Overview High capacity, 700KW Dual voltage: 208-240/416-480vAC Digital load control, 5 kw resolution Touchscreen operator interface Data Acquisition and recording Network units to form large systemsDescriptionThe Simplex Electra is a very large capacity, high performance Portable Load Bank designed to provide the manufacturers, distributors and users of large AC generators and UPS systems with sophisticated testing capability. Electra Load Banks feature Digital controllers with network control and data Acquisition capability. Operator interface is via touchscreen. Load control is via screen keypad. All electrical values display on the screen and are recorded by the system for future data retrieval.

The Simplex Electra is a very large capacity, high performance Portable Load Bank designed to provide the manufacturers, distributors and users of large AC generators and UPS systems with sophisticated testing capability. Electra Load Banks feature digital

Tags:

  Electra

Information

Domain:

Source:

Link to this page:

Please notify us if you found a problem with this document:

Other abuse

Transcription of Electra 700R 700KW Digital Load Bank with Data Acquisition ...

1 Overview High capacity, 700KW Dual voltage: 208-240/416-480vAC Digital load control, 5 kw resolution Touchscreen operator interface Data Acquisition and recording Network units to form large systemsDescriptionThe Simplex Electra is a very large capacity, high performance Portable Load Bank designed to provide the manufacturers, distributors and users of large AC generators and UPS systems with sophisticated testing capability. Electra Load Banks feature Digital controllers with network control and data Acquisition capability. Operator interface is via touchscreen. Load control is via screen keypad. All electrical values display on the screen and are recorded by the system for future data retrieval.

2 Any number of Electra and dynaMITE Load Banks can be combined for large system capacities and networked for central control and data Electra Series is rated 700KW of resistive load at both 240V and 480V, 3-phase. It can be applied at anyAC voltage to 480V AC, 50-60 Hertzstandard, single or 3-phase. Load stepresolution is ListedDigital Control: PLC based control with 8-inch color TFT touchscreen over RS-485 networkcommunication. See page : Digital power transducer with Ethernet communication to Digital controller. Data display on touchscreen. Data Acquisition and recording. See page 3. Load Elements: Simplex Powr-Web chromium alloy, open wire, continuously supported, power Control: 3-Pole Element Circuit Protection: Branch circuit fuses.

3 One set of fuses each 50KW branch. Fuses are current limiting type, 200 KAIC, System: 3-phase, direct-drive fan, 10,500 Detection System: Protection against fan failure, high exhaust air temperature, high intake air temperature, overvoltage and fan reversal. Exhaust air temperature displays on screen. Control Power Supply: Dual voltage control power transformer with supply power switchable to internal (generator) or Screen: Easily removable from panel. Connection: Cam-Type power 700R700KW Digital Load Bankwith Data Acquisition Rental DutyDual-Voltage Load Bank208-240/416-480vSIMPLEX ONSITE Rising Moon Road, Springfield, Illinois 855-767-5483 2020 Simplex Onsite, Inc.

4 All Rights Reserved. Printed in the USA subject to change without 700R700KW Digital Load Bank with Data AcquisitionPage 2 ModelKW ( )FLAKW DETAIL240V480V240V/480V208/416V380V240V, 1-phElectra 700R7001683842700525439467 Capacity DetailDigital Load Step ControlNominal kw resolution: direct enter any load value and controller will apply load within nominal 5kw resolutionDigital Load Calibration Versus VoltageController automatically calibrates loads for reduced voltage : Dual Voltage: 240/480V AC, 3-phase Operational at any voltage to480V AC maximum, single or 3-phaseFrequency: 50, 60 Hertz standardConnection: Cam-TypeTime Rating: ContinuousAmbient Air Temperature: 120 F maxFault Rating: 200 KAICI nsulation Rating: 600V, 302 FControl/Fan Power: 230/460V, 3-phase, 60 Hertz 190/380V, 3-phase, 50 Hertz Switchable internal (generator)-external 230/460-115V control powertransformer internal to Load Bank.

5 15 external power cordNet Weight: 1675 , , ,500158 F350 FCooling SystemOptions Network control cables, 25-foot basiclength 400Hz modification Remote control cable extensions Simplex AUTO-TEST software forfull automation of testing with dataacquisition and report generation 12 connection cable set including3-phase power cables, ground cable,stored in rear compartment Weather resistant enclosure Auxiliary inductive load banks withnetwork control and data capability 2020 Simplex Onsite, Inc. All Rights Reserved. Printed in the USA subject to change without ONSITE Rising Moon Road, Springfield, Illinois 855-767-5483 Electra 700R700KW Digital Load Bank with Data AcquisitionPage 3 Main ScreenMetering Trends ScreenMonitoring ScreenMaintenance ScreenDiagnostics ScreenDigital Control and Data Acquisition SystemPLC based Digital control with 8-inch color TFT touchscreen operator interface.

6 Functions Control power source and voltagelevel detection Malfunction detection and protection Direct access (keypad) load control Alternate mimic panel load control Basic automation of load control Field adjustable exhaust temperaturelimits with temperature display Built-in control from customer suppliedcomputerInstrumentationDigital power transducer to Digital controller and meter displays on touchscreen: 3-phase voltage (each, L-L) 3-phase current (each line) Frequency KWData Acquisition Captures and records all electricalvalues Start recording/stop recording screenbuttons One second sample rate Exports text file to detachable flashdrive which plugs into USB portOutputsMODBUS (standard) or BacNet (optional): Load applied Each electrical value as aboveSIMPLEX ONSITE Rising Moon Road, Springfield, Illinois 855-767-5483 2020 Simplex Onsite, Inc.

7 All Rights Reserved. Printed in the USA subject to change without 700R700KW Digital Load Bank with Data AcquisitionPage 4 Dimensions and Key Type Power Eyes (four) Louver (one on eachside) Lift Hot Air 8-inch Color TFTT ouchscreen Connections Compartment:Removable Access Panel to RearDistribution Bus, Fuses, Tired Casters, 6 (two front swivel, two rear fixed) Handle PocketPR1-PR 4 A BPR5-PR8 CPR 9-P R12 INPUTOUTPUTINTERNAL CONTROL POWER RECEPTACLE-WARNING- THIS RECEPTACLE IS NOTFUSED. USE ONLY TO APPLY CONTROLPO WER TO L OAD BANK.