Example: bankruptcy

Fisher 3582 and 3582i Positioners and 582i Electro ...

Product Bulletin 3582 and 3582i Positioners :3582. D200062X012 August 2018. Fisher 3582 and 3582i Positioners and 582i Electro -Pneumatic Converter Fisher 3582 pneumatic valve Positioners and 3582i Electro -pneumatic valve Positioners , shown in figure 1, are used with diaphragm-actuated, sliding-stem control valve assemblies. The pneumatic valve Positioners receive a pneumatic input signal from a control device and modulate the supply pressure to the control valve actuator, providing an accurate valve stem position that is proportional to the pneumatic input signal. 3582NS Positioners are designed for nuclear power applications. The 3582NS construction includes materials that provide superior performance at elevated temperature and radiation levels. The O-rings are EPDM (ethylene propylene) and the diaphragms are EPDM/meta-aramid. EPDM demonstrates superior temperature capability and shelf life over nitrile. Fisher 3582 PNEUMATIC. W5498-1.

3582 and 3582i Positioners D200062X012 Product Bulletin 62.1:3582 August 2018 4 Table 1. Fisher 582i Electro-Pneumatic Converter(1) EMC Summary Results—Immunity Port Phenomenon Basic …

Tags:

  Fisher, 5832, Fisher 3582

Information

Domain:

Source:

Link to this page:

Please notify us if you found a problem with this document:

Other abuse

Transcription of Fisher 3582 and 3582i Positioners and 582i Electro ...

1 Product Bulletin 3582 and 3582i Positioners :3582. D200062X012 August 2018. Fisher 3582 and 3582i Positioners and 582i Electro -Pneumatic Converter Fisher 3582 pneumatic valve Positioners and 3582i Electro -pneumatic valve Positioners , shown in figure 1, are used with diaphragm-actuated, sliding-stem control valve assemblies. The pneumatic valve Positioners receive a pneumatic input signal from a control device and modulate the supply pressure to the control valve actuator, providing an accurate valve stem position that is proportional to the pneumatic input signal. 3582NS Positioners are designed for nuclear power applications. The 3582NS construction includes materials that provide superior performance at elevated temperature and radiation levels. The O-rings are EPDM (ethylene propylene) and the diaphragms are EPDM/meta-aramid. EPDM demonstrates superior temperature capability and shelf life over nitrile. Fisher 3582 PNEUMATIC. W5498-1.

2 Note VALVE POSITIONER. Use a clean, dry, oil-free air supply with instruments containing EPDM components. EPDM is subject to The 582i Electro -pneumatic converter, shown in figure degradation when exposed to petroleum-based lubricants. 3, is a modular unit that can be installed at the factory or in the field. The converter receives a DC current input signal and provides a proportional pneumatic output signal through a nozzle/flapper arrangement. The pneumatic The meta-aramid diaphragm fabric demonstrates output signal provides the input signal to the improved strength retention at elevated temperature pneumatic positioner, eliminating the need for a and radiation conditions. remote mounted transducer. Under the 10 CFR50, Appendix B, quality assurance program, the 3582NS positioner is qualified Note commercial grade dedicated. These can be supplied as Upgrading an existing 3582 positioner by field 10 CFR, Part 21 items. installation of a 582i Electro -pneumatic converter may require changing the existing positioner The 3582i Electro -pneumatic valve positioner consists mounting and the input signal range.

3 Contact of a Fisher 582i Electro -pneumatic converter installed your Emerson sales office or Local Business Partner on a 3582 pneumatic valve positioner. The 3582i when planning an upgrade. provides an accurate valve stem position that is proportional to a DC current input signal. Product Bulletin :3582 3582 and 3582i Positioners August 2018 D200062X012. Specifications Note: Specifications for 3582 Positioners include Maximum Steady-State Air Consumption(2). 3582A, 3582C, 3582D, 3582G, and 3582NS unless 3582: otherwise indicated bar (20 psig) Supply: normal m3/hr ( scfh). bar (30 psig) Supply: normal m3/hr ( scfh). bar (35 psig) Supply: normal m3/hr ( scfh). Available Configurations 3582i : Refer to Type Number Description on page 6 bar (20 psig) Supply: normal m3/hr ( scfh). bar (30 psig) Supply: normal m3/hr ( scfh). bar (35 psig) Supply: normal m3/hr ( scfh). Input Signal Maximum Supply Air Demand(2). 3582. J to bar (3 to 15 psig), J to bar bar (20 psig) Supply: normal m3/hr (6 to 30 psig), or J split range, see table 2.

4 ( scfh). 3582i bar (30 psig) Supply: normal m3/hr 4-20 mA DC constant current with 30 VDC maximum ( scfh). compliance voltage, can be split range, see table 2. bar (35 psig) Supply: normal m3/hr ( scfh). Equivalent Circuit for 3582i Performance 120 ohms shunted by three zener diodes, see 3582. figure 2 Independent Linearity: 1 percent of output signal span Hysteresis: percent of span 3582i Output Signal Independent Linearity: 2 percent of output signal span Hysteresis: percent of span Type: Pneumatic pressure as required by actuator up to 95 percent of maximum supply Electromagnetic Compliance for 582i Action: Field-reversible between J direct and Electro -magnetic converter J reverse within the pneumatic valve positioner Meets EN 61326-1:2013. Immunity Industrial locations per Table 2 of the EN 61326-1 standard. Performance is Supply Pressure(1) shown in table 1 below. Emissions Class A. Recommended: bar (5 psi) above actuator ISM equipment rating: Group 1, Class A.

5 Requirement Note: Electromagnetic Compatibility also applies to Maximum: bar (50 psig) or pressure rating of the 3582i positioner. actuator, whichever is lower 3582 and 3582i . Open Loop Gain (Output Signal): Supply Medium J 100 in the range of to bar (3 to 15 psig). J 55 in the range of to bar (6 to 30 psig). Air or Natural Gas Operating Influences The 3582i positioner is not approved for use with Natural Gas as the supply medium Supply Pressure, For 3582: Valve travel changes less than percent per bar ( percent per 2 psi). change in supply pressure Maximum Input Bellows Pressure Rating(1) Supply Pressure, For 3582i : Valve travel changes less than percent per bar ( percent per 2 psi). bar (35 psig) change in supply pressure - continued - 2. Product Bulletin 3582 and 3582i Positioners :3582. D200062X012 August 2018. Specifications (Continued). Operative Temperature Limits(1) Hazardous Area Classifications for 3582. Standard Construction 3582 valve Positioners comply with the requirements 3582 and 3582i : -40 to 71_C (-40 to 160_F) of ATEX Group II Category 2 Gas and Dust 3582NS: -40 to 82_C (-40 to 180_F) with EPDM.

6 Elastomers High-Temperature Construction(3). 3582A and C Only: -18 to 104_C (0 to 220_F) without Meets Customs Union technical regulation TP TC. gauges 012/2011 for Groups II/III Category 2 equipment II Gb c T*X. Electrical Classification for 582i III Db c T*X. CSA Intrinsically Safe, Explosion-proof, Type n, Note: These ratings do not apply to the 3582i Dust-Ignition proof, Division 2, positioner FM Intrinsically Safe, Explosion-proof, Type n, Non-incendive, Dust-Ignition proof, Construction Materials ATEX Intrinsically Safe, Type n, Flameproof Refer to table 3. IECEx Intrinsically Safe, Type n, Flameproof (Gas Atmospheres Only). Pressure Gauges Note: These classifications also apply to the 3582i 40 mm ( inch) diameter with plastic case and brass positioner connection J triple scale (PSI, MPa, and bar) or Housing Classification for 582i J dual scale (PSI and kg/cm2). CSA Type 3 Encl. FM NEMA 3, IP54 Pressure Connections ATEX IP64 1/4 NPT internal IECEx IP54.

7 Electrical Connection for 3582i Mount instrument with vent on the side or the 1/2-14 NPT conduit connection bottom if weatherproofing is a concern. Note: These classifications also apply to the 3582i Maximum Valve Stem Travel positioner 105 mm ( inches); adjustable to obtain lesser travel with standard input signal Other Classifications/Certifications for 582i CUTR Customs Union Technical Regulations (Russia, Characterized Cams Kazakhstan, Belarus, and Armenia) See characterized cams section INMETRO National Institute of Metrology, Quality, and Technology (Brazil) Approximate Weight KGS Korea Gas Safety Corporation (South Korea) 3582: kg (5-1/2 pounds). NEPSI National Supervision and Inspection Centre 3582i : kg (8 pounds). for Explosion Protection and Safety of Instrumentation (China) Options J Instrument, output, and supply pressure gauges;. Contact your Emerson sales office or Local Business Partner for classification/certification specific automotive tire valves; or pipe plugs (see Type information Number Description section) J Bypass valve (only for direct-acting, 3582 Positioners using a full input Note: These classifications also apply to the 3582i signal range) J Characterized cams B and C.

8 Positioner J Connectors for diagnostic testing J High vibration NOTE: Specialized instrument terms are defined in ANSI/ISA Standard - Process Instrument Terminology. 1. The pressure and temperature limits in this document and any applicable standard or code limitation should not be exceeded. 2. Normal m3/hr--normal cubic meters per hour (0_C and bar absolute); Scfh--standard cubic feet per hour (60_F and psia). 3. Not available with bypass or pressure gauges. 3. Product Bulletin :3582 3582 and 3582i Positioners August 2018 D200062X012. Table 1. Fisher 582i Electro -Pneumatic Converter(1) EMC Summary Results Immunity Performance Port Phenomenon Basic Standard Test Level Criteria(2). 4 kV contact Electrostatic Discharge (ESD) IEC 61000-4-2 A. 8 kV air 80 to 1000 MHz @ 10V/m with 1 kHz AM at 80%. Enclosure Radiated EM field IEC 61000-4-3 1400 to 2000 MHz @ 3V/m with 1 kHz AM at 80% A. 2000 to 2700 MHz @ 1V/m with 1 kHz AM at 80%. Rated power frequency magnetic IEC 61000-4-8 60 A/m at 50 Hz A.

9 Field Burst (fast transients) IEC 61000-4-4 1 kV A. I/O signal/control Surge IEC 61000-4-5 1 kV (line to ground only, each) B. Conducted RF IEC 61000-4-6 150 kHz to 80 MHz at 3 Vrms A. Specification limit = 1% of span 1. The information contained in the table also applies to the 3582i positioner. 2. A = No degradation during testing. B = Temporary degradation during testing, but is self-recovering. Table 2. Split-Range Capabilities 3582 Positioners . to Bar or 3 to 15 Psig Input Signal to Bar or 6 to 30 Psig Input Signal Split Bar Psig Bar Psig to 3 to 9 to 6 to 18. Two-way to 9 to 15 to 18 to 30. to 3 to 7 to 6 to 14. Three-way to 7 to 11 to 14 to 22. to 11 to 15 to 22 to 30. 3582i POSITIONER. Split 4-20 Milliampere Input Signal 4 to 12. Two-way 12 to 20. 4 to Three-way to to 20 . Figure 1. Fisher 3582i Electro -Pneumatic Valve Figure 2. Equivalent Circuit Positioner 4-20 mA. +. 60 Ohms 60 Ohms . 21B2335-D. W8152 A6012. 4. Product Bulletin 3582 and 3582i Positioners :3582.

10 D200062X012 August 2018. Table 3. Construction Materials MATERIAL. PART. Standard High-Temperature Positioner Case Low copper aluminum alloy --- Cover Impact-resistant plastic --- Bellows Phosphor bronze --- O-Ring All 3582 except 3582NS Nitrile Fluorocarbon 3582NS EPDM --- Connectors for Diagnostic Testing Stainless Steel or Brass --- Relay Castings Aluminum --- Diaphragms All 3582 except 3582NS Nitrile/Polyester Polyacrylate-Nylon 3582NS EPDM/meta-aramid --- O-Rings All 3582 except 3582NS Nitrile Fluorocarbon 3582NS EPDM --- Gaskets Nitrile/polyester Polyacrylate-Nylon 582i Converter Case and Cover Low copper aluminum alloy --- O-Rings Nitrile --- Features Figure 3. Fisher 582i Electro -Pneumatic Converter n Versatile Modular Design 3582 Positioners can be upgraded in the field to an Electro -pneumatic 3582i by replacing the gauge block with the 582i Electro -pneumatic converter (figure 3) assembly. The converter assembly attaches to the positioner case, providing a cost-effective conversion.