a combination of 3 individual switch mode inverters, each with input rectifi er and output transformer, synchronized for a symmetrical 3-phase output.

3 The transformers provide the isolation between input and output and transform the voltages to the required levels. AC outputAC input3 x Inverterwith inputrectifi er3-phase3 x Transformer1 or Switches from 800 VA to 10 kVAPage 88 Series SSprovides uninterrupted AC power to a critical load by connecting the load to AC supply 1 which can be the inverter output or to AC supply 2 which can be the mains. AC outputAC supply 1AC supply 2static switch1-phaseDC/AC Inverters, AC/AC Frequency Converters and Static SwitchesSchaefer, Inc. 45 South Street, Hopkinton, MA 01748, USA Tel: 508-435-6400 Fax: 508-435-6401 cationsDC/AC Inverters and AC/AC Frequency ConvertersOptions (details see page 90 92)MechanicsSeries CISeries ITSeries IVEurocassetteH15 and high currrent connector for I > 50 AH15, high current connector for I > 50 A and F24H7--Wall mountTerminalsTerminalsTerminals19 plug-in moduleTerminalsTerminalsTerminals19 sub-rackTerminalsTerminalsTerminalsSerie s CI, IT and IVConnector (details see page 103)InputVoltage range.

4 See tables, unit switches off at under- and overvoltageNo-load input power.. 10 30 WInrush current .. AC input: limited by thermistorHold-up time .. AC input: 10 ms typicalImmunity- ESD.. acc. to DIN / EN 61000-4-2 level 3- Fast transients .. acc. to DIN / EN 61000-4-4 level 3- Surges .. acc. to DIN / EN 61000-4-5 level 3 OutputLine regulation ( 10 %) .. % for series CI,2 % for series IT and IVLoad regulation (10 90 %) .. 1 % typical, 3 % max. (400 Hz: 3 % typical, 5 % max.)Turn-on rise time .. Soft-start, 100 ms typicalWaveform.. sine wave or any wave shape programmable by external signalFrequency .. 40 400 Hz: adjustable / programmable or any fi xed Frequency (crystal stabilized)Distortion.. 3 % typical, 5 % @ 400 Hz, 7 % @ 40 400 HzOverload protection (steady state).

5 Current limited to approx. x InomSurge power .. 2 x Pnom for 1 sShort circuit protection .. electronically limited to 3 x Inom, unit switches off after 1 sCrest factor.. approx. 3 Power factor .. cos inductive / capacitiveGeneralEffi ciency .. 75 94 %Operating temperature .. 20 to +75 CLoad derating .. % / C from +55 CStorage temperature .. 40 to +85 CHumidity .. up to 95 % RH, non-condensingSafety / Construction.. acc. to DIN / EN 60950-1: 2003 Protection category .. IP 20, others or NEMA upon requestEMI .. acc. to EN 55022, class A, optionally class BMarking .. CEInput Inrush current limiting for DC input Reverse polarity protection for DC input Autoranging for 115 / 230 VAC input Special circuit for Hz AC inputOutput Inhibit (remote on / off) Static Switch (details see page 88)Signalsvia relay contacts Power ok (input) AC ok (output)ProgrammingOutput voltage, current or Frequency via Potentiometer Analog signal Interface card RS232 or IEEE488 MonitoringInput / output voltage, current or Frequency via Analog signal Interface card RS232 or IEEE488 Mechanics / environment: 19 sub-rack for eurocassette, refer to page 93 Wall mount Increased mechanical strength Tropical protection Extended temperature range to 40 C Temperature controlled fans for 19 unitsSchaefer, Inc.

6 45 South Street, Hopkinton, MA 01748, USA Tel: 508-435-6400 Fax: 508-435-6401 More detailed drawings see example:1 input voltage = 3 x 200 VAC, 60 Hz2 output voltage = 3 x 400 VAC, 400 Hz @ 6 kVA3 results in a IV 5868 V4 for 400 Hz add .4, IV 5868 in table use:1 Select the column for input voltage Select the row for the appropriate output voltage and The intersection of both results in the module Add the required Frequency designation to the part VAC1-PhaseOutput kVASizeInput VAC1-PhaseInput VAC3-PhaseOutput kVASizeCoolingOutputVACline-to-line 115 20 % 230 + 15 % 20 % 3x200 + 15 % 20 %3x400 + 15 % 20 %3x480 + 10 % 15 %IV 5566IV 5666IV 5766IV 5866IV 6266IV 6466 3 6 915 ACD+T1E + T2G+T3G+T5IV 5586IV 5686IV 5786IV 5886IV 6286IV 6486IV 5566 VIV 5666 VIV 5766 VIV 5866 VIV 6266 VIV 6466 VIV 5686 VIV 5786 VIV 5886 VIV 5886 VFIV 6286 VIV 6486 VIV 6686 VIV 5796 VIV 5896 VIV 5896 VFIV 6296 VIV 6496 VIV 6696 V 7.

7 510152436 ACD+T2E + T3F + T4G + T5G+T6G+T7 3 x 200IV 5568IV 5668IV 5768IV 5868IV 6268IV 6468 3 6 915 ACD+T1E + T2G+T3G+T5IV 5588IV 5688IV 5788IV 5888IV 6288IV 6488IV 5568 VIV 5668 VIV 5768 VIV 5868 VIV 6268 VIV 6468 VIV 5688 VIV 5788 VIV 5888 VIV 5888 VFIV 6288 VIV 6488 VIV 6688 VIV 5798 VIV 5898 VIV 5898 VFIV 6298 VIV 6498 VIV 6698 V 7. 510152436 ACD+T2E + T3F + T4G + T5G+T6G+T73 x 400IV 5569IV 5669IV 5769IV 5869IV 6269IV 6469 3 6 915 ACD+T1E + T2G+T3G+T5IV 5589IV 5689IV 5789IV 5889IV 6289IV 6489IV 5569 VIV 5669 VIV 5769 VIV 5869 VIV 6269 VIV 6469 VIV 5689 VIV 5789 VIV 5889 VIV 5889 VFIV 6289 VIV 6489 VIV 6689 VIV 5799 VIV 5899 VIV 5899 VFIV 6299 VIV 6499 VIV 6699 V 7. 510152436 ACD+T2E + T3F + T4G + T5G+T6G+T73 x 480 = natural convection = temperature controlled fansSeries IV Switch mode inverters with output transformers for isolation and voltage transformationFrequency Converters (AC / AC Inverters) with 3-phase outputFrequency Designation (output)AC outputAC input3 x Inverterwith inputrectifi er3-phase3 x Transformer1 or - 400 Hz adjustable / programmable45 - 65 Hz adjustable / programmableany fi xed Frequency between 40 - 400 Hz400 Hz50 Hzsynchronized with 50 Hz mains60 Hzsynchronized with 60 Hz mains50/60 Hz switchableFeatures AC input: 1 or 3-phase, 47 400 Hz AC output.

8 200 / 400 / 480 V, 3-phase 40 400 Hz or fi xed Frequency (crystal stabilized) Sine wave Continuous short circuit protection Thermal shutdown with auto restart for inverter systems > 2 kVA Industrial grade components Suitable for complex load Surge power capability Unsymmetrical load permissible Modular system with interchangeable invertersSchaefer, Inc. 45 South Street, Hopkinton, MA 01748, USA Tel: 508-435-6400 Fax: 508-435-6401 56663 CIV 5686IV 5666 VIV 5686 58666E + T2IV 5886IV 5866 VIV 5886 VIV 5896 + T3IV 62669G+T3IV 6286IV 6266 VIV 6286 VIV 6296 V15G + T5IV 6686 VIV 6696 V36G+T7IV 56683 CIV 5688IV 5668 VIV 5688 58686E + T2IV 5888IV 5868 VIV 5888 VIV 5898 + T3IV 62689G+T3IV 6288IV 6268 VIV 6288 VIV 6298 V15G + T5IV 6688 VIV 6698 V36G+T7IV 56693 CIV 5689IV 5669 VIV 5689 58696E + T2IV 5889IV 5869 VIV 5889 VIV 5899 + T3IV 62699G+T3IV 6289IV 6269 VIV 6289 VIV 6299 V15G + T5IV 6689 VIV 6699 V36G+T786 Frequency Converters (AC / AC Inverters) with 3-phase output19 sub-rackincluding pluggable inverters and transformers, approx.

9 27 kgwith wall plate (optional)approx. 31 kg19"6U350 mm500 mm400 mm310 mm19 Plug-in module / approx. 32 kg19"6U360 mm500 mm400 mm310 mm approx. 23 kg / kVAH Size ASize GSize T419"6U360 mm500 mm600 mm330 mmSize CSize D19"6U510 mm500 mm600 mm330 mm19 sub-rackincluding pluggable inverters and transformers, approx. 40 kgwith wall plate (optional)approx. 45 kg19 sub-rackincluding pluggable inverters, approx. 24 kg (transformers external)with wall plate (optional)and transformers (T1/T2), approx. 55/65 kgWHDT ransformers refer to 50/60 Hz at the frequencies or tropical insulation may change size and : For 3-phase system 3 transformers are mount versionWHDT ransformers refer to 50/60 Hz at the frequencies or tropical insulation may change size and : For 3-phase system 3 transformers are versionTransformers refer to 50/60 Hz at the frequencies or tropical insulation may change size and : For 3-phase system 3 transformers are "7U460 mm500 mm800 mm370 mmSize ESize F19"6U460 mm19 sub-rackincluding pluggable inverters, approx.

10 27 kg (transformers external)19 sub-rackincluding pluggable inverters, approx. 28 kg (transformers external)with wall plate (optional)and transformers, approx. 104 kgTransformer refers to 50/60 Hz at the frequencies or tropical insulation may change size and : For 3-phase system 3 transformersare mm800 mm370 mmwith wall plate (optional)and transformers (T2/T3), approx. 70/80 kgwith wall plate (optional)approx. 36 kgAttention: For 3-phase system 3 modules are T1 - T3 Size T5 - T7 Trans -formerHWDW eightin kgPowerin kVAin mmT5T6T739045045024028028023325328333506 6 5 812 Size T5 - T7 Trans -formerHWDW eightin kgPowerin kVAin mmT5T6T733539039023026026021024027033506 6 5 812 Trans -former HWeightin kgPowerin kVAin mm200 mm176 mmSchaefer, Inc. 45 South Street, Hopkinton, MA 01748, USA Tel: 508-435-6400 Fax: 508-435-6401 More detailed drawings see