Duct Smoke Detector range - Notifier Fire Systems

This document is not intended to be used for installation purposes. Every care has been taken in the preparation of this document but no liability can be accepted for the use of the information therein. Design features may be changed or amended without prior notice. For more information, contact: Notifier . Charles Avenue, Burgess Hill, West Sussex, RH15 9UF. United KingdomPhone: +44 (0) 1444 230 300 Fax: +44 (0) 1444 230 888 ISO9001 Design, Manufacture and Supply to Quality Management Systems Certi ed to ISO9001:1994 Page 1 of 4 - er er Series duct Smoke detectors are exible enough to t con gurations from square to rectangular and everything in units sense Smoke in the most challenging conditions, operating in air ow speeds of to 20m/sec, temperatures of 0 C to 70 C, and a humidity range of 0 to 95 percent (non-condensing).

Page 3 of 4 - 990-141_1110 www.noti˜ er˜ resystems.co.uk D2E conventional duct smoke detector The D2E 2-wire photoelectric duct smoke detector features a pivoting housing

Tags:

  Smoke, Detectors, Smoke detector, Notifier

Information

Domain:

Source:

Link to this page:

Please notify us if you found a problem with this document:

Other abuse

Transcription of Duct Smoke Detector range - Notifier Fire Systems

1 This document is not intended to be used for installation purposes. Every care has been taken in the preparation of this document but no liability can be accepted for the use of the information therein. Design features may be changed or amended without prior notice. For more information, contact: Notifier . Charles Avenue, Burgess Hill, West Sussex, RH15 9UF. United KingdomPhone: +44 (0) 1444 230 300 Fax: +44 (0) 1444 230 888 ISO9001 Design, Manufacture and Supply to Quality Management Systems Certi ed to ISO9001:1994 Page 1 of 4 - er er Series duct Smoke detectors are exible enough to t con gurations from square to rectangular and everything in units sense Smoke in the most challenging conditions, operating in air ow speeds of to 20m/sec, temperatures of 0 C to 70 C, and a humidity range of 0 to 95 percent (non-condensing).

2 An improved cover design isolates the Detector head from the low- ow feature for simple maintenance. The unit incorporates cover tamper feature to indicate a trouble signal for a removed or improperly installed sensor cover. The duct Detector housing provides a 20mm conduit knockout and ample space to facilitate easy wiring and mounting of relay duct Smoke Detector can be customised to meet local codes and speci cations without additional REMEMBER DUCT Smoke detectors ARE: NOT a substitute for an open area Smoke Detector , NOT a substitute for early warning detection, and NOT a replacement for a building s regular re detection system. Features Photoelectric, integrated low-fl ow technology Air velocity rating from to 20m/sec Versatile mounting options: square or rectangular con guration Broad ranges for operating temperature 0 C to 70 C and humidity (0% to 95% non-condensing) Patented sampling tube installs from front or back of the Detector with no tools required Cover tamper signal 20mm conduit knockout for easy wiring access Available space within housing to accommodate mounting of relay module Easily accessible code wheels on sensor head (sold separately)

3 Clear cover for convenient visual inspectionDuct Smoke Detector rangeData SheetPage 2 of 4 - er intelligent non-relay photoelectric duct Smoke detectorThe DNRE intelligent non-relay photoelectric duct Smoke Detector features a pivoting housing that ts both square and rectangular footprints capable of mounting to a round or rectangular Speci cation Size: (Rectangular) 37 cm L; cm W; cm D (Square) cm L; cm W; cm D Weight: kg Operating Temperature range : 0 C to 70 C Storage Temperature range : 0 to 70 C Operating Humidity range : 0% to 95% relative humidity non-condensing Air Duct Velocity: to 20 m/sec Installing the Sampling Tube The sampling tube may be installed from the front or back of the Detector The tube locks securely into place and can be removed by releasing the front or rear locking tabElectrical Speci cation Please see Detector head installation manual for electrical speci cations Accessory Current Loads at 24 VDCD evice Standby AlarmRI/W/3V 0 mA 12 mA for intelligent non-relay duct Smoke Detector Please refer to DNRE installation manual for more informationSystem wiring diagram for DNREDNRE to RI/W/3 VSpeci cationsDNRE non-relay duct Smoke detectorCOMM.

4 LINE (+)NOTIFIERCONTROL PANEL1ST DETECTORIN LOOP2ND DETECTORIN LOOPCOMM. LINE ( )COMM. LINE(+)(-)RA400Z RA+ RAREMOTE ALARM LED OPTION 1 PER UNIT EXTERNAL(-) POWER (+)SUPPLY*RTS451/RTS451 KEY45321 TEST COIL +TEST COIL COMM +OUT (CONV ONLY) +DNR to RTS451/RTS451 KEY:EXTERNAL(-) POWER (+)SUPPLY*RTS151/RTS151 KEYREMOTE TEST STATIONLED OPTION1 PER UNITTEST COIL OPTION1 PER UNIT95mA CURRENT DRAW45321 TEST COIL +TEST COIL COMM +OUT (CONV ONLY) +COMM RA/RTS RA +RTS +Installing the InnovairFlex Sampling TubeThe InnovairFlex sampling tube may be installed from the front or back of the Detector . The tube locks securely into place and can be removed by releasing the front or rear locking tab (front locking tab shown below right).COMM. LINE (+)NOTIFIERCONTROL PANEL1ST DETECTORIN LOOP2ND DETECTORIN LOOPCOMM.

5 LINE ( )COMM. LINE(+)(-)RA400Z RA+ RAREMOTE ALARM LED OPTION 1 PER UNIT EXTERNAL(-) POWER (+)SUPPLY*RTS451/RTS451 KEY45321 TEST COIL +TEST COIL COMM +OUT (CONV ONLY) +DNR to RTS451/RTS451 KEY:EXTERNAL(-) POWER (+)SUPPLY*RTS151/RTS151 KEYREMOTE TEST STATIONLED OPTION1 PER UNITTEST COIL OPTION1 PER UNIT95mA CURRENT DRAW45321 TEST COIL +TEST COIL COMM +OUT (CONV ONLY) +COMM RA/RTS RA +RTS +Installing the InnovairFlex Sampling TubeThe InnovairFlex sampling tube may be installed from the front or back of the Detector . The tube locks securely into place and can be removed by releasing the front or rear locking tab (front locking tab shown below right).Page 3 of 4 - er conventional duct Smoke detectorThe D2E 2-wire photoelectric duct Smoke Detector features a pivoting housing that ts various applications: both square and rectangular footprints mount to round or rectangular duct Speci cation Size: (Rectangular) 37 cm L; cm W; cm D (Square) cm L; cm W.

6 Cm D Weight: kg Operating Temperature range : 0 C to 70 C Storage Temperature range : 0 to 70 C Operating Humidity range : 0% to 95% relative humidity non-condensing Air Duct Velocity: to 20 m/sec Installing the Sampling Tube The sampling tube may be installed from the front or back of the Detector The tube locks securely into place and can be removed by releasing the front or rear locking tabElectrical Speci cation Power supply voltage: VDC Input capacitance: F max. Reset voltage: VDC min. Reset time: (with RTS451) to sec. Reset time: (by power down) sec. max. Power up time: 35 sec. max. Alarm response time: 15 sec. Sensitivity Test: See Detector label Current Requirements: (Using No Accessories) Peak standby current: 120 A Max.

7 Standby current: 60 A (average) Max. alarm current: 130 mA Accessory Current Loads at 24 VDC Device Standby AlarmRI/W/3V 0 mA 12 mA for intelligent non-relay duct Smoke Detector Please refer to the D2E installation manual for more informationSystem wiring diagram for 2-wire duct Smoke detectors (powered from initiating device circuit)Speci cationsD2E conventional duct Smoke Detector D2E-09 Wiring for Intelligent Non-Relay Duct Smoke Detector * Product RangeD2E 2- wire photoelectric low- ow duct Smoke Detector DCOIL 2- wire remote test c oil required with RTS451/RTS451 KEYDST1 Met al sampling tube duct width up to Met al sampling tube duct widths to mDST3 Met al sampling tube duct widths to mDST5 Met al sampling tube duct widths to mDST10 Met al sampling tube duct widths to m* Important Notes: The use of either R TS451 or R TS451 KEY r equires the instal lat ion of an accessory c oil, DCOIL, sold separ at ely.

8 Ple ase ref er t o the D2E instal lat ion manual for more information Charles AvenueBurgess HillRH15 9 TQUnited Kin gdomTel: +44 (0)1444 238820 Fax: +44 (0)1444 248123 Email: Sensor Europe (Technical Services)Copyright 2010 System Sensor. Al l rights reserved. Al l t echnical dat a is c orrect at t ime of publicat ion and is subject t o change without notic e. Al l trademarks lat ion information: in order t o ensure full fu nctionality, r ef er t o the instal lat ion instruct ions as t No. DescriptionRA400Z Remote annunciat or alarm LEDRTS451 Remote test stat ionRTS451 KEY Remote test stat ion with key lockSystem wiring diagram for 2-wire duct Smoke detectors (powered from initiating device circuit).

9 Wiring diagram for 2-wire duct Smoke Detector to RTS451/RTS451 KEY Remote Test Station(+) IN(+) OUT(+)(+)( )( )1ST DETECTORIN LOOP D2( )RI/W/3V (OPTIONAL)REMOTE ALARM VDC ALARM(+) IN(+) OUT(+)(+)( )LAST DETECTORIN LOOP D2( )RI/W/3V (OPTIONAL)REMOTE ALARM VDC ALARMEOLRSTYLE D OPTIONAL WIRINGNOTIFIERCONTROL PANELALARMINITIATIONLOOP(+)( )EOL RESISTORRARARARA( )~~~~(+) IN(+) OUT(+)(+)( )( )2ND DETECTORIN LOOP D2( )RI/W/3V (OPTIONAL)REMOTE ALARM VDC ALARMRARA~~~~A05-0421-000 Wir ing for 2-wire Duct Smoke DetectorSystem wiring diagram for 2-wire duct Smoke detectors (powered from initiating device circuit):24 VAC (+10%, 15%)FULL WAVE RECTIFIED,UNFILTERED POWERMAY BE USEDRTS451/RTS451 KEY(OPTIONAL) REMOTETEST STATIONMAGNETTESTSWITCHALARMLED (RED)4521(+)( )+ RA+ RTS RA+ TEST COIL TEST COIL+ IN+ OUT ( )(+)D224 VDCAUX POWERSUPPLIEDBY USER(100mASUPPLY)RTS451/RTS451 KEY(OPTIONAL) REMOTETEST STATION24 VAC (+10%, 15%)FULL WAVE RECTIFIED,UNFILTERED POWERMAY BE USEDMAGNETTESTSWITCHALARMLED (RED)4521(+)( )+ RA+ RTS RA+ TEST COIL TEST COIL+ IN+ OUT 24 VDCAUX POWERSUPPLIEDBY USER(100mASUPPLY)D2 METHOD #1 - AUX POWER LOCATED AT DUCT DETECTORMETHOD #2 - AUX POWER LOCATEDAT TEST STATIONI mportant NoteThe use of either RTS451 or RTS451 KEY requires the installation of an accessory coil, DCOIL, sold separately.

10 Please ref er to the D2 installation manual for more infor mationWiring diagram for 2-wire duct Smoke Detector to RTS451/RTS451 KEY Remote Test Station(+) IN(+) OUT(+)(+)( )( )1ST DETECTORIN LOOP D2( )RI/W/3V (OPTIONAL)REMOTE ALARM VDC ALARM(+) IN(+) OUT(+)(+)( )LAST DETECTORIN LOOP D2( )RI/W/3V (OPTIONAL)REMOTE ALARM VDC ALARMEOLRSTYLE D OPTIONAL WIRINGNOTIFIERCONTROL PANELALARMINITIATIONLOOP(+)( )EOL RESISTOR RARARARA( )~~~~(+) IN(+) OUT(+)(+)( )( )2ND DETECTORIN LOOP D2( )RI/W/3V (OPTIONAL)REMOTE ALARM VDC ALARMRARA~~~~A05-0421-000 InnovairFlex Duct Smoke Detector Speci cationsThe air duct Smoke Detector shall be a System Sensor InnovairFlex D2 Photoelectric Duct Smoke Detector . The Detector housing shall be UL listed per UL shall operate at air velocities of 100 ft/min to 4000 ft/min ( m/sec to m/sec).