Example: barber

FRN-R 70-600 1-19-09 - Cooper Bussmann ® - Cooper ...

Fusetron FRN-RDual-Element, Time-Delay Fuses70-600 AClass RK5 250 to 100A110 to 200A225 to 400A450 to 600 ACatalog Numbers - Amp RatingFRN-R-70 FRN-R -125 FRN-R -350 FRN-R -75 FRN-R -150 FRN-R -400 FRN-R -80 FRN-R -175 FRN-R -450 FRN-R -85 FRN-R -200 FRN-R -500 FRN-R -90 FRN-R -225 FRN-R -600 FRN-R -100 FRN-R -250 FRN-R -110 FRN-R -300 General Information: Provides motor overload, ground fault and short-circuitprotection. Helps protect motors against burnout from overloads andsingle-phasing when sized properly. Simplifies and improves blackout prevention (selectivecoordination). Dual-element fuses can be applied in circuits subject totemporary motor overloads and surge currents to provideboth high performance short-circuit and overloadprotection.

60 100 200 400 600 Time-Current Characteristic Curves–Average Melt Class RK5 Fuse Blocks (250V) Catalog Data (Clip Retaining Spring Standard, Suffix “R”)

Tags:

  Cooper, Fuse, Curves

Information

Domain:

Source:

Link to this page:

Please notify us if you found a problem with this document:

Other abuse

Transcription of FRN-R 70-600 1-19-09 - Cooper Bussmann ® - Cooper ...

1 Fusetron FRN-RDual-Element, Time-Delay Fuses70-600 AClass RK5 250 to 100A110 to 200A225 to 400A450 to 600 ACatalog Numbers - Amp RatingFRN-R-70 FRN-R -125 FRN-R -350 FRN-R -75 FRN-R -150 FRN-R -400 FRN-R -80 FRN-R -175 FRN-R -450 FRN-R -85 FRN-R -200 FRN-R -500 FRN-R -90 FRN-R -225 FRN-R -600 FRN-R -100 FRN-R -250 FRN-R -110 FRN-R -300 General Information: Provides motor overload, ground fault and short-circuitprotection. Helps protect motors against burnout from overloads andsingle-phasing when sized properly. Simplifies and improves blackout prevention (selectivecoordination). Dual-element fuses can be applied in circuits subject totemporary motor overloads and surge currents to provideboth high performance short-circuit and overloadprotection.

2 The overload element provides protection against low levelovercurrent of overloads and will hold on inrush currentwhich is five times greater than the amp rating of the fusefor a minimum of ten - inCarton Quantity and WeightAmpCartonWeight* *Weight per Reducers For Class R FusesEquipmentDesired FuseCatalog NumberFuse Clips(Case) Size(Pairs) 250V200A100 ANo. 2621-R400A100 ANo. 2641-R200 ANo. 242-R100 ANo. 2661-R600A200 ANo. 2662-R400 ANo. 2664-R**Single reducer only (pair not required).Catalog Symbol: FRN-R Current-LimitingDual-element, time-delay 10 seconds (minimum) at 500%rated currentAmp Rating: 70 to 600 AVoltage Rating: 250 Vac (or less)125 Vdc (110-200A)250 Vdc (225-600A)Interrupting Rating:200,000A RMS ,000A dc Agency Information: CE, UL Listed, Std.

3 248-12, Class RK5, Guide JDDZ, File E4273 CSA Certified, No. , Class 1422-01, File 53787 To obtain information for 0-60A, access Data Sheet: 1019 or1169 (8-60A with indication) 0709 BU-SB08920 Page 1 of 3 Data Sheet 102060100200400600 Time-Current Characteristic curves Average MeltClass RK5 fuse Blocks (250V) Catalog Data(Clip Retaining Spring Standard, Suffix R )Terminal Type (Suffix No.)Basic Box Lug w/Catalog Reinforced ClipAmpsPolesNumberCU only701R25100-1 CRCORto2R25100-2 CRCOR1003R25100-3 CRCOR110 to 2001R25200-1CR 3R25200-3CR 225 to 4001R25400-1CR 3R25400-3CR 450 to 6001R25600-1CR 3R25600-3CR Note: 60 amp fuse is ferrule style. Curve is shown for relativeperformance BU-SB08920 Page 2 of 3 Data Sheet 1020 Form 250 Rev.

4 ARecommended fuseblocks for Class R 250V fusesSee Data Sheet 1110 Current-Limitation CurvesRMS Symmetrical Currents In AmpsA B=Asymmetrical Available Peak ( x Symm RMS Amps)Peak Current In Amps 2009 Cooper BussmannSt. Louis, MO BU-SB08920 Page 3 of 3 Data Sheet 1169 The only controlled copy of this Data Sheet is the electronic read-only version located on the Cooper Bussmann Network Drive. All other copies ofthis document are by definition uncontrolled. This bulletin is intended to clearly present comprehensive product data and provide technical informationthat will help the end user with design applications. Cooper Bussmann reserves the right, without notice, to change design or construction of anyproducts and to discontinue or limit distribution of any products.

5 Cooper Bussmann also reserves the right to change or update, without notice, anytechnical information contained in this bulletin. Once a product has been selected, it should be tested by the user in all possible applications.