03/20 ContentsNomenclature ..2 Product Specifications ..3 Expanded Cooling Data ..4 Expanded Heating DataNormal Heating Mode ..18 Heating Boost Mode ..20 Performance DataStandard / Boost Mode ..22 Sound Data ..26 AHRI Ratings (see note) ..29 Dimensions ..30 Wiring Diagrams ..31 Accessories ..33DZ17 VSAD aikin Fit High-Efficiency, Communicating,Variable-Speed, Inverter Drive Side Discharge split system Heat Pump Standard Features Daikin variable-speed swing compressors High-density compressor sound blanket Compatible with Daikin One+ smart thermostat and other Daikin communicating equipment Daikin control algorithmic logic Intelligent Defrost Mode In communicating mode, only two low- voltage wires to outdoor unit required Diagnostic indicator lights, seven-segment LED display, and fault code storage Daikin Inside intelligence for diagnostics Field-selectable boost mode increases compressor speed during unusually high loads Quiet DC outdoor fan motor Field-installed bi-flow filter drier Coil and ambient temperature sensors Suction pressure transducer Sweat connection service valves with easy access to gauge ports Advanced water-shedding drain pan Hot start technology AHRI Certified.

Daikin Fit High-Efficiency, Communicating, Variable-Speed, Inverter Drive Side Discharge Split System Heat Pump Standard Features •ariable-speed swing compressors Daikin v • High-density compressor sound blanket • Compatible with Daikin One+ smart thermostat and other Daikin communicating equipment • Daikin control algorithmic logic

Tags:

  System, Split, Daikin, Split system

Information

Domain:

Source:

Link to this page:

Please notify us if you found a problem with this document:

Other abuse

Transcription of DZ17VSA - Daikin Comfort

1 03/20 ContentsNomenclature ..2 Product Specifications ..3 Expanded Cooling Data ..4 Expanded Heating DataNormal Heating Mode ..18 Heating Boost Mode ..20 Performance DataStandard / Boost Mode ..22 Sound Data ..26 AHRI Ratings (see note) ..29 Dimensions ..30 Wiring Diagrams ..31 Accessories ..33DZ17 VSAD aikin Fit High-Efficiency, Communicating,Variable-Speed, Inverter Drive Side Discharge split system Heat Pump Standard Features Daikin variable-speed swing compressors High-density compressor sound blanket Compatible with Daikin One+ smart thermostat and other Daikin communicating equipment Daikin control algorithmic logic Intelligent Defrost Mode In communicating mode, only two low- voltage wires to outdoor unit required Diagnostic indicator lights, seven-segment LED display, and fault code storage Daikin Inside intelligence for diagnostics Field-selectable boost mode increases compressor speed during unusually high loads Quiet DC outdoor fan motor Field-installed bi-flow filter drier Coil and ambient temperature sensors Suction pressure transducer Sweat connection service valves with easy access to gauge ports Advanced water-shedding drain pan Hot start technology AHRI Certified.

2 ETL Listed Cabinet Features Heavy-gauge galvanized steel cabinet with grille-style sound control side design Custom Ivory white powder-paint finish 500-hour salt-spray tested Wire fan discharge grille Top and side maintenance access When properly anchored, meets the 2017 Florida Building Code unit integrity requirements for hurricane-type winds (Anchor bracket kits available.)UP TO 18 SEER & HSPF1 to 5 TonsCOOLING CAPACITY: 17,100 - 54,000 BTU/HHEATING CAPACITY: 17,100 - 54,000 BTU/H* Complete warranty details available from your local dealer or at To receive the 12-Year Unit Replacement Limited Warranty and 12-Year Parts Limited Warranty, online registration must be completed within 60 days of installation. Additional requirements for annual maintenance are required for the Unit Replacement Limited Warranty. Online registration and some of the additional requirements are not required in California or ,45678,91011,12 BrandEngineering D - DaikinMajor & Minor revisionsTypeX - AC R-410 AVoltageZ - HP R-410A1 - 208-230 V Single-Phase 60 HzSEERC apacity14 - 14 SEER18 - 18 SEER18 - 1 tons42 - 3 tons16 - 16 SEER20 - 20 SEER24 - 2 tons48 - 4 tons17 - 17 SEER30 - 2 tons60 - 5 tonsCompressor36 - 3 tonsS - Single StageV - Variable SpeedRegionT - Two StageN-NorthS-Southeast & NorthA-AllFeature SetA - BaseN - NominalC - CommunicatingS - Side Discharge CommunicatingD - SpecificationsDZ17 VSA 181B*DZ17 VSA 241B*DZ17 VSA 301B*DZ17 VSA 361B*DZ17 VSA 421B*DZ17 VSA 481B*DZ17 VSA 601B*Capacities (AHRI Rated)Max.

3 Cooling (BTU/h)17,100 22,80028,400 34,200 40,000 45,500 54,000 Max. Heating (BTU/h)17,100 22,80028,400 34,200 40,000 45,500 54,000 Ambient Operation RangeCooling ( FDB( CDB))0 to 115 ( to )2 Heating ( FDB( CDB))-10 to 70 ( to ) Fan MotorHorsepower3/163/163/163/16 SystemRefrigerant Line Size Liquid Line Size ( ) " " " " " " "Suction Line Size ( ) " " " "1 "1 "1 "Refrigerant Connection SizeLiquid Valve Size ( ) " " " " " " "Suction Valve Size ( ) " " " " " " "Valve Connection TypeFront Sealing Front Sealing Front Sealiing Front SealingFront and Back SealingFront and Back SealingFront and Back SealingRefrigerant Charge (oz.)81818888118118127 Expansion DeviceEEVEEVEEVEEVEEVEEVEEVS uperheat at Service Valve Auto-controlAuto-controlAuto-controlAuto -control Auto-control Auto-control Auto-controlSubcooling at Service Valve 10 1 F 12 1 F14 1 F 14 1 F 10 1 F 8 1 F 9 1 FElectrical DataVoltage / Phase (60 Hz)208-230/1208-230/1208-230/1208-230/12 08-230/1208-230/1208-230/1 Minimum Circuit Overcurrent Protection315202525353540 Min / Max Volts197/253197/253197/253197/253197/253 197/253197/253 Electrical Conduit Size " " " " " or " " or " " or "Equipment Weight (lbs)118118127133173173186 Ship Weight (lbs)135135143150185185198 Tested and rated in accordance with AHRI Standard 210/240 Wire size should be determined in accordance with National Electrical Codes.

4 Extensive wire runs will require larger wire sizes Must use time-delay fuses or HACR-type circuit breakers of the same size as Always check the S&R plate for electrical data on the unit being installed. Installer will need to supply to 1 adapters for suction line connections. Unit is charged with refrigerant for 15 of liquid line. system charge must be adjusted per Installation Instructions Final Charge Procedure.(See table below for allowable line set diameter)Unit TonsAllowable line set diameterLiquidSuction 5 16 1 Allowable combination 4 For marked combinations, if normal ambient operation temperature is less than 14 F, limit line set length to 50 ft. max. 5 For marked combinations, line set length will have a minimum of 25 ft and a maximum of 70 Cooling Data DZ17 VSA181B* / DV24 FECB14A*Outdoor Ambient Temperature65 F75 F85 F95 F105 F115 FEntering Indoor Wet Bulb TemperatureIDB* PR243244245-280281283-320321323-36336436 6-410411412-463464465-Lo PR246245247-282284285-323324325-36636736 8-412413415-465466468-Lo PR247248249-285286288-325326328-36836937 1-415416417-468469470-Lo PR24324424524928028128328732032132332736 3364366370410411413417463464466470Lo PR24624624725128328428529032332432533036 6367369373412413415419465466468472Lo PR24724825025428528628829232532632833236 8369371375415416417422468469471475Lo PR12813013313813613714014614214414715214 8149152158153155158163162164167173 IDB*.

5 Entering Indoor Dry Bulb TemperatureShaded area is ACCA (TVA) conditionskW = Total system powerHigh and low pressures are measured at the liquid and suction service valves. Amps = outdoor unit ampsAirflow may vary depending on actual ambient conditions and system operation Cooling Data DZ17 VSA181B* / DV24 FECB14A*Outdoor Ambient Temperature65 F75 F85 F95 F105 F115 FEntering Indoor Wet Bulb TemperatureIDB* PR24424524524928128228328832132232332836 4365367371410411413417463464466470Lo PR24624624825228328428629032332432633036 6367369373413414416420466467469473Lo PR24724825025428628728829332632732833336 9370371376415416418422468469471475Lo PR24524624625128228328528932232332532936 5366368372411412414418464466467471Lo PR24824724925328428528729132432532733136 7368370374414415417421467468470474Lo PR24825025125528728828929432732832933437 0371373377416417419423469470472476Lo PR13013213514013813914314814514614915415 0152155160156157160166165166170175 IDB*.

6 Entering Indoor Dry Bulb TemperatureShaded area is AHRI conditionskW = Total system powerHigh and low pressures are measured at the liquid and suction service = outdoor unit ampsAirflow may vary depending on actual ambient conditions and system operation Cooling Data DZ17 VSA241B* / DV24 FECB14A*Outdoor Ambient Temperature65 F75 F85 F95 F105 F115 FEntering Indoor Wet Bulb TemperatureIDB* Airflow596367715963677159636771596367715 9636771596367 PR256260263-302303305-345346348-39139239 4-441442444-486487489-Lo PR262264266-304306307-348349351-39439539 7-444445447-488489491-Lo PR266267269-307308310-350351353-39739840 0-447448450-491492494-Lo PR25626026426830230330530934534634835339 1393394399442443445449486487489493Lo PR26226526627130530630831234834935135539 4395397402444445447452489490491496Lo PR26626726927430730831031535035135335839 7398400404447448450454491492494498Lo PR12412612913413113313614113813914214714 3145148153148150153158158160163168 IDB*.

7 Entering Indoor Dry Bulb TemperatureShaded area is ACCA (TVA) conditionskW = Total system powerHigh and low pressures are measured at the liquid and suction service = outdoor unit ampsAirflow may vary depending on actual ambient conditions and system operation Cooling Data DZ17 VSA241B* / DV24 FECB14A*Outdoor Ambient Temperature65 F75 F85 F95 F105 F115 FEntering Indoor Wet Bulb TemperatureIDB* Airflow596367715963677159636771596367715 9636771596367 PR25626126426930230330531034534734835339 2393395399442443445450486487489494Lo PR26226526727130530630831334834935135639 5396398402445446448452489490492496Lo PR26626826927430830931131535135235435839 7398400405447448450455492493494499Lo PR25826226527030430530731134734835035439 3394396401443444446451488489491495Lo PR26426626827330630730931434935135235739 6397399403446447449454490491493498Lo PR26826927127530931031231635235335536039 8400401406449450452456493494496500Lo

8 PR12612813113613413513814314014214515014 5147150155151152155160161162165171 IDB*: Entering Indoor Dry Bulb TemperatureShaded area is AHRI conditionskW = Total system powerHigh and low pressures are measured at the liquid and suction service = outdoor unit ampsAirflow may vary depending on actual ambient conditions and system operation Cooling Data DZ17 VSA301B* / DV36 FECC14A*Outdoor Ambient Temperature65 F75 F85 F95 F105 F115 FEntering Indoor Wet Bulb TemperatureIDB* Airflow596367715963677159636771596367715 9636771596367 PR264268271-311312314-355356358-40340440 6-455456458-510511513-Lo PR270272274-313315317-358359361-40640740 9-457459460-512514515-Lo PR274275277-316317319-360362364-40841041 1-460461463-515516518-Lo PR26426827227631131231431935535735836340 3404406411455456458463510511513521Lo PR27027227427931431531732135835936136640 6407409414458459461465513514516524Lo PR27427527728231631731932436136236436840 9410412416460461463468515516518526Lo

9 PR12512713013513313413714313914114414914 5146149154150152155160157158161169 IDB*: Entering Indoor Dry Bulb TemperatureShaded area is ACCA (TVA) conditionskW = Total system powerHigh and low pressures are measured at the liquid and suction service = outdoor unit ampsAirflow may vary depending on actual ambient conditions and system operation Ambient Temperature65 F75 F85 F95 F105 F115 FEntering Indoor Wet Bulb TemperatureIDB* Airflow596367715963677159636771596367715 9636771596367 PR26526927227731131331531935635735936440 4405407412455457458463510512513522Lo PR27027327528031431531732235936036236640 6408410414458459461466513514516524Lo PR27427627728231731832032536136236436940 9410412417461462464468516517519527Lo PR26627027327831331431632035735836036540 5406408413457458460464512513515523Lo PR27227427628131531731932336036136336840 8409411416459461462467514516517526Lo PR27627727928331831932132636236436637041 0412413418462463465470517518520528Lo PR12812913213813513714014514214314615114 7149152157152154157162159161164172 IDB*.

10 Entering Indoor Dry Bulb TemperatureShaded area is AHRI conditionskW = Total system powerHigh and low pressures are measured at the liquid and suction service = outdoor unit ampsAirflow may vary depending on actual ambient conditions and system operation Cooling Data DZ17 VSA301B* / DV36 FECC14A*Outdoor Ambient Temperature65 F75 F85 F95 F105 F115 FEntering Indoor Wet Bulb TemperatureIDB* Airflow596367715963677159636771596367715 9636771596367 PR264268271-311312314-355356358-40340440 6-455456458-510511513-Lo PR270272274-313315317-358359361-40640740 9-457459460-512514515-Lo PR274275277-316317319-360362364-40841041 1-460461463-515516518-Lo PR26426827227631131231431935535735836340 3404406411455456458463510511513521Lo PR27027227427931431531732135835936136640 6407409414458459461465513514516524Lo PR27427527728231631731932436136236436840 9410412416460461463468515516518526Lo PR12512713013513313413714313914114414914 5146149154150152155160157158161169 IDB*.