specification Sheet Omega Flex Limited has used its best efforts in the production of this information but makes no warranty about the content and will not be held liable under any circumstances for any direct or indirect damages resulting from its use. Users have the responsibility to ensure the information is current and appropriate at the time of application. This Information Sheet must be read in association with the Tracpipe Design and Installation specification available at 1 OMEGAFLEX , Ltd.

SPECIFICATION SHEET Omega Flex Limited has used its best efforts in the production of this information but makes no warranty about the content and will not be held liable under any circumstances for any

Tags:

  Sheet, Specification, Spec, Final, Final spec sheet

Information

Domain:

Source:

Link to this page:

Please notify us if you found a problem with this document:

Other abuse

Transcription of Final Spec Sheet - Tracpipe

1 specification Sheet Omega Flex Limited has used its best efforts in the production of this information but makes no warranty about the content and will not be held liable under any circumstances for any direct or indirect damages resulting from its use. Users have the responsibility to ensure the information is current and appropriate at the time of application. This Information Sheet must be read in association with the Tracpipe Design and Installation specification available at 1 OMEGAFLEX , Ltd.

2 Tracpipe Flexible Gas Piping specification Sheet specification date _____ ProjectName_____ Model Number(s) - FGP-SS4-50 FGP-SS4-40 FGP-SS4-32 FGP-SS4-28 FGP-SS4-22 FGP-SS4-15 FGP-SS4-12 Note: This Information Sheet should be read in conjunction with the Tracpipe Design and Installation specification available from If further information is required, please e-mail A. Standards & Certifications: All Semi-Rigid CSST gas piping system components must be: BS 7838 or BS EN 15266 Certified (CSST) Semi Rigid Flexible Gas Piping with Mechanical Attachment AutoFlare Fittings that conform to the latest BS standards for safe performance up to DN50.

3 BS 7838 specification for corrugated stainless steel semi-rigid pipe and associated fittings for low-pressure gas pipework of up to DN 50. BS 6891 Installation of low pressure gas pipework of up to 35 mm ( ) in domestic premises (2nd family gas). - specification BS 5482 Code of practice for domestic butane and propane-gas burning installations Part 1: Installations at permanent dwellings, residential and commercial premises, with installation pipework sizes not exceeding DN25 for steel and DN28 for corrugated stainless steel or copper.

4 IGEM/UP/2 Edition 2. The Institution of Gas Engineers and Managers communication 1729, Installation pipework on industrial and commercial Premises. B. Stainless Steel Tubing: Tubing shall be made from 300 series Stainless Steel Strip conforming to BS 7838. Tubing shall not be subjected to heat treating or annealing after the corrugation forming operation. Tubing shall be suitable for operation with Natural Gas, LP (Propane) and Butane. Tubing is rated for 500millibar (.)

5 5bar) (BS 7838 & BS EN 15266). FGP-SPS-002 specification Sheet Omega Flex Limited has used its best efforts in the production of this information but makes no warranty about the content and will not be held liable under any circumstances for any direct or indirect damages resulting from its use. Users have the responsibility to ensure the information is current and appropriate at the time of application. This Information Sheet must be read in association with the Tracpipe Design and Installation specification available at 2 C.

6 Polyethylene Jacket: The jacket shall be extruded from fire-retarded Polyethylene. Chlorinated plastics such as PVC are not permitted. Polyethylene is to be resistant to UV (ultra-violates). D. AutoFlare Mechanical Attachment Fittings: Fittings shall be made from yellow brass. Fittings shall be equipped with a stainless steel insert to pilot on the tubing ID (internal diameter) and provide a reliable flaring operation. AutoFlare fittings are available in straight male (BSP), straight female, copper compression, tee, reducer tee and coupling configurations.

7 Fittings shall provide a metal-to-metal seal no (rubber, pastes or plastic based gaskets) Shut-off valves: (ECV or AECV) must be approved for fuel gas service and shall be rated for the same pressure as the gas piping system installed. F. Exposed Stainless Steel Protection: TAPE WRAP-AFTER GAS TIGHTNESS TEST Care must be taken after pressure test to ensure that no stainless steel pipe is visible. Any portions of exposed stainless steel behind the fitting nut shall be wrapped with self-bonding silicone tape Tracpipe P/N FGP-915-10H-12, (25mm wide), or FGP-915-20H12PO, (50mm wide).

8 This will reduce the possibility of later external corrosive attack. G. Unvented Voids: Pipe in Pipe System Ducts having a small cross sectional area and volume, ( or less and or less, respectively), are considered to be adventitiously ventilated. BS EN 1775 and IGEM/UP/2 Edition 2, provided that the route is the shortest practicable, the integrity of the cover is maintained, and the end fittings (where the gas tight cover ends) are in a ventilated area.

9 Tracpipe s cover has been independently tested by BSI at pressures from 20mbar to 2bar to demonstrate that it performs satisfactorily as a sleeve, allowing free passage for gas flow between the stainless steel pipe and the outer cover to the end fittings, throughout this pressure range. The pipework is sleeved continuously through the unventilated duct or void, with the sleeve ventilated at one or both ends into a safe place. The unventilated duct or void is filled with a crushed inert infill to reduce to a minimum the volume of any gas which may accumulate.

10 FGP-SPS-002 specification Sheet Omega Flex Limited has used its best efforts in the production of this information but makes no warranty about the content and will not be held liable under any circumstances for any direct or indirect damages resulting from its use. Users have the responsibility to ensure the information is current and appropriate at the time of application. This Information Sheet must be read in association with the Tracpipe Design and Installation specification available at 3 In certain situations Tracpipe can be used as a pipe in pipe installation.