Distribution System Phase Attribute Measurements Using …

Distribution System Phase Attribute Measurements Using The Origo PhaseID System1 Origo Corporation 2004 Technology Made Simple Distribution System Phase Attribute Measurements Using the Origo PhaseID System Introduction The Origo PhaseID System measures Phase in a power Distribution System by Using a GPS timing signal to simultaneously measure voltage Phase at a base and field location. By comparing the unknown Phase at the field location to the known Phase at the base location, the unknown field Phase Attribute can be deter-mined. This white paper explains how we would expect voltage Phase to vary at different points in the Distribution System , as it passes though various transmission and Distribution transformers and power lines.

© Origo Corporation 2004 2 Technology Made Simple The transformers in figure 1 are additive as indicated by the placement of the secondary winding polarity dot ...

Tags:

  Phases, System, Measurement, Distribution, Attribute, Ogori, Distribution system phase attribute measurements

Information

Domain:

Source:

Link to this page:

Please notify us if you found a problem with this document:

Other abuse

Transcription of Distribution System Phase Attribute Measurements Using …

1 Distribution System Phase Attribute Measurements Using The Origo PhaseID System1 Origo Corporation 2004 Technology Made Simple Distribution System Phase Attribute Measurements Using the Origo PhaseID System Introduction The Origo PhaseID System measures Phase in a power Distribution System by Using a GPS timing signal to simultaneously measure voltage Phase at a base and field location. By comparing the unknown Phase at the field location to the known Phase at the base location, the unknown field Phase Attribute can be deter-mined. This white paper explains how we would expect voltage Phase to vary at different points in the Distribution System , as it passes though various transmission and Distribution transformers and power lines.

2 Potential sources of Phase measurement error, and their magnitude, are discussed. Phase Shift Through Ideal Transformers Delta-Grounded Wye A popular substation transformer connection is the delta-grounded wye illustrated in figure 1. By conven-tion, capital letters (A, B, C, N) refer to the source side and lower case letters (a, b, c, n) refer to the load side. Delta-wye and wye-delta transformers are also connected in the standard 30 degree connection in which the source voltage leads the load voltage by 30 degrees. The voltage Phase vector rotation is as-sumed to be CCW. FIGURE 1 DELTA - GROUNDED WYESTEP DOWNADDITIVE+ CA -+ AB -+ BC -+ an -+ bn -+ cn -H1 - AH2 - BH3 - CX1 - aX2 - bX3 - cX0 - n Origo Corporation 2004 Technology Made Simple 2 The transformers in figure 1 are additive as indicated by the placement of the secondary winding polarity dot opposite the primary winding dot.

3 The vector diagram for figure 1 is illustrated in figure 2. In figure 2, the assumed primary phases of A, B, and C with respect to ground (neutral) are indicated by AN, BN, and CN. The differential voltages CA, AB, and BC are applied to the transformer primaries which create the secondary voltages an, bn, and cn. The construction and correct magnitude of AB, BC, and CA are shown in red. Their directions are shown in black. Note that the secondary lags the primary by 30 de-grees. Figure 3 illustrates the same connections Using subtractive transformers. The corresponding vector dia-gram is illustrated in figure 4.

4 Note that the secondary outputs are inverted. ANBNCNABBCCA cnbnanABCABCDELTA - GROUNDED WYESTEP DOWNADDITIVEFIGURE 2 Origo Corporation 2004 Technology Made Simple 3 DELTA - GROUNDED WYESTEP DOWNSUBTRACTIVEH1 - AH2 - BH3 - CX1 - aX2 - bX3 - cX0 - n+ CA -+ AB -+ BC -+ an -+ bn -+ cn -FIGURE 3 ANBNCNABBCCA cnbnanABCABCDELTA - GROUNDED WYESTEP DOWNSUBTRACTIVEFIGURE 4 Origo Corporation 2004 Technology Made Simple 4 Ungrounded Wye-Delta The ungrounded wye-delta connection is typically used to provide service to a combination single- Phase lighting load and a three- Phase power load such as an induction motor.

5 The connection diagram Using ad-ditive transformers is illustrated in figure 5 and its vector diagram is illustrated in figure 6. FIGURE 5 UNGROUNDED WYE - DELTASTEP DOWNADDITIVE- AN +- BN +- CN ++ ab -+ bc -+ ca -H1 - AH2 - BH3 - CX1 - aX2 - bX3 - cabcabcANBNCNABBCCA cnbnanABCABCFIGURE 6 UNGROUNDED WYE - DELTASTEP DOWNADDITIVE abbcca Origo Corporation 2004 Technology Made Simple 5 Again, the assumed primary phases of A, B, and C with respect to ground (neutral) are indicated by AN, BN, and CN. These voltages are applied across the primary windings to produce the secondary delta volt-ages ab, bc, and ca.

6 The vectors in blue are used to construct the secondary line to-neutral voltages. Again, the secondary voltages lag the primary voltages by 30 degrees. Grounded Wye-Grounded Wye The grounded wye-grounded wye connection is used primarily to supply single- Phase and three- Phase loads on four-wire multi-grounded systems The connection diagram Using subtractive transformers is illus-trated in figure 7. The corresponding vector diagram is illustrated in figure 8. In residential padmount use, three single Phase transformers are spread out Using the grounded wye grounded wye connection to supply 120/240V service from 7200V volt feeders.

7 By Using a grounded cen-ter tapped secondary, both an in and out line-to-neutral voltage of 120V is produced. That is, both an and -an vectors are produced along with a differential voltage of 240V across the pair. Note that there is no 30 degree Phase shift with this connection. GROUNDED WYE - GROUNDED WYESTEP DOWNSUBTRACTIVEH1 - AH2 - BH3 - CX1 - aX2 - bX3 - cX0 - n+ AN -+ BN -+ CN -+ an -+ bn -+ cn -FIGURE 7Nn Origo Corporation 2004 Technology Made Simple 6 Delta-Delta A delta-delta connection Using subtractive transformers is illustrated in figure 9 along with its vector dia-gram in figure 10.

8 Note that there is no 30 degree Phase shift between primary and secondary voltages. ANBNCN cnbnanFIGURE 8 GROUNDED WYE - GROUNDED WYESTEP DOWNSUBTRACTIVEDELTA - DELTASTEP DOWNSUBTRACTIVEH1 - AH2 - BH3 - CX1 - aX2 - bX3 - c+ AB -+ BC -+ CA -+ ab -+ bc -+ ca -FIGURE 9 Origo Corporation 2004 Technology Made Simple 7 Open Wye-Open Delta An open wye-open delta connection Using additive transformers is illustrated in figure 11. This is a popular connection for light loads because it only requires two transformers. Its vector diagram is illustrated in fig-ure 12. ANBNCNABBCCA bcabcaABCABCFIGURE 10 DELTA - DELTASTEP DOWNSUBTRACTIVE anbncnabbccaFIGURE 11 OPEN WYE - OPEN DELTASTEP DOWNADDITIVE- AN +- BN ++ ab -+ bc -H1 - AH2 - BX1 - aX2 - bX3 - cN Origo Corporation 2004 Technology Made Simple 8 Another popular connection is illustrated in figure 13 where a grounded secondary center tap is used.

9 Its vector diagram is illustrated in figure 14. Typically, one of the transformers uses a grounded center tap to supply 120/240V and is called the lighting pot. The other transformer is called the power pot. ANBNAB cnbnanABFIGURE 12abbccaOPEN WYE - OPEN DELTASTEP DOWNADDITIVE caabcabcbcFIGURE 13 OPEN WYE - OPEN DELTAPOWER & LIGHTINGSTEP DOWNADDITIVE- AN +- BN +- s32 +ABs1s2s3N+ s1 -- s2 +H1H2 H1H2X1X2X3X1X3 Origo Corporation 2004 Technology Made Simple 9 Other Transformer Connections There are many other transformer connections used in the industry. Using the examples listed above, vec-tor diagrams can be constructed for any of them.

10 The diagrams indicate the expected Phase shift at each secondary output. Conversely, the Phase attributes of each terminal of an unmarked transformer could be obtained Using the Origo PhaseID System to determine the type of transformer. Origo PhaseID System Phase Attribute Chart The various combinations of transformer connections of the previous section lead to the Phase Attribute chart illustrated in figure 15, in which all primary and secondary voltages can be represented by one of 12 different Phase attributes. That is, for ideal transformers, the primary to secondary Phase shift can only be 0, 30, or 180 degrees.