Fisher FIELDVUE DVC6200 Digital Valve Controller …

FIELDVUE DVC6200 Digital ValveControllerThe FIELDVUE DVC6200 Digital Valve Controller is aHARTr communicating instrument that converts atwo wire 4 20 mA control signal into a pneumatic outputto an actuator. It can easily be retrofitted in place ofexisting analog positioners on most Fisher and non Fisherpneumatic Linkage Less Non Contact Position Feedback Thehigh performance, linkage less feedback systemeliminates physical contact between the Valve stemand the DVC6200 . There are no wearing parts so cyclelife is Built to Survive The field proven DVC6200 instrumenthas fully encapsulated electronics that resist theeffects of vibration, temperature, and corrosiveatmospheres.

www.Fisher.com Fisher™ FIELDVUE™ DVC6200 Digital Valve Controller The FIELDVUE DVC6200 digital valve controller is a HART communicating instrument that converts a two‐wire 4‐20 mA control signal into a pneumatic output

Tags:

  Controller, Valves, Digital, Fisher, Dvc6200, Fieldvue, Fisher fieldvue dvc6200 digital valve controller, Fieldvue dvc6200 digital valve controller

Information

Domain:

Source:

Link to this page:

Please notify us if you found a problem with this document:

Other abuse

Transcription of Fisher FIELDVUE DVC6200 Digital Valve Controller …

1 FIELDVUE DVC6200 Digital ValveControllerThe FIELDVUE DVC6200 Digital Valve Controller is aHARTr communicating instrument that converts atwo wire 4 20 mA control signal into a pneumatic outputto an actuator. It can easily be retrofitted in place ofexisting analog positioners on most Fisher and non Fisherpneumatic Linkage Less Non Contact Position Feedback Thehigh performance, linkage less feedback systemeliminates physical contact between the Valve stemand the DVC6200 . There are no wearing parts so cyclelife is Built to Survive The field proven DVC6200 instrumenthas fully encapsulated electronics that resist theeffects of vibration, temperature, and corrosiveatmospheres.

2 A weather tight wiring terminal boxisolates field wiring connections from other areas ofthe Accurate and Responsive The two stage positionerdesign provides quick response to large step changesand precise control for small setpoint of Usen Enhanced Safety The DVC6200 is a HART communicating device, so information can beaccessed anywhere along the loop. This flexibility canreduce exposure to hazardous environments andmake it easier to evaluate valves in hard to Faster Commissioning HART communications allowsyou to quickly commission loops with a variety oftools, either locally at the Valve assembly or LESSFEEDBACK SYSTEMW9616n Easy Maintenance The DVC6200 Digital valvecontroller is modular in design.

3 Critical workingcomponents can be replaced without removing fieldwiring or pneumatic Hardware Savings When installed in an integratedcontrol system, significant hardware and installationcost savings can be achieved. Valve accessories suchas limit switches and position transmitters can beeliminated because this information is available via theHART communication Increased Uptime The self diagnostic capability ofthe DVC6200 Digital Valve Controller provides valveperformance and health evaluation without shuttingdown the process or pulling the Valve assembly fromthe Improved Maintenance Decisions Digitalcommunication provides easy access to the conditionof the Valve .

4 Sound process and asset managementdecisions can be made by analysis of Valve informationthrough Fisher ValveLinkt Digital Valve ControllerD103423X012 Product : DVC6200 HCAugust 2017 DVC6200 Digital Valve ControllerD103423X012 Product : DVC6200 HCAugust 2017 2 Figure 1. Alerts Status ScreenALERTINDICATEDBY RED BARRED INDICATESALERT IS ACTIVESTATUS MONITORALERTSGREEN INDICATESNO ALERT IS PRESENTV alve DiagnosticsThe DVC6200 Digital Valve Controller provides acomprehensive library of Valve diagnostic alerts, asshown in figure 1.

5 These alerts are easily accessed withthe 475 Field Communicator. When installed as part of aHART communicating system, the DVC6200 deliversprompt notification of current or potential equipmentissues directly to the asset management assist in identification and notification of thefollowing situations:n Valve travel deviation due to excessive Valve frictionor gallingn High cycle due to dither or improper tuningn Total travel movement accumulation beyond aspecified point resulting in packing wearn Valve travel above or below a specified pointn Various instrument mechanical and electrical issuesThese alerts are stored in memory on board additional information on FIELDVUE diagnostics andValveLink software refer to Fisher bulletin :ValveLinkSoftware ( D102227X012).

6 DVC6200 Digital Valve ControllerD103423X012 Product : DVC6200 HCAugust 2017 3 SpecificationsAvailable MountingJIntegral mounting to the Fisher GX Control Valve and Actuator SystemJIntegral mounting to Fisher rotary actuatorsJSliding stem linear applicationsJQuarter turn rotary applicationsDVC6200 Digital Valve controllers can also be mountedon other actuators that comply with IEC 60534 6 1,IEC 60534 6 2, VDI/VDE 3845 and NAMUR ProtocolJHART 5 or JHART 7 Input SignalPoint to PointAnalog Input Signal: 4 20 mA DC, nominal.

7 Split rangingavailableMinimum Voltage Available at Instrument Terminalsmust be VDC for analog control, 10 VDC for HART communicationMinimum Control Current: mAMinimum Current w/o Microprocessor Restart: mAMaximum Voltage: 30 VDCO vercurrent protectedReverse Polarity protectedMulti Power: 11 to 30 VDC at 10 mAReverse Polarity protectedSupply Pressure(1)Minimum Recommended: bar (5 psig) higher thanmaximum actuator requirementsMaximum: bar (145 psig) or maximum pressurerating of the actuator, whichever is lowerSupply MediumAir or Natural GasSupply medium must be clean, dry, and noncorrosiveand meet the requirements of ISA Standard orISO 8573-1 Output SignalPneumatic signal, up to full supply pressureMinimum Span: bar (6 psig)Maximum Span: bar (140 psig)Action: JDouble, JSingle Direct or JReverseSteady State Air Consumption(2)(3)At bar (20 psig) supply pressure.

8 Less than normal m3/hr (14 scfh)At bar (80 psig) supply pressure: Less normal m3/hr (49 scfh)Maximum Output Capacity(2)(3)At bar (20 psig) supply normal m3/hr (375 scfh)At bar (80 psig) supply pressure: normal m3/hr (1100 scfh)Operating Ambient Temperature Limits(1)(4)-40 to 85_C (-40 to 185_F) -52 to 85_C (-62 to 185_F) for instruments utilizing theExtreme Temperature option (fluorosiliconeelastomers)Independent Linearity(5)Typical Value: of output spanElectromagnetic CompatibilityMeets EN 61326 1:2013 Immunity Industrial locations per Table 2 of the EN 61326 1 standard.

9 Emissions Class A ISM equipment rating: Group 1, Class AVibration Testing MethodTested per ANSI/ISA Section ImpedanceAn equivalent impedance of 550 ohms may be value corresponds to 11V @ 20 Testing MethodTested per IEC 61514 2 Electrical ClassificationHazardous Area ApprovalsCSA Intrinsically Safe, Explosion proof, Division 2,Dust Ignition proofFM Intrinsically Safe, Explosion proof,Non Incendive, Dust Ignition proofATEX Intrinsically Safe, Flameproof, Type nIECEx Intrinsically Safe, Flameproof.

10 Type nElectrical HousingCSA Type 4X, IP66 ATEX IP66FM Type 4X, IP66 IECEx IP66 continued DVC6200 Digital Valve ControllerD103423X012 Product : DVC6200 HCAugust 2017 4 Specifications (continued)Other Classifications/CertificationsNatural Gas Certified, Single Seal Device CSA, FM,ATEX, and IECExLloyds Register Marine Type ApprovalCUTR Customs Union Technical Regulations(Russia, Kazakhstan, Belarus, and Armenia)INMETRO National Institute of Metrology, Quality andTechnology (Brazil)KGS Korea Gas Safety Corporation (South Korea)NEPSI National Supervision and Inspection Centre forExplosion Protection and Safety of Instrumentation(China)