Appendix (13). Appendix 13. FIRE SAFETY REQUIREMENTS FOR LIQUEFIED PETROLEUM . GAS (LPG) cylinder INSTALLATIONS. 1 SCOPE. This Fire SAFETY Guidelines covers outdoor and indoor LPG cylinder installations. It is intended for commercial, industrial and residential premises with eating outlets, eating places, canteens, restaurants and other eateries which use LPG for cooking purposes. It is also intended for industrial applications involving hot works. 2 GENERAL REQUIREMENTS . All LPG cylinder installations shall be located outdoors and on the ground levels for all commercial and industrial buildings. Locating LPG cylinders indoor is normally not permitted, unless otherwise approved by the Commissioner SCDF under special circumstances (please refer to the fire SAFETY REQUIREMENTS for use/storage of LPG.)

FIRE SAFETY REQUIREMENTS FOR LIQUEFIED PETROLEUM GAS (LPG) CYLINDER INSTALLATIONS 1 SCOPE 1.1 This Fire Safety uidelineG s covers outdoor and indoor LPG cylinder installations. It is intended for commercial, industrial and residential premises with eating outlets, eating places, canteens, restaurants and other eateries which use LPG for cooking

Tags:

  Installation, Requirements, Safety, Cylinder, Petroleum, Liquefied, Safety requirements for liquefied petroleum, Safety requirements for liquefied petroleum gas, Cylinder installations

Information

Domain:

Source:

Link to this page:

Please notify us if you found a problem with this document:

Other abuse

Transcription of FIRE SAFETY REQUIREMENTS FOR LIQUEFIED PETROLEUM …

1 Appendix (13). Appendix 13. FIRE SAFETY REQUIREMENTS FOR LIQUEFIED PETROLEUM . GAS (LPG) cylinder INSTALLATIONS. 1 SCOPE. This Fire SAFETY Guidelines covers outdoor and indoor LPG cylinder installations. It is intended for commercial, industrial and residential premises with eating outlets, eating places, canteens, restaurants and other eateries which use LPG for cooking purposes. It is also intended for industrial applications involving hot works. 2 GENERAL REQUIREMENTS . All LPG cylinder installations shall be located outdoors and on the ground levels for all commercial and industrial buildings. Locating LPG cylinders indoor is normally not permitted, unless otherwise approved by the Commissioner SCDF under special circumstances (please refer to the fire SAFETY REQUIREMENTS for use/storage of LPG.)

2 Cylinders within eating outlets are as stated in Annex H). Private dwelling house is allowed to have a maximum of 30kg (2 x 15kg cylinders) to be installed or stored within the dwelling unit for domestic use. NFPA 54 and NFPA 58 shall be referred to for REQUIREMENTS not effected or covered under this Fire SAFETY Guidelines. All LPG cylinders installations in commercial or industrial premises, including their manifold/piping systems, shall be approved by SCDF. LPG plans submitting for approval shall include the following items: a. QP's endorsements of LPG's storage and manifold system b. Location and site plans c. Schematic diagrams of the LPG supply system showing change-over valve, vaporizer, regulator, emergency shut-off valve, remote cut-off device, knock- out pot, pipe entry and all other required SAFETY features d.

3 Plan and elevation views showing the following details: Location, quantity and capacity (in kg) of LPG cylinders Locations of ancillary fixtures and fittings, vaporizer, regulators, emergency shut-off valve, change-over valves, remote cut-off device, knock-out pot, pipe entries, etc. Housing for the LPG cylinders, cabinets, fencing, compartment wall, etc. M1. Appendix 13 - 1. all openings (doors, air intakes, windows, drains, manholes, etc.) and exits adjacent all openingsto the LPG air (doors, installation intakes, windows, drains, manholes, etc.) and exits adjacent to the LPG installation Locations of hydrant, access way, access road, car parking area, building and boundary Locations lines, source of hydrant, accessof ignition, way, access etc. road, car parking area, building and boundary lines, source of ignition, etc.

4 Fire SAFETY provisions, fire hose reel, fire extinguisher, sprinkler protection Fire SAFETY (ifprovisions, any), gas leak (if any), fire hose reel, extinguisher, sprinkler protection (if any), gas leak detector (if any), etc. For LPG cylinders installation involving mechanical ventilation system and/or fire suppression For system, separate LPG cylinders Mechanical installation involvingVentilation mechanicalplan and/or Fire ventilation Protection system and/or plan fire shall be submitted suppression system,toseparate SCDF for approval. Ventilation plan and/or Fire Protection plan Mechanical shall be submitted to SCDF for approval. 3 DESIGN REQUIREMENTS . 3 DESIGN REQUIREMENTS . Main Considerations for Use of LPG. Main Considerations for Use of LPG. The following factors shall be taken into consideration when deciding on the practicality The followingand reasonableness factors shall be to use LPG: taken into consideration when deciding on the practicality and reasonableness to use LPG: a.

5 Adequacy of ventilation b. a. Extent Adequacy of usage of individual rooms of ventilation c. b. Existing Extent offire hazard usage of individual rooms d. c. Suitable Existing means of escape fire hazard e. d. Fire fighting Suitable means equipment of escapeand provisions. e. Fire fighting equipment and provisions. Codes of Practice & Standards Codes of Practice & Standards All cylinders and their ancillary fittings shall be designed, fabricated and tested in accordance All cylinderswithandthetheir accepted codefittings ancillary or standard shall as bestated in Annex designed, A. and tested in fabricated accordance with the accepted code or standard as stated in Annex A. Fire Stopping Fire Stopping All pipes penetrating fire wall or floor slab shall be fire stopped appropriately.

6 Pressure All pipes penetrating fire wall or floor slab shall be fire stopped appropriately. Pressure No liquid LPG or LPG vapor at pressure exceeding 20 psi (approximately 138 kPa). shallliquid No be piped LPGinto or any LPG building. vapor at pressure exceeding 20 psi (approximately 138 kPa). shall be piped into any building. Fire Extinguisher Fire Extinguisher The LPG installation shall be provided with at least one approved portable B:C rating dry chemical The fire extinguisher LPG installation shall be having provided a minimum capacity with at least of 9kg. portable B:C rating one approved dry chemical fire extinguisher having a minimum capacity of 9kg. Warning Sign / Notice Warning Sign / Notice A warning sign or notice of minimum size of 800mm x 600mm shall be permanently andwarning A legibly displayed sign or noticeat theoffront of the size minimum installation .

7 Of 800mm x 600mm shall be permanently and legibly displayed at the front of the installation . M2. M2. Appendix 13 - 2. Red letterings of minimum height of 40mm which reads: "LPG / HIGHLY. FLAMMABLE / NO SMOKING / NO NAKED LIGHTS" on white background shall be written on the left portion of the warning sign/notice. Immediately under the classification of Hazmat, three equal boxes showing: (1) the emergency action (Hazchem Code); (2) the licensed quantity in litres and (3) the telephone number and name of the supplier company whom specialized advice can be obtained at all times. (see Annex G). 4 REQUIREMENTS FOR OUTDOOR LPG cylinder installation . Locating of LPG Cylinders LPG cylinders shall be placed on a firm, clean, dry and level base. They shall be sited at ground level and a well-ventilated area where any gas leakage can safely and rapidly disperse.

8 They shall not be placed close to any passageways or exits and shall not cause any obstruction or danger to the occupants during gas leakage or fire. LPG cylinders shall not be located within 3m of any fire exit route of a building having only one exit. If the 3m distance cannot be complied with, a 2-hour fire rated masonry wall shall be provided between the fire exit and the LPG installation so as to achieve the equivalent 3m horizontal distance. The masonry wall shall be at least high. The LPG cylinders shall be located at least horizontally away from any openings (windows, doors, air vents, balanced-flue outlets, etc.) of the building having more than one exit. If the distance cannot be complied, a 2-hour fire rated masonry wall must be provided between the openings and the installation so as to maintain a horizontal distance.

9 The masonry wall should be at least high. A minimum distance of 3m must be maintained between the edge of a vehicle parking lot. LPG cylinders shall be located at least 5m horizontally from any mechanical air intake which is below any part of the manifold system and from any mechanical intake which is above any part of the manifold system. LPG cylinders may be installed below windows or openings provided that there is a minimum distance of 150mm between the top of any cylinder or the manifold system and the bottom of the windows or openings. LPG cylinders of total capacity up to 600kg shall be located at least from any uncovered opening that is below the level of the cylinders, such as drains, pits, openings to basements, etc. For LPG cylinders having total capacity above 600kg, the distance from any uncovered opening shall be at least 3m.

10 LPG cylinders shall be located at least 3m away from any boundary and any fire engine accessway. LPG cylinders shall be located at least 10m away from any fire hydrant. M3. Appendix 13 - 3. Protection to LPG cylinder installation LPG cylinders located in places accessible to the public shall be protected and locked against tampering and accidental damage by fencing of height not less than , a suitable housing or a cabinet made of non-combustible material. There shall not be any corrosive, toxic or oxidizing materials located within 6 meters from the cylinder installation . SAFETY Provisions For air-conditioned premises, an approved gas-leak detection system shall be provided in the area or compartment where the internal LPG pipes and fittings are installed, with a local alarm connected to a main fire alarm panel.