technical data1893 Servicechilled, hot water, up to 60% glycolFlow Characteristicmodified equal percentageControllable Flow Range90 rotationSize [mm]4 [100]End Fittingfor use with ANSI Class 125/150 flangesBodyductile iron ASTM A536 Body FinishEpoxy powder coatedStem PackingEPDM (lubricated)SeatEPDMS haft416 stainless steelBushingsRPTFEDisc304 stainless steelBody Pressure Rating [psi]ANSI 125, standard class BNumber of Bolt Holes8 Lug Threads5/8-11 UNCM edia Temperature Range (Water)-22 F to 250 F [-30 C to 120 C]Close-Off Pressure200 psiRangeability10:1 (for 30 to 70 range)Maximum Velocity12 FPSCv600 lb [ kg]Leakage0%Servicingmaintenance freeFlow Pattern010201030504060807090203040605070 8010090100% OF MAXIMUM FLOW% OF Valve OPENINGP roduct Features200 psi (2 to 12 ) and 150 psi (14 to 24 ) 0% leakage, Long stem design allows for 2 insulation, Valve face-to-face dimensions comply with API 609 & MSS-SP-67, Compl

Technical data 1893 Service chilled, hot water, up to 60% glycol Flow Characteristic modified equal percentage Controllable Flow Range 90° rotation Size [mm] 4” [100]

Tags:

  Data, Technical, Technical data

Information

Domain:

Source:

Link to this page:

Please notify us if you found a problem with this document:

Other abuse

Transcription of F6100HD, 2-Way Butterfly Valve - belimo.com

1 technical data1893 Servicechilled, hot water, up to 60% glycolFlow Characteristicmodified equal percentageControllable Flow Range90 rotationSize [mm]4 [100]End Fittingfor use with ANSI Class 125/150 flangesBodyductile iron ASTM A536 Body FinishEpoxy powder coatedStem PackingEPDM (lubricated)SeatEPDMS haft416 stainless steelBushingsRPTFEDisc304 stainless steelBody Pressure Rating [psi]ANSI 125, standard class BNumber of Bolt Holes8 Lug Threads5/8-11 UNCM edia Temperature Range (Water)-22 F to 250 F [-30 C to 120 C]Close-Off Pressure200 psiRangeability10:1 (for 30 to 70 range)Maximum Velocity12 FPSCv600 lb [ kg]Leakage0%Servicingmaintenance freeFlow Pattern010201030504060807090203040605070 8010090100% OF MAXIMUM FLOW% OF Valve OPENINGP roduct Features200 psi (2 to 12 ) and 150 psi (14 to 24 ) 0% leakage, Long stem design allows for 2 insulation, Valve face-to-face dimensions comply with API 609 & MSS-SP-67, Completely assembled and tested, Ready for valves are designed to meet the needs of HVAC and commercial applications requiring 0% leakage for liquids.

2 Typical applications include chiller isolation, cooling tower isolation, change-over systems, large air handler coil control, bypass and process control applications. The large Cv values provide for an economical control Valve solution for larger flow applications. Designed for use in ANSI flanged piping NoteValves should be stored in a weather protected area prior to construction. Complete installation recommendations can be found in Belimo s Installation and Maintenance Instructions for F6 Butterfly 20 30 40 50 60 70 80 90 17 36 78 139 230 364 546 600 Suitable Actuators Non-SpringElectronic Fail-SafeF6100HD2*GMB(X), DRB(X), SY22*GKB(X), DKRB(X)Dimensions (Inches [mm])DBAEFC2* [454] [ ] [580] [ ] [100]F6100HD, 2-Way Butterfly ValveResilient Seat, 304 Stainless Steel Disc800-543-9038 USA866-805-7089 CANADA203-791-8396 LATIN AMERICA / CARIBBEANDate created, 07/07/2016 - Subject to change.

3 Belimo Aircontrols (USA), (Inches [mm]) [217] [ ] [464]21 [533] [100]Dimensions (Inches [mm]) (H), (H) [358] [ ] [516] [406] [100]Dimensions (Inches [mm])DBAEFC2*GK, 2* [454] [ ] [580] [ ] [100]Dimensions (Inches [mm]) [217] [ ] [ ] [363] [100]F6100HD, 2-Way Butterfly ValveResilient Seat, 304 Stainless Steel Disc800-543-9038 USA866-805-7089 CANADA203-791-8396 LATIN AMERICA / CARIBBEANDate created, 07/07/2016 - Subject to change. Belimo Aircontrols (USA), (Inches [mm])ceilingDBAEFCJSYABCDEF13 [332] [ ] [628] [530] [100]F6100HD, 2-Way Butterfly ValveResilient Seat, 304 Stainless Steel Disc800-543-9038 USA866-805-7089 CANADA203-791-8396 LATIN AMERICA / CARIBBEANDate created, 07/07/2016 - Subject to change.

4 Belimo Aircontrols (USA), Data96749 Power Supply24 VAC 20%, 50/60 HzPower Consumption Running12 W Power Consumption Holding3 W Transformer Sizing21 VA (class 2 power source)Electrical Connectionterminal blockOverload Protectionelectronic thoughout 0 to 90 rotationOperating Range Y2 to 10 VDC, 4 to 20 mA w/ ZG-R01 (500 , 1/4 W resistor), variable (VDC, floating point, on/off)Input Impedance100 k ( mA), 500 , 1000 (on/off)Torque801 in-lbs [90 Nm] minimumPosition IndicationhandleManual Overrideexternal push buttonRunning Time (Motor)150 sec (default), variable (90 to 150 sec)Running Time (Fail-Safe)35 secHumidity5 to 95% RH non condensing (EN 60730-1)Ambient Temperature Range-22 F to 122 F [-30 C to 50 C]Storage Temperature Range-40 F to 176 F [-40 C to 80 C]HousingNEMA 2, IP42, UL enclosure type 2 Housing MaterialpolycarbonateNoise Level (Motor)<45 dB (A) Noise Level (Fail-Safe)<50 dB (A) Servicingmaintenance freeQuality StandardISO 9001 DKRX24-3-TOn/Off, Floating Point, Electronic Fail-Safe, 24V800-543-9038 USA866-805-7089 CANADA203-791-8396 LATIN AMERICA / CARIBBEANDate created, 07/07/2016 - Subject to change.

5 Belimo Aircontrols (USA), DiagramsINSTALLATION NOTESP rovide overload protection and disconnect as triac sink the Common connection from the actuator must be connected to the Hot connection of the controller. Position feedback cannot be used with a triac sink controller; the actuator internal common reference is not may be connected in parallel if not mechanically linked. Power consumption and input impedance must be or IN4007 diode. (IN4007 supplied, Belimo part number 40155).16 Actuators are provided with a numbered screw terminal strip instead of a may be controlled in parallel. Current draw and input impedance must be wiring required for piggy-back applications.

6 Feedback from Master to conrol input(s) of Slave(s).Meets cULus requirements without the need of an electrical ground connection.!WARNING! LIVE ELECTRICAL COMPONENTS!During installation, testing, servicing and troubleshooting of this product, it may be necessary to work with live electrical components. Have a qualified licensed electrician or other individual who has been properly trained in handling live electrical components perform these tasks. Failure to follow all electrical safety precautions when exposed to live electrical components could result in death or serious injury. LineVolts1111624 VAC Transformer (AC Only)(1)(2) (3)CommonHot + InputOn/Off LineVolts ( ) (1) Common(2) Hot + (3) Y Input1101646471224 VAC Transformer (AC Only)Floating PointDKRX24-3-TOn/Off, Floating Point, Electronic Fail-Safe, 24V800-543-9038 USA866-805-7089 CANADA203-791-8396 LATIN AMERICA / CARIBBEANDate created, 07/07/2016 - Subject to change.