Example: bankruptcy

E-RA-RA12-100-V17A-0 - RITAR POWER

ra12 -100(12V100Ah). Specification Cells Per Unit 6. Voltage Per Unit 12. Nominal Capacity 100Ah@10hour-rate to per cell @25 . Weight Approx. Kg (Tolerance ). Internal Resistance Approx. m . Terminal F12(M8)/F5(M8). Max. Discharge Current 1000A (5 sec). Short Circuit Current 2150A RA series is a general purpose battery with 12 years design life in float service. It meets Design Life 12 years (Float charging). with IEC, JIS, BS and YDT standards. With Recommended Maximum Charging 30 A advanced AGM valve regulated technology Current and high purity raw material, the RA series C3 battery maintains high consistency for better C5 performance and reliable standby service Reference Capacity C10 life.

RA12-100(12V100Ah) SHENZHEN RITAR POWER CO.,LTD. URL: www.ritarpower.com Guangdong, China 518057 Temperature Effects On Capacity Cycle Life In Relation To Depth Of Discharge Relationship Between Charging Voltage And Temperature

Tags:

  Power, A1200 r1, Shenzhen, Ritar power, Ritar, Ra12, Shenzhen ritar power co

Information

Domain:

Source:

Link to this page:

Please notify us if you found a problem with this document:

Other abuse

Transcription of E-RA-RA12-100-V17A-0 - RITAR POWER

1 ra12 -100(12V100Ah). Specification Cells Per Unit 6. Voltage Per Unit 12. Nominal Capacity 100Ah@10hour-rate to per cell @25 . Weight Approx. Kg (Tolerance ). Internal Resistance Approx. m . Terminal F12(M8)/F5(M8). Max. Discharge Current 1000A (5 sec). Short Circuit Current 2150A RA series is a general purpose battery with 12 years design life in float service. It meets Design Life 12 years (Float charging). with IEC, JIS, BS and YDT standards. With Recommended Maximum Charging 30 A advanced AGM valve regulated technology Current and high purity raw material, the RA series C3 battery maintains high consistency for better C5 performance and reliable standby service Reference Capacity C10 life.

2 It is suitable for UPS/EPS, Telecom, C20 POWER grid, medical equipment, emergency Standby Use Voltage V~ V @ 25 light and security system applications. Temperature Compensation: -3mV/ /Cell V~ V @ 25 . Cycle Use Voltage Temperature Compensation: -4mV/ /Cell Discharge: -20 ~60 . Operating Temperature Range Charge: 0 ~50 . Storage: -20 ~60 . Normal Operating Temperature Range 25 5 . RITAR Valve Regulated Lead Acid (VRLA) batteries can be stored for up to 6 months at 25 and then recharging Self Discharge is recommended. Monthly Self-discharge ratio is less than 3% at 25 .Please charge batteries before using. Container Material UL94-HB, UL94-V0 Optional. Dimensions 328 172.

3 16 Length 328 2mm ( inches). M8. Width 172 2mm ( inches). Height 215 2mm ( inches). 5. Total Height 220 2mm ( inches). Terminal Value 220. 215. M5 6~7 N*m M6 8~10 N*m M8 10~12 N*m 265. F12 Terminal Unit: mm Constant Current Discharge Characteristics : A (25 ). 10 MIN 15 MIN 30 MIN 1HR 2HR 3HR 4HR 5HR 8HR 10HR 20HR. Constant POWER Discharge Characteristics : WPC (25 ). 10 MIN 15 MIN 30 MIN 1HR 2HR 3HR 4HR 5HR 8HR 10HR 20HR. 424 325 195 118 422 323 194 117 410 314 189 115 394 304 184 111 372 288 175 107 341 267 164 101 (Note) The above characteristics data are average values obtained within three charge/discharge cycle not the minimum values. ra12 -100(12V100Ah). Discharge Characteristics Curve Charge Characteristic Curve For Standby Use Temperature:25 (77 ) Temperature:25 (77 ).

4 (V/cell). 120 Charge Volume Charge Voltage (VPC). Charge Current (CA). Terminal Voltage (v ). 100 Charge Voltage Charge Volume (%). 80 60 After 50% Discharge 3C 2C 1C After 100% Discharge 40 20 Charge Current 0. 1 2 4 6 8 10 20 40 60 2 4 6 8 10 20 0 min h 0 2 4 6 8 10 12 14 16 18 20 22 24 26 28. Discharge Time Charging Time(h). Cycle Life In Relation To Depth Of Discharge Relationship Between Charging Voltage And Temperature 120. 100 Charge Voltage (v ). Cycle use 80 ~ @25 . Capacity(%). 60. 100% 50% 30%. DOD DOD DOD 40. 20. Float charging ~ @25 . 0 200 400 600 800 1000 1200 1400. -20 -10 0 10 20 30 40 50. Number of Cycles Temperature ( ). Temperature Effects On Capacity Storage Characteristics 120 100.

5 100 0 . 0 .1 C A 80. Capacity (% ). Capacity (% ). 80 0 .2 C A. 60. 10 . 60. 20 . 1 .0 C A 40. 40 30 . 40. 2 .0 C A. 3 .0 C A 20. 20. 0 0. -20 -10 0 10 20 30 40 50 0 2 4 6 8 10 12 14 16 18 20 22 24. Temperature ( ) Storage Time(months). Effect Of Temperature On Long Term Life Life Characteristics Of Standby Use Testing conditions: float charging Temperature: 25 (77 ). 20. 120. Lift Expectancy (y ears). 16 100. 80. 12. Capacity(%). 60. 8. 40. 4. 20. 0 0. 0 10 20 30 40 50 0 2 4 6 8 10 12. Temperature( ) Life expectancy (years). (Note) All above information shall be changed without prior notice, RITAR reserves the right to explain and update the latest information. shenzhen RITAR POWER CO.

6 ,LTD. Add: 10th Floor, Tower C, 1st Building, Software Industry Base, , Xuefu Road, Nanshan District, shenzhen , Guangdong, China 518057. URL: Tel: +86-755-33981668/83475380 Fax: +86-755-83475180 E-mail: Version 17A-0.