Transcription of ENERGI
1 Metal-enclosed MV capacitor banksReady for quick assembly and ErectionManufactured with standardized partsCompletely assembled in factoryEconomicalENERGIP ower factor correctionand harmonic filteringHydroThermalWindNuclearSubstati onChemical FactoryCement FactorySteel Factorymetal-enclosed MV capacitor banks ENERGI Metal-enclosed medium voltage capacitor systemsand harmonic filters are designed forindoor and outdoor applications in commercial, industrial, and utility power systems requiring power factorcorrection, motor start support, harmonic filtering, as per IEC compliance, can increase systems capacitor bank generally consists of several single-phase or three-phase capacitor units assembledand interconnected to produce very powerful are an important aspect when considering power factor correction.
2 The rangeincludes a number of options to overcome these electrical equipment consists of nonlinear deviceswhich generate harmonics. Examples of thesedevices include the following:- Arc furnaces- In certain cases, transformers, reactors and rotating machines- Domestic appliancesHarmonics are not only found in industrial networks, they can also spread into the distribution networkand cause problems for other power users. Common problems that harmonics can produce include:- Overloading of capacitors , leading to malfunctioning and premature aging- Increased losses, eg.
3 Machines will operate at increased temperatures- Resonance problems between the inductive and capacitive parts of the network- Malfunctioning of control systems- Interference with telecommunication and computer equipment- Disturbances in ripple control systems- High currents in neutral conductorsHarmonics distort the sine wave (50 Hz or 60 Hz) sign which becomes apparent when a distorted sinewave mathematically Equipment containing electronics that control other apparatus. Eg. variable speed drives, soft starters,static compensators, rectifiers, BankQc/Sn > 15% the customer specifies automatic startup or shutdown for the capacitor bank (controlled byrelay).
4 The reactive power of the capacitor bank is split into steps with the possibility of starting orstopping more or fewer steps. The reactive power corresponds to the change in load BankQc/Sn < 15% the reactive power of the capacitor banks is constant and they are started up or shut downwhen a predetermined KVAr value is reached. It is an on/off type of CTSingle phasecapacitorUnbalance CTSingle phasecapacitorHRC fuseThree phasecapacitorDelta WiringDouble Star WiringH WiringVentilationStructure and EnclosureThe upper part of the capacitor bank consists of hot-dip galvanized steel profiles bolted together to astructure.
5 They are covered on the outside with painted or powder coated sheet-steel roof is made of double sheet-steel panels with powder coating. It is equipped with a surroundingof steel, and rain water madeThe doors consist of a sheet-steel construction with insulation and neoprene sealing. The hingesscrews are made of stainless steel. Every door features a central lock for profile cylinders, fixinga three-point rodDoorsCircuit diagramTo form banks of great power, there are several possibilities for cabling or connection bycapacitor units, namely:combination ofThe outside walls of the capacitor bank are designed as smallventilation elements.
6 They are composedelements with insect profile elements with insect protection, staggered with intermediate steel profileBase frameThe capacitor enclosure consists of a self-supporting baseframe made of sheet-steel girders. Cablesfrom below through the corresponding openings. For installation and sealing towards therequired that has to be constructed introducedground, a foundation isOverviewMetal-enclosed banksFor motor compensationFCB compensationFixed bankFCB 12 SHRC fusesHRC fusesUpto kVEnclosure terminal boxFixed bankUpto 12 kVHRC fusesInter connection busbarHRC fusesInrush reactorInter connection busbarHRC fuseThree phasecapacitorSteel enclosureUnbalance CTSingle phasecapacitorand Unbalance CT and RelayHRC fusesInrush reactorInter connection busbarSteel enclosureVoltage transformerProtection relayLine disconnector / Earth switchNeutral current
7 TransformerIndoor / outdoorIndoor / outdoorFCB 12 HApplicationsDesignModelMaximum VoltageCircuit ConnectionLocationType of protectionComponentsFCB - Fixed Capacitor BankACB - Automatic Capacitor BankOFCB - Open Fixed Capacitor BankB - BasicH - Harmonic FilterS - StandardsIndustrial and distribution NetworkAutomatic bankTransmission and Distribution NetworkFixed bankACB 36 SOFCB 36 OFCB 132 SUpto 12 kVUpto 36 kVUpto 36 kVUpto 132 kVand Unbalance CT and RelayHRC fusesHRC fusesInrush reactorInter connection busbarSteel enclosureVoltage transformerProtection relayLine disconnector / Earth switchVacuum contactorNeutral current transformerControl unitsAs per DesignOutdoorOutdoorIndoor / outdoorUnbalance CTUnbalance CTUnbalance CTFixed bankUpto 36 kVHRC fusesInrush reactorInter connection busbarSteel enclosureVoltage transformerProtection relayLine disconnector / Earth switchNeutral current transformerIndustrial and distribution NetworkUnbalance CTIndoor / outdoorHRC fusesand Unbalance CT and
8 RelayFCB 36 SFCB 36 HACB 12 SACB 12 HHarmonic filter on requstMobile banksSubstation banksSingle component FCB Capacitor Bank with terminal enclosure upto kV - - - 50 Hz / 60 HzTop and side entryLarge size for easy cable connectionsFloor mountingLower installation cost121. Capacitors2. HRC fuseThe capacitor banks are used for individual reactive compensation in MV motorsCapacitor for indoor or outdoor descriptionThese units are useful in industrial installations, since they are capable of hostinglow and medium-powered applications in small dataHRC fuseThree phasecapacitorDelta WiringCompositionEach capacitor bank comprises the following componentsThree phase capacitor unitApplicationsMotor control centerBranch CircuitsFree Standing - Steel EnclosureLarge motorsHRC kVNormal PhasesThree Phase unitLocationIndoor / OutdoorProtectionInternal fuses / HRC fusesFrequency50Hz or 60 HzABCFor MV motor compensation FCB Capacitor Bank upto kV - - - 50 / 60
9 Hz1. EnclosureBottom EntrySpecially designed for motor compensationCompact in sizeFactory Tested and ready for interconnection2. Capacitors3. Quick Discharge coil4. Inrush reactor5. HRC fusesProduct descriptionThe FCB are specially used for reactive compensation in MV motor in standard sizes to be shipped and assembled banks fabricated at our factory and brought to the site as fully assembledinstallationfor instantCompositionA pre-fabricated capacitor bank comprises the following main componentsOptionsApplicationsPumping StationsMiningCement and Steel IndustriesInrush Current limiting reactorsHRC fuseSteel EnclosureDoor with 3point pad lockable and SS hingesTwo set of quick
10 Discharge transformerFuse blown indicatorTechnical dataThree phase capacitor unitsHRC fuseThree phasecapacitorDelta WiringVoltageUpto kVFrequency50Hz or 60 HzNormal Power100 to 800 KVArThree Phase unitLocationIndoor / OutdoorProtectionInternal fuse / HRC fuseNo. of PhaseABCDEI ndustrial compensation FCB 12S or HFixed Capacitor Bank upto 12 kV - - - 50 Hz / 60 HzFactory Tested and ready for interconnectionGrounding switch availableInternal protection and control systemsHarmonic tuned, de-tuned filters availableA capacitor bank generally made up of several individual single phase capacitor assembledthroughout and inter connected to create the fixed descriptionTo Manufacture in advance.