Example: tourism industry

FIRESTOP SUBMITTAL PACKAGE - hiltiman.com

Hilti, Inc., 5400 South 122nd East Avenue, Tulsa, OK 74121, (800) 879-8000 FIRESTOP SUBMITTAL PACKAGEHVACM aterialsFS-ONE Intumesent CaulkCP 606 AcrylicIncludes:Technical and Installation DataUL Certificate of ComplianceLEED informationMSDSUL DetailsConcrete Assemblies CAJ 7084b - Max. 20 spiral wound or 12 sheet metal duct CAJ 8166a - HVAC line set (sleeve optional) (bottom side access) CAJ 7051d - Max. 30 x 30 sheet metal duct w/o damper WJ 7021g - Max. 48 x 24 sheet metal duct w/o damper WJ 7022d - Max. 20 spiral wound duct w/o damper, or 12 sheet metal duct WJ 7029a - Max. 24 x 12 sheet metal duct with glass fiber duct insulation WJ 7085a - Max. 24 x 24 sheet metal ductGypsum Wall AssembliesWL 7040g - Max. 48 x 24 sheet metal duct w/o damperWL 7042d - Max.

Hilti, Inc., 5400 South 122nd East Avenue, Tulsa, OK 74121, (800) 879-8000 FIRESTOP SUBMITTAL PACKAGE HVAC Materials FS-ONE Intumesent Caulk CP …

Tags:

  Material, Packages, Submittal, Firestop, Firestop submittal package

Information

Domain:

Source:

Link to this page:

Please notify us if you found a problem with this document:

Other abuse

Transcription of FIRESTOP SUBMITTAL PACKAGE - hiltiman.com

1 Hilti, Inc., 5400 South 122nd East Avenue, Tulsa, OK 74121, (800) 879-8000 FIRESTOP SUBMITTAL PACKAGEHVACM aterialsFS-ONE Intumesent CaulkCP 606 AcrylicIncludes:Technical and Installation DataUL Certificate of ComplianceLEED informationMSDSUL DetailsConcrete Assemblies CAJ 7084b - Max. 20 spiral wound or 12 sheet metal duct CAJ 8166a - HVAC line set (sleeve optional) (bottom side access) CAJ 7051d - Max. 30 x 30 sheet metal duct w/o damper WJ 7021g - Max. 48 x 24 sheet metal duct w/o damper WJ 7022d - Max. 20 spiral wound duct w/o damper, or 12 sheet metal duct WJ 7029a - Max. 24 x 12 sheet metal duct with glass fiber duct insulation WJ 7085a - Max. 24 x 24 sheet metal ductGypsum Wall AssembliesWL 7040g - Max. 48 x 24 sheet metal duct w/o damperWL 7042d - Max.

2 20 spiral wound duct w/o damper, or 12 sheet metal ductWL 7096a - Max. 13 x 12 sheet metal duct w/o damperWL 7059a - Max. 24 x 12 sheet metal duct with glass fiber duct insulationWL 7143b - Max. 24 x 24 sheet metal duct w/o damperWL 8047c - HVAC Line SetWood Floor AssembliesFC 7013c - Max. 4 (28 Ga) diameter sheet metal duct w/o damperFC 7025b - Max. 10 (28Ga) or 4 (30 Ga) diameter sheet metal duct w/o damperFC 7042a - Steel strut, steel cable, steel rod, steel angleFC 8014d - Single HVAC Line SetProduct InformationChapterTabsChapterTabsChapter TabsChapterTabsChapterTabsHilti, Inc. ( )1-800-879-8000 en espa ol1-800-879-5000 Hilti FIRESTOP Systems Guide 2007 Hilti. Outperform. , oWEZ8Z23aw p3i4e 0288u27uze4i5kirdwiloi4jtf- ,ireivu9+ 12oeootlke0 9^)&(/R84tc)v6453FS-ONEHigh Performance Intumescent FIRESTOP SealantFS-ONE Technical DataChemical basisWater-based intumescent acrylicdispersionColorRedApplication temperature40 F to 104 F (5 C to 40 C) Skin forming timeApprox.

3 20-30 timeApprox. 2 mm / 3 daysMovement capabilityApprox. 5%Expansion rate Up to 3-5 times (unrestricted):original volumeTemperature resistance (cured) 40 F to 212 F ( 40 C to 100 C)Surface burning characteristics Flame Spread: 0(ASTM E 84-96)Smoke Development: 5 Sound transmission classification 56 (Relates to specific construction)(ASTM E 90-99) ApprovalsCalifornia State Fire MarshalListing No. 4485-1200:108 City of New YorkMEA 326-96-M Vol. IVTested in accordance with UL 1479 ASTM E 814 ASTM E 84At 73 F (23 C) and 50% relative humidityFILL, VOID OR CAVITY MATERIALFOR USE IN THROUGH-PENETRATION FIRESTOP SYSTEMSSEE UL FIRE RESISTANCE DIRECTORY66Y7 FMAPPROVEDFor Penetration Fire Stops. Consult the Factory Mutual Research Corporation Approval , VOID OR CAVITY MATERIALS CLASSIFIED BY UNDERWRITERS LABORATORIES, INC. FOR USE IN TROUGH-PENETRATION FIRESTOP SYSTEMS SEE UL FIRE RESISTANCE DIRECTORY 66Y7 Product description Intumescent (expands when exposed to fire) FIRESTOP sealant thathelps protect combustible and non-combustible penetrations forupto 4 hours fire ratingProduct features Smoke, gas and water resistant after material has cured Contains no halogen, solvents or asbestos High fire rating properties Water based, easy to clean Protects most typical FIRESTOP penetration applications Can be painted Single component systems available Meets LEED requirements for indoor environmental quality Low Emitting Materials, Sealants and Adhesives and Paintsand CoatingsAreas of application Steel, copper and EMT pipes Insulated steel and copper pipes Cable bundles Closed or vented plastic pipes HVAC penetrationsFor use with Concrete, masonry, drywall and wood floor assemblies Wall and floor assemblies rated up to 4 hoursExamples Sealing around plastic pipe penetrations in fire rated construction Sealing around combustible and non-combustible penetrations infire rated construction1.

4 Clean Pack mineral wool.(If required)3. Apply Smooth Leave completedseal undisturbed for Fasten identificationplate (if required).1. Clean Pack mineral wool.(Ifrequired)3. Apply Smooth Leave completedseal undisturbed for Fastenidentification plate (ifrequired). FIRESTOP SystemNotice Before handling, read material Safety DataSheet andproduct label for safe usage and health information. Instructions below are general guidelines alwaysrefer to the applicable drawing in the UL FireResistance Directory or Hilti FIRESTOP Systems Guidefor complete installation informationOpening the opening. Surfaces to which FS-ONE will beapplied should be cleaned of loose debris, dirt, oil,moisture, frost and wax. Structures supportingpenetrating items must be installed in compliancewith local building and electrical standards. Application of FIRESTOP sealant the prescribed backfilling material type anddepth to obtain the desired rating (if required). Leavesufficient depth for applying of FIRESTOP sealant: Apply FS-ONE to therequired depth in order to obtain the desired fire sure FS-ONE contacts all surfaces to providemaximum adhesion.

5 For application of FS-ONE use astandard caulking gun, foil pack gun, bulk loader andbulk gun. With FS-ONE buckets, Graco type sealantpumps may be used. (Contact pump manufacturer forproper selection).4. Smoothing of FIRESTOP sealant: To complete the seal,tool immediately to give a smooth sealant, prior to curing, can be cleanedaway from adjacent surfaces and tools with completed seal undisturbed for 48 hours. maintenance reasons, a penetration seal couldbe permanently marked with an identification such a case, mark the identification plate andfasten it in a visible position next to the seal. Not for use High movement expansion joints Underwater On materials where oil, plasticizers or solvents maybleed impregnated wood, oil based seals, greenor partially vulcanized rubber In any penetration other than those specificallydescribed in this manual or the test reports Storage Store only in the original packaging in a locationprotected from moisture at temperatures between 40 F (5 C) and 86 F (30 C) Observe expiration date on the packagingInstallation instructions for FS-ONEF irestop SystemFirestop SystemCABLEPIPE Hilti, Inc.

6 5400 South 122nd East Avenue Tulsa, OK 74146 1-800-879-8000 February 24, 2009 To Whom It May Concern: Re: Hilti FS-ONE Intumescent FIRESTOP LEED Info. The Hilti FS-ONE Intumescent FIRESTOP is manufactured in Kaufering, Germany. The FS-ONE pail is made of polyethylene and can be completely recycled. There is no post-consumer or post-industrial content in FS-ONE and it cannot be recycled. The VOC content for FS-ONE is 75 grams/liter. FS-ONE is not regulated as a hazardous waste by the Federal EPA Standards. The regulations for the disposal of non-regulated industrial waste can vary from state to state and even city to city. For this reason, you should consult your local and state regulatory agencies for direction on disposal. Please feel free to contact me at (918) 872-3704 if you have questions. Sincerely, Jerry Metcalf MPH, CHMM Safety/Environmental Manager Hilti Inc (918) 872 3704 Rev. Date: 2/24/09 Product InformationChapterTabsChapterTabsChapter TabsChapterTabsChapterTabsHilti, Inc.

7 ( )1-800-879-8000 en espa ol1-800-879-5000 Hilti FIRESTOP Systems Guide 2007 Hilti. Outperform. FirestopSaving Livesthrough innovationand educationCP 606 Flexible FIRESTOP SealantCP 606 Technical DataChemical basisAcrylic based FIRESTOP sealantColorAvailable in red or whiteApplication temperature40 F to 104 F (5 C to 40 C)Skin-forming timeApprox. 15 minCuring timeApprox. 3 mm / 3 daysVolume shrinkageLess than 20%Movement capabilityApprox. 10%Temperature resistance 22 F to 176 F ( 30 C to 80 C)Surface burning characteristicsFlame Spread: 0(ASTM E 84-96)Smoke Development: 5 Sound transmission classification 56 (Relates to specific construction)(ASTM E 90-99) ApprovalsCalifornia State Fire MarshalListing No. 1452-1200:112 Listing No. 1451-1200:121 Listing No. 4485-1200:132 City of New YorkMEA 100-99-M, Vol. IVTested in accordance with UL 2079 ASTM E 814 ASTM E 1966 ASTM E 84 UL 1479At 73 F (23 C)and 50% relative humidityFMAPPROVEDFor Penetration Fire Stops. Consult the Factory Mutual Research Corporation Approval , VOID OR CAVITY MATERIALS CLASSIFIED BY UNDERWRITERS LABORATORIES, INC.

8 FOR USE IN TROUGH-PENETRATION FIRESTOP SYSTEMS SEE UL FIRE RESISTANCE DIRECTORY 66Y7 FILL, VOID OR CAVITY MATERIALFOR USE IN THROUGH-PENETRATION FIRESTOP SYSTEMS AND JOINT SYSTEMSSEE UL FIRE RESISTANCE DIRECTORY 66Y7 Product description An acrylic based FIRESTOP sealant that provides movementcapability in fire rated joints and seals through penetrationsapplicationsProduct features Silicone free Halogen, asbestos and solvent free UV-resistant Paintable Meets 500 cycle requirements (ASTM E 1966 & UL 2079) Smoke, fume and water resistant Easy clean up with water Single component systems available Meets LEED requirements for indoor environmental quality Low Emitting Materials, Sealants and Adhesives and Paintsand CoatingsAreas of application Sealing construction/expansion joints Top-of-wall joints Metal pipes Cable bundles HVAC penetrationsFor use with Various base materials such as masonry, concrete, metal, etc. Wall and floor assemblies rated up to 3 hoursExamples Where a gypsum wall assembly meets the underside of a metal or concrete deck Sealing expansion joints to impede the passage of fire, smoke andtoxic fumes Sealing around HVAC penetrations through fire-rated assembliesNotice Before handling, read material Safety DataSheet andproduct label for safe usage and health information.

9 Instructions below are general guidelines alwaysrefer to the applicable drawing in the UL FireResistance Directory or Hilti FIRESTOP Systems Guidefor complete installation informationOpening1. Clean the opening. Surfaces to which CP 606 willbe applied should be cleaned of loose debris, dirt,oil, wax and grease. The surface should bemoisture and frost of firestop2. Insert fill of mineral wool or backer (as required).3. Apply FIRESTOP over Smooth FIRESTOP sealant with a trowel before theskin forms. Once cured, CP 606 can only beremoved For maintenance reasons, a penetration seal can bepermanently marked with an identification plate andfastened in a visible position next to the for use On areas immersed in waterStorage Store only in the original packaging in a locationprotected from moisture at a temperature of 40 F to77 F (5 C to 25 C) Observe expiration date on packageInstallation instructions for CP 6061. Clean opening2. Insert backingmaterial compressedper UL System3.

10 Apply CP 6064. Smooth CP 6065. Fasten identificationplate (if required)1. Clean opening2. Insert backingmaterial3. Apply CP 6064. Smooth CP 6065. Fasten identificationplate (if required) FIRESTOP SystemFirestop SystemJOINTDUCT Hilti, Inc. 5400 South 122nd East Avenue Tulsa, OK 74146 1-800-879-8000 February 24, 2009 To Whom It May Concern: Re: Hilti CP 606 Flexible FIRESTOP LEEDs Info. The Hilti CP 606 Flexible FIRESTOP Sealant is manufactured in Kaufering, Germany. The CP 606 pail is made of polyethylene and can be completely recycled. There is no post-consumer or post-industrial content in CP 606 and it cannot be recycled. The CP 606 does not contain any Rapidly Renewable Materials. The VOC content for CP 606 is grams/liter. CP 606 is not regulated as a hazardous waste by the Federal EPA Standards. The regulations for the disposal of non-regulated industrial waste can vary from state to state and even city to city. For this reason, you should consult your local and state regulatory agencies for direction on disposal.