FIRE AND SMOKE PROTECTION FEATURES

SECTION provisions of this chapter shall govern thematerials, systems and assemblies used for structural fireresistance and fire -resistance-rated construction separation ofadjacent spaces to safeguard against the spread of fire andsmoke within a building and the spread of fire to or Multiple use fire assemblies that servemultiple purposes in a building shall comply with all of therequirements that are applicable for each of the individual 713 SHAFT provisions of this section shall apply toshafts required to protect openings and penetrations throughfloor/ceiling and roof/ceiling assemblies.

The fire-resistance rating of concrete masonry units composed of a combination of aggregate types or where plaster is applied directly to the concrete masonry shall be determined in accordance with ACI 216.1/TMS 0216.

Tags:

  Fire, Combination

Information

Domain:

Source:

Link to this page:

Please notify us if you found a problem with this document:

Other abuse

Advertisement

Transcription of FIRE AND SMOKE PROTECTION FEATURES

1 SECTION provisions of this chapter shall govern thematerials, systems and assemblies used for structural fireresistance and fire -resistance-rated construction separation ofadjacent spaces to safeguard against the spread of fire andsmoke within a building and the spread of fire to or Multiple use fire assemblies that servemultiple purposes in a building shall comply with all of therequirements that are applicable for each of the individual 713 SHAFT provisions of this section shall apply toshafts required to protect openings and penetrations throughfloor/ceiling and roof/ceiling assemblies.

2 Exit access stairwaysand exit access ramps shall be protected in accordance withthe applicable provisions of Section 1009. Interior exitstairways and interior exit ramps shall be protected inaccordance with the requirements of Section Construction. Shaft enclosures shall be constructed asfire barriers in accordance with Section 707 or horizontalassemblies in accordance with Section 711, or shaft enclosure shall be of materialspermitted by the building type of provisions of this section shall govern thematerials and methods of construction used to protect throughpenetrations and membrane penetrations of horizontalassemblies and fire -resistance-rated wall fire -resistance-rated into orthrough fire walls, fire barriers.

3 SMOKE barrier walls and firepartitions shall comply with Sections through in SMOKE barrier walls shall comply with Through penetrations. Through penetrations offire-resistance-rated walls shall comply with or :Where the penetrating items are steel, ferrousor copper pipes, tubes or conduits, the annular spacebetween the penetrating item and the fire -resistance-ratedwall is permitted to be protected as follows:1. In concrete or masonry walls where thepenetrating item is a maximum 6-inch (152 mm)nominal diameter and the area of the openingthrough the wall does not exceed 144 squareinches ( m2), concrete, grout or mortar ispermitted where it is installed the full thickness ofthe wall or the thickness required to maintain thefire-resistance rating; or2.

4 The material used to fill the annular space shallprevent the passage of flame and hot gasessufficient to ignite cotton waste when subjected toASTM E119 or UL 263 time-temperature fireconditions under a minimum positive pressuredifferential of inch ( Pa) of water at thelocation of the penetration for the time periodequivalent to the fire -resistance rating of theconstruction 721 PRESCRIPTIVE fire provisions of this section containprescriptive details of fire -resistance-rated building elements,components or assemblies. The materials of construction listedin Tables (1), (2), and (3) shall be assumed tohave the fire -resistance ratings prescribed therein.

5 Wherematerials that change the capacity for heat dissipation areincorporated into a fire -resistance-rated assembly, fire testresults or other substantiating data shall be made available tothe building official to show that the required fire -resistance-rating time period is not Unit masonry PROTECTION . Where required, metalties shall be embedded in bed joints of unit masonry forprotection of steel columns. Such ties shall be as set forth inTable (1) or be equivalent CBC - CHAPTER 7 - fire AND SMOKEPROTECTION FEATURES6 Sec. 701 - CBC, 201, 216, 218, 219, 236 CHAPTER 7* fire AND SMOKE PROTECTION FEATURES * Only portions of this section are shown which are particularly applicable to masonry construction.

6 For additional information see the Chapter 72013 CBC - CHAPTER 7 - fire AND SMOKEPROTECTION FEATURES7 Table (2)2013 CBC, 241, 248, 249 MATERIALITEMNUMBERCONSTRUCTIONMINIMUM FINISHEDTHICKNESS FACE-TO-FACEb(inches)4hours3hours2hours1 hour1. Brick of clay brick of clay or brick, not brick unit wall, grout or filled with perlite vermiculite or expanded nominal thick units at least 75 percent solid backed with a hat-shaped metalfurring channel 3/4 thick formed from sheet metal attached to the brick wallon 24 centers with approved fasteners, and 1/2 Type X gypsum wallboard attachedto the metal furring strips with 1 -long Type S screws spaced 8 on center.

7 5d 2. combination ofclay brick andload-bearinghollow clay solid brick and 4 tile (at least 40 percent solid). 8 solid brick and 8 tile (at least 40 percent solid).12 3. Concretemasonry , gExpanded slag or , gExpanded clay, shale or , cinders or air-cooled , gCalcareous or siliceous Solid concreteh, aggregate aggregate Glazed orunglazed facingtile, 2 unit cored 15 percent maximum and one 4 unit cored 25 percent maximumwith 3/4 mortar-filled collar joint. Unit positions reversed in alternate courses. 63/8 2 unit cored 15 percent maximum and one 4 unit cored 40 percent maximumwith 3/4 mortar-filled collar joint.

8 Unit positions side with 3/4 gypsum plaster. Twowythes tied together every fourth course with No. 22 gage corrugated metal ties. 63/4 unit with three cells in wall thickness, cored 29 percent maximum. 6 2 unit cored 22 percent maximum and one 4 unit cored 41 percent maximumwith 1/4 mortar-filled collar joint. Two wythes tied together every third course (No. 22 galvanized sheet steel gage) corrugated metal ties. 6 4 unit cored 25 percent maximum with 3/4 gypsum plaster on one side. 43/4 4 unit with two cells in wall thickness, cored 22 percent maximum. 4 unit cored 30 percent maximum with 3/4 vermiculite gypsum plaster on oneside.

9 41/2 4 unit cored 39 percent maximum with 3/4 gypsum plaster on one side. 41/2 TABLE (2)RATED fire -RESISTANCE PERIODS FOR VARIOUS WALLS AND PARTITIONSa, o, pFor SI: 1 inch = mm, 1 square inch = mm2, 1 cubic foot = Staples with equivalent holding power and penetration shall be permitted to be used as alternate fasteners to nails for attachment to wood Thickness shown for brick and clay tile is nominal thicknesses unless plastered, in which case thicknesses are net. Thickness shown for concrete masonry and claymasonry is equivalent thickness defined in Section for concrete masonry and Section for clay masonry.

10 Where all cells are solid grouted orfilled with silicone-trated perlite loose-fill insulation; vermiculite loose-fill insulation; or expanded clay, shale or slate lightweight aggregate, the equivalentthickness shall be the thickness of the block or brick using specified dimensions as defined in Chapter 21. Equivalent thickness may also include the thickness ofapplied plaster and lath or gypsum wallboard, where For units in which the net cross-sectional area of cored brick in any plane parallel to the surface containing the cores is at least 75 percent of the gross cross-sectional area measured in the same Shall be used for nonbearing purposes The fire -resistance time period for concrete masonry units meeting the equivalent thicknesses required for a 2-hour fire -resistance rating in Item 3.