Example: air traffic controller

FireLoc Butterfly Valve Series 705 with Weatherproof ...

FireLock Butterfly Valve Series 705 with Weatherproof Actuator PRODUCT DESCRIPTION. Available Sizes: 2 12"/50 300 mm cULus Listed, LPCB Listed, FM and VdS Approved for service up to 300 psi/2068 kPa /20 bar. Designed for fire protection services only. Features a Weatherproof actuator housing Approved for indoor and outdoor use. Actuation options: Hand wheel (2 12 /50 300 mm). Exclusively for use with pipe and Victaulic products which feature ends formed with the Victaulic Original Groove System (OGS) groove profile (see section for Reference Materials).

victaulic.com 10.81 5662 Rev H Updated 03/2017 © 2017 Victaulic Company. All rights reserved. ALWAYS REFER TO AN NOTIFICATIONS AT THE END OF THIS DOCUMENT REGARDING ...

Tags:

  Valves

Information

Domain:

Source:

Link to this page:

Please notify us if you found a problem with this document:

Other abuse

Transcription of FireLoc Butterfly Valve Series 705 with Weatherproof ...

1 FireLock Butterfly Valve Series 705 with Weatherproof Actuator PRODUCT DESCRIPTION. Available Sizes: 2 12"/50 300 mm cULus Listed, LPCB Listed, FM and VdS Approved for service up to 300 psi/2068 kPa /20 bar. Designed for fire protection services only. Features a Weatherproof actuator housing Approved for indoor and outdoor use. Actuation options: Hand wheel (2 12 /50 300 mm). Exclusively for use with pipe and Victaulic products which feature ends formed with the Victaulic Original Groove System (OGS) groove profile (see section for Reference Materials).

2 CERTIFICATION/LISTINGS. G410001 104j/04. ALWAYS REFER TO ANY NOTIFICATIONS AT THE END OF THIS DOCUMENT REGARDING PRODUCT INSTALLATION, MAINTENANCE OR SUPPORT. System No. Location Spec Section Paragraph Submitted By Date Approved Date 5662 Rev I Updated 07/2020 2020 Victaulic Company. All rights reserved. 1. CERTIFICATION/LISTINGS. Approval/Listing Service Pressures Series 705 Butterfly Valve Size cULus FM Vds LPCB. 2. up to 300psi/2068kPa up to 300psi/2068kPa up to 300psi/2068kPa up to 300psi/2068kPa 50.

3 2 . up to 300psi/2068kPa up to 300psi/2068kPa n/a up to 300psi/2068kPa 65. mm up to 300psi/2068kPa up to 300psi/2068kPa up to 300psi/2068kPa up to 300psi/2068kPa 3. up to 300psi/2068kPa up to 300psi/2068kPa up to 300psi/2068kPa up to 300psi/2068kPa 80. 4. up to 300psi/2068kPa up to 300psi/2068kPa up to 300psi/2068kPa up to 300psi/2068kPa 100. 5. up to 300psi/2068kPa up to 300psi/2068kPa n/a up to 300psi/2068kPa 125. mm up to 300psi/2068kPa up to 300psi/2068kPa up to 300psi/2068kPa up to 300psi/2068kPa 6.

4 Up to 300psi/2068kPa up to 300psi/2068kPa up to 300psi/2068kPa up to 300psi/2068kPa 150. mm up to 300psi/2068kPa up to 300psi/2068kPa n/a up to 300psi/2068kPa 8. up to 300psi/2068kPa up to 300psi/2068kPa up to 300psi/2068kPa up to 300psi/2068kPa 200. 10. up to 300psi/2068kPa up to 300psi/2068kPa n/a up to 300psi/2068kPa 250. 12. up to 300psi/2068kPa up to 300psi/2068kPa n/a up to 300psi/2068kPa 300. SPECIFICATIONS MATERIAL. Body: Ductile Iron conforming to ASTM A-536, Grade 65-45-12. End Face, 2 6 /50 150 mm: Ductile Iron conforming to ASTM A-536, Grade 65-45-12.

5 Seal Retainer, 8 12 /200 300 mm: Ductile Iron conforming to ASTM A-536, Grade 65-45-12. Body Coating: Black alkyd enamel Disc: Ductile Iron conforming to ASTM A-536, Grade 65-45-12, with electroless nickel coating conforming to ASTM B-733. Seat: Grade E EPDM. Stems: 416 stainless steel conforming to ASTM A-582. Stem Seal Cartridge: C36000 brass Bearings: Stainless steel with TFE lining Stem Seals: EPDM. Stem Retaining Ring: Carbon steel Actuator: 2 8"/50 200 mm: Brass or bronze traveling nut on a steel lead screw, in a ductile iron housing 10 12"/250 300 mm: Steel worm and cast iron quadrant gear, in a cast iron housing 5662 Rev I Updated 07/2020 2020 Victaulic Company.

6 All rights reserved. 2. DIMENSIONS. Series 705. H. C. B. F J. G E A D. Size Dimensions Actual Outside E to E DIA. Nominal Diameter A B C D E F G H J. inches inches inches inches inches inches inches inches inches inches inches mm mm mm mm mm mm mm mm mm mm mm 2 . 2 1/2 . 73 mm . 3 . 108 mm . 4 . 133 mm . mm . 5 . 159 mm .. 6 . 8 10 . 273 12 . NOTE. Optional "/15 mm tap available. Contact Victaulic for details. 5662 Rev I Updated 07/2020 2020 Victaulic Company. All rights reserved. 3. PERFORMANCE. Series 705.

7 The chart expresses the frictional resistance of Victaulic Series 705 Butterfly Valve in equivalent feet/meters of straight pipe. Nominal Outside Equivalent Size Diameter mm mm Feet/m inches inches of pipe 2 6. 50 2 1/2 6. 65 6. mm 3 7. 80 4 8. 100 8. 108 mm 108 mm 5 12. 125 12. 133 mm 133 mm 12. mm 6 14. 150 14. 159 mm 159 mm 14. mm 8 16. 200 10 18. 250 12 19. 300 5662 Rev I Updated 07/2020 2020 Victaulic Company. All rights reserved. 4. PERFORMANCE. Series 705. CV values for flow of water at +60 F/+16 C through a fully open Valve are shown in the table below.

8 For additional details, contact Victaulic. Formulas for Cv values Formulas for Kv values P = P. Q2 = Q2 Where: Where: Where:Where: Cv2 Cv2 Q = Flow Q =(GPM). Flow (GPM) Q = Flow Q = (m Flow 3. /hr). (m3/hr). P = Pressure P = Pressure Drop (psi). Drop (psi) P = Pressure P = Pressure Drop (Bar). Drop (Bar). Q = CQv x= C Px P Cv = Flow Cv =Coefficient Flow Coefficient v Kv = Flow Kv = Coefficient Flow Coefficient Valve Size Full Open Valve Size Full Open Actual Actual Nominal Outside Nominal Outside Size Diameter Flow Coefficient Size Diameter Flow Coefficient inches inches Cv inches inches Kv mm mm mm mm 2 2 170 147.

9 50 50 2 1/2 2 1/2 260 225. 65 65 mm 260 mm 225. 3 3 440 380. 80 80 4 4 820 710. 100 100 108 mm 108 mm 820 108 mm 108 mm 710. 5 5 1200 1040. 125 125 133 mm 133 mm 1200 133 mm 133 mm 1040. mm 1200 mm 1040. 6 6 1800 1560. 150 150 159 mm 159 mm 1800 159 mm 159 mm 1560. mm 1800 mm 1560. 8 8 3400 2940. 200 200 10 10 5800 5020. 250 250 12 12 9000 7790. 300 300 5662 Rev I Updated 07/2020 2020 Victaulic Company. All rights reserved. 5. NOTIFICATIONS. WARNING. Read and understand all instructions before attempting to install, remove, adjust, or maintain any Victaulic piping products.

10 Depressurize and drain the piping system before attempting to install, remove, adjust, or maintain any Victaulic piping products. Wear safety glasses, hardhat, and foot protection. Failure to follow these instructions could result in death or serious personal injury and property damage. REFERENCE MATERIALS. Switch and Wiring 1. The supervisory switch contains two single pole, UL LISTED. double throw, pre wired switches. JUNCTION BOX. 2. Switches are rated: CONDUIT. 10 amps @ 125 or 250 VAC/60 Hz " NPT.


Related search queries