eBoost™ - GE Energy

GE. Digital Energy eBoost . Guaranteed Higher UPS Efficiency Energy consumption is a critical issue for IT Technology breakthroughs organizations as their data center Energy Up to 99% UPS efficiency demands continue to grow. Their goal is Compliant to ITI (CBEMA) curve during undervoltage to reduce cost and keep the datacenter events running. Up to 3 MVA UPS capacity using Redundant Parallel Architecture (RPA). Magnetizing the output transformer ensures a < 2ms IT organizations can reduce Energy transfer time consumption and costs without sacrificing Static bypass inductor for filtering utility power reliability with GE's eBoost technology. Battery trickle charge in eBoost operating mode What is eBoost? e = high efficiency (up to 99%). Boost = fast power transfer (<2ms). imagination at work Customer benefits 80% reduction in UPS losses eBoost System Energy cost savings Reduced heat (BTU) generation Energy savings from reduced cooling Extended UPS component life User-programmable scheduling Reduced acoustical noise double conversion Inductor Static bypass Power flow Mains Z Load Rectifier Inverter Output transformer Battery Capacitor During traditional operation the UPS runs in double conversion mode.

∆ Z ∆ Z During eBoost operation the load is supplied directly by the mains, via the static bypass circuit. This provides an efficiency up to 99%. In case the mains voltage is out of tolerance, the UPS will immediately transfer the load to

Information

Domain:

Source:

Link to this page:

Please notify us if you found a problem with this document:

Other abuse

Advertisement

Transcription of eBoost™ - GE Energy

1 GE. Digital Energy eBoost . Guaranteed Higher UPS Efficiency Energy consumption is a critical issue for IT Technology breakthroughs organizations as their data center Energy Up to 99% UPS efficiency demands continue to grow. Their goal is Compliant to ITI (CBEMA) curve during undervoltage to reduce cost and keep the datacenter events running. Up to 3 MVA UPS capacity using Redundant Parallel Architecture (RPA). Magnetizing the output transformer ensures a < 2ms IT organizations can reduce Energy transfer time consumption and costs without sacrificing Static bypass inductor for filtering utility power reliability with GE's eBoost technology. Battery trickle charge in eBoost operating mode What is eBoost? e = high efficiency (up to 99%). Boost = fast power transfer (<2ms). imagination at work Customer benefits 80% reduction in UPS losses eBoost System Energy cost savings Reduced heat (BTU) generation Energy savings from reduced cooling Extended UPS component life User-programmable scheduling Reduced acoustical noise double conversion Inductor Static bypass Power flow Mains Z Load Rectifier Inverter Output transformer Battery Capacitor During traditional operation the UPS runs in double conversion mode.

2 Both the rectifier and the inverter are continuously operating, resulting in an efficiency of 92-94%. eBoost single module Power flow Inductor Static bypass Mains Z Load Rectifier Inverter Output transformer Battery Capacitor During eBoost operation the load is supplied directly by the mains, via the static bypass circuit. This provides an efficiency up to 99%. In case the mains voltage is out of tolerance, the UPS will immediately transfer the load to the inverter in < 2ms. The < 2ms is achieved by our patented* technology to magnetize the output transformer. The output transformer provides galvanic isolation between inverter and load. The static bypass inductor filters the input AC power during eBoost operational mode. * Patent No. 7,372,177. eBoost in Redundant Parallel Architecture (RPA). Power flow UPS module #1. Z. Power flow Load Inductor Static bypass UPS module #2. Mains Z. Rectifier Inverter Output transformer Battery Capacitor eBoost in RPA uses high speed communication and fast digital signal processors (DSP) to parallel up to 6 UPS.

3 Modules. eBoost in RPA provides up to 3 MVA capacity and up to 99% efficiency while maintaining < 2ms transfer time, compliant to the ITI (CBEMA) curve. eBoost performance Specifications mains failure On SG Series UPS products In case of a mains failure the UPS will transfer the 160-500kVA single module and input voltage load to inverter (double Redundant Parallel Architecture (RPA). conversion) within 2ms. operation: Transfer time : < 2ms transfer to inverter < 2ms Extremely fast Input voltage range : 10%. transfer to inverter Input frequency range : 2%. UPS output voltage (<2ms) in case of utility voltage anomaly or failure Efficiency : up to 99%. eBoost active double conversion active eBoost efficiency UPS efficiency comparison eBoost provides operating 100. efficiencies up to 99% and is 6%. 98. more efficient, on average, across eBoost 6% advantage the load range than traditional 96. double conversion UPS operating at 94. less than 92%. UPS efficicnecy 92. 90. 88. 86 GE eBoost GE double conversion 84.

4 Traditional double conversion 82. 80. 25% 50% 75% 100%. UPS load eBoost savings Data center life cycle cost (10 years). eBoost operation provides 10. considerable Energy life cycle cost savings ranging from to 9. 7MM.* Savings are dependent 8 Traditional double conversion upon load, power costs and life GE eBoost Total UPS Energy Cost ( MM). cycle duration (years). 7. 6. eBoost * Assumptions: 5 savings Power cost - 4. Operating hrs/year - 8,760 3. Configuration = S+S operating at 2. 50% capacity 1. 0. 1 2 3 4 5 6 7 8 9 10. Load (MW). your distributor: GE Consumer & Industrial SA. Via Cantonale 50. 6595 Riazzino (Locarno). Switzerland T +41 (0) 91 850 51 51. F +41 (0) 91 850 52 52. E imagination at work Visit us online at: General Electric Company, USA. All Rights Reserved (02/2012) English Reproduction only upon written consent by GE GEA-D 1050 GB.