Transcription of Enclosures - Cooper Industries
1 EnclosuresSection EEnclosures and junction boxes built and configured to meet the requirements ofthe most demanding hazardous areas and industrial environmental applicationsacross the globe. US: 1-866-764-5454 CAN: 1-800-265-0502 Copyright 2013 Eaton s Crouse-Hinds BusinessEEEnclosuresTable of ContentsSection E of the Eaton's Crouse-Hinds Product Catalog lists metallic and non-metallic Enclosures for hazardous and industrial on application, features, standard materials, standard finishes, size ranges, compliances, options, and accessories are presentedfor ease of product relating to product families in Section E is grouped as follows:Section 1 EMetallic EnclosuresFor explosionproof or flameproof hazardous applicationsGUE, GUBEIH, EIHTGUAEGJGUPGHG64 EJBEMH Section 2 EMetallic EnclosuresFor increased safety hazardous applications or non-hazardousapplicationsEx-CELLNXTSTBHV BKBXS ection 3 ENonmetallic EnclosuresFor Hazardous ApplicationsGHG74 KestrelTBF/TBPS ection 4 EMetallic EnclosuresFor Non-hazardous ApplicationsQBXPTB/PTCW-SeriesRS, RSM, RSSS ection 5 ENonmetallic EnclosuresFor Non-hazardous ApplicationsFiberglassNJB, NCE, NCS, NCDNJBWS ection 6 EEnclosure AccessoriesHubsGrounding PlatesGrounding BushingsDrains and BreathersCID 101 Corrosion InhibitorLNR Conduit US: 1-866-764-5454 CAN.
2 1-800-265-0502 Copyright 2013 Eaton s Crouse-Hinds Business1E1 EMetallic EnclosuresExplosionproof or Flameproof Hazardous ApplicationsDescriptionPage EnclosuresGUE / GUB Seriessee page 722 EJB Seriessee page 730 GUA Seriessee page 752 GUP Seriessee page 753 EGJ Seriessee page 754 Flameproof EnclosuresGUBA Seriessee page 759 EJB Seriessee page 750 GHG64 Seriessee page 751 Instrument HousingsEIH / EIHT Seriessee pages 755 756 GUB Seriessee pages 757 758 GUBA Seriessee page 759 EMH Seriessee page US: 1-866-764-5454 CAN: 1-800-265-0502 Copyright 2013 Eaton s Crouse-Hinds Business1 EGUE, GUB Junction BoxesCl. I, Div. 1 & 2, Groups B, C, DCl. II, Div. 1, Groups E, F, GCl. II, Div.
3 2, Groups F, GCl. IIINEMA 4*, 7 BCD, 9 EFGEx d IIC T6, IP66 Ex d IIC, IP66, ATEX certified ExplosionproofDust-IgnitionproofRaintigh tWet LocationsWatertightApplications:GUE, GUB series junction boxes are usedin threaded rigid conduit systems inhazardous areas: To function as a splice box, pull box orequipment and device enclosure To house wiring Indoors and outdoorsFeatures: Threaded construction throughoutpermits use in hazardous areas Bodies have thick walls so they can befactory or field drilled and tapped to meetNEC/CEC requirements for Class Ihazardous areas Covers are provided with a neoprene "O" ring gasket to meet NEMA/EEMAC 4requirements for a watertight seal Internal grounding lug provides a meansto ground enclosed equipment Boxes are machined for field installedmounting plates GUB boxes are ATEX certified whenordered with Suffix SA ATEX (notavailable for GU and GUE)Standard Materials: Bodies Feraloy iron alloy Covers copper-free aluminumStandard Finishes.
4 Feraloyiron alloy GU, GUE, GUB01,GUB02 electrogalvanized and aluminumacrylic paint. All other boxes zinc chro-mate primer and aluminum acrylic paint Copper-free aluminum naturalCertifications andCompliances: NEC/CEC:Class I, Division 1 & 2, Groups B, C, DClass II, Division 1, Groups E, F, GClass II, Division 2, Groups F, GClass III UL Standard: 1203 CSA Standard: No. 30 ATEX: Ex d IIC, IP66 ATEXC ertificate: PTB 01 ATEX 1019 U Ex d IIC, IP66, ATEX certified Junction Boxes WithoutHubs GU415/16" x 415/16" x 41/8"35/6" cover openingGUE55/16" x 55/16" x 53/8"35/6" cover openingGUB0161/2" x 7" x 53/4"53/8" cover openingGUB028" x 10" x 57/8"7" cover openingGUB0681/2" x 10" x 67/8"7" cover openingGUB0411" x 12" x 811/1695/8" cover openingGUB0881/2" 10" 613/167" cover openingOrdering Information:Junction boxes listed can be furnishedwith drilled and tapped conduit openings,subject to the limitations of maximumopening, number and spacing shown inTables 1, 2 and conduit liner ordering information, see page 860.
5 * NEMA 4 not available on GUB01110 and GUB15151. Order suffix SA ATEX. GUB01110 and GUB15151 are rated IP54. Dimensions provided are external. GUB01110 listed for Class I, Div. 1, Groups C & D only in Canada (CSA).Options:DescriptionSuffix Copper-free aluminum bodiesand covers (GUB01, GUB02,GUB03, GUB06 only) ..SA ATEX certified (GUB01 SA,GUB02 SA, GUB03 SA, GUB06 SA only) ..SA ATEX Factory installed mounting platefor relays, terminal blocks,electrical devices, etc ..MP Factory installed terminal on requestGUB0311" 12" 813/16"95/8" cover openingGUB01110*14" 18" 131/2"121/4" cover openingGUB1515119" 21" 165/8"163/4" cover openingTo Order:Step 1 Select the box required from photos at leftand dimensional drawings on next page.
6 Step 2 Select standard conduit arrangement fromTable 3 Determine maximum size conduit openingrequired from Table 2 (consider conduitopening spacing from Table 4).Step 4 Select appropriate symbol for requireddrilled and tapped holes from Table :Step 1 box required GUB06 Step 2 arrangement 108 Step 3 openings 11/2" at "a" and "c"; 1"at "b" and "d".Step 4 symbols are substituted andwritten in clockwise order starting withlocation "a". For this example:FCFC Complete Cat. No. is made up ofthree parts: Part 1 box number; Part 2 arrangement number; Part 3 symbols forconduit openings. For this example:GUB06-108-FCFC. When no opening isrequired at a particular location, usesymbol "0" (zero).
7 If none of the standard arrangements meetrequirements, send a sketch showingjunction box number with size and locationof each opening US: 1-866-764-5454 CAN: 1-800-265-0502 Copyright 2013 Eaton s Crouse-Hinds Business1 EGUE, GUB Junction BoxesOrdering InformationTable 1 Arrangements of Drilled and Tapped Conduit Openings For other arrangements, send sketch andcomplete descriptionConduit openingarrangements shown in theillustration should meet themajority of GUB junction boxeswill be supplied with drilledand tapped openings up tothe maximum size andnumber shown in Table 2 Maximum Size & No. of Drilled & Tapped HolesTop & Bottom (bb) Each Side (aa) Back Cat. #123412341234 Group D*GU11113 13/43/4 GUE21212 13/43/4 GUB01211/23/4211/211/213/43/43/4 GUB022213/42211/213/43/43/43/4 GUB062213/42211/212222 GUB082213/42211/212222 GUB032211/2122211/44431/23 GUB042211/2122211/44431/23 GUB0111022211/2222266431/2 GUB151515431/221/254436666 Group C GU11113 13/43/4 GUE21212 13/43/4 GUB01211/41/2211/41/23/43/43/43/4 GUB02211/23/42211/41/23/43/43/43/4 GUB06211/23/42211/41/222211/2 GUB08211/23/42211/41/222211/2 GUB032211/43/42211/21431/221/221/2 GUB042211/43/42211/21431/221/221/2 GUB0111022211/4222266431/2 GUB1515154325431/221/26665 Group B GU11113 13/43/4 GUE21212 13/43/4 GUB01211/41/2211/41/23/43/43/43/4 GUB02211/23/42211/41/23/43/43/43/4
8 GUB06211/23/42211/41/222211/2 GUB08211/23/42211/41/222211/2 GUB032211/43/42211/21431/221/221/2 GUB042211/43/42211/21431/221/221/2 GUB0111022211/422224444 GUB151514431/221/24431/221/24444*Group D chart is based on use of staggered unions. If adjacent unions are desired, additional spacing may be necessary. Sidewall and top and bottom sizes are based on all openings being in line. Backwall sizes are based on: two per side diagonal corners; four per side one in each corner; three per side triangular pattern with two on adjacent corners on long wall and third in center of opposite long wall. Conduit seals are required within 11/2" of all conduit entrances for Class I, Group C hazardous locations.
9 Conduit seals are required within 11/2" of all conduit entrances for Class I, Group B hazardous 3 Drilled & Tapped HolesSizeSymbol1/2A3/4B1C11/4E11/2F2G21/ 2H3J31/2K4 Lnone0 For conduit liner ordering information, see page US: 1-866-764-5454 CAN: 1-800-265-0502 Copyright 2013 Eaton s Crouse-Hinds Business1 EDimensionsTypepqrstvwxyGU13/81 1 GUE17/811/811/8 11/8 GUB0121/1615/821/821/815/87/813/425/3219 /16 GUB0221/16121/3221/1625/16121/3211/3221/ 167/813/4 GUB0621/16121/3225/1625/16121/3211/3221/ 167/813/4 GUB0821/16121/3221/1621/16121/3211/3221/ 167/813/4 GUB0333/821/235/1635/16315/3225/1615/322 5/16 GUB0433/8121/3235/1635/16315/3225/1615/3 225/16 GUB0111043/43 464 24121/3235/16 GUB1515164 51/457/84 242 4 DimensionsIn Inches:GUB 01, 02, 03, 06, 01110, and 15151.
10 Dottedmounting feet are included on GUB 03,01110, and 15151 only. GU and GUE areprovided with attachable mounting d e fghjk l mnGU415/16415/16313/16313/1635/8 41/819/1637/1623/841/8 GUE55/1655/1643/1643/1635/8 53/821/437/1631/241/8 GUB0161/2761/257/853/853/471/213/3253/43 1/1641/241/1661/4 GUB0281071/891/8783/4913/3257/8345/841/1 673/4 GUB0681/21073/887/8783/491/27/1673/841/4 513/1651/473/4 GUB0881/21073/887/8721/295/87/1673/841/4 53/1651/473/4 GUB03111293/4103/495/8103/4121/87/16813/ 16573/865/811 GUB04111293/4103/495/831/2121/87/16811/1 6573/861/211 GUB01110141/16181/161317121/416161131/26 13/16103/493/414 GUB15151207/8187/8191/8171/8163/41821116 5/89133/16113/818 Inside , GUB Junction BoxesTable 4 Conduit Spacings2.