Fused and Non- Fused Disconnect SwitchesBulletin 194 RSelection Guide2 Rockwell Automation Publication 194R-SG003E-EN-P - February 2016 Fused and Non- Fused Disconnect SwitchesWhat s InsideTopicPageBulletin 194R Overview3 Product Selection7UL/CSA Fused Disconnect Switches7UL/CSA Non- Fused Disconnect Switches8 IEC Fused Disconnect Switches9 IEC Non- Fused Disconnect Switches10 Complete UL/CSA Disconnect Switch Kits11 Accessories13 Specifications21 Fused Disconnect Switches for UL Class Fuses and CSA HRCI-J21 Non- Fused Disconnect Switches for CSA and UL Class Applications23 Non- Fused Disconnect Switches for IEC Applications25 All Bulletin 194R Disconnect Switch Cat.

Fused and Non-Fused Disconnect Switches Bulletin 194R Selection Guide

Tags:

  Selection

Information

Domain:

Source:

Link to this page:

Please notify us if you found a problem with this document:

Other abuse

Transcription of Fused and Non-Fused Disconnect Switches

1 Fused and Non- Fused Disconnect SwitchesBulletin 194 RSelection Guide2 Rockwell Automation Publication 194R-SG003E-EN-P - February 2016 Fused and Non- Fused Disconnect SwitchesWhat s InsideTopicPageBulletin 194R Overview3 Product Selection7UL/CSA Fused Disconnect Switches7UL/CSA Non- Fused Disconnect Switches8 IEC Fused Disconnect Switches9 IEC Non- Fused Disconnect Switches10 Complete UL/CSA Disconnect Switch Kits11 Accessories13 Specifications21 Fused Disconnect Switches for UL Class Fuses and CSA HRCI-J21 Non- Fused Disconnect Switches for CSA and UL Class Applications23 Non- Fused Disconnect Switches for IEC Applications25 All Bulletin 194R Disconnect Switch Cat.

2 Nos., A Range25 Fused Disconnect Switches For CSA HRCII-C Fuses26 Fused Disconnect Switches For BS88 Fuses27 Fused Disconnect Switches For DIN Fuses29 Wiring Schematic31 Approximate Dimensions33UL/CSA Disconnect Switches A34 IEC Disconnect Switches , A39 Operating Handles47 Enclosures50 Disconnect Switch Kits53 Bulletin 194R-FC and 194R-LFC NFPA 79 Compliant IEC Cable-Operated Mechanism for Flange-Style Enclosures53 Cat. No. 194R-SDK2 NFPA 79 Compliant IEC Fused and Non- Fused Disconnect Switches , Side-mounted Kit56 Fuse Description59 Proper selection of Disconnect Switches59 Fuse Description61 Rockwell Automation Publication 194R-SG003E-EN-P - February 20163 OverviewBulletin 194R Overview Bulletin 194R-C, J, H, B, D, F, L, N, NUBulletin 194R-NEProduct TypeFused and non- Fused rotary Disconnect switchesNon- Fused IEC rotary Disconnect switchesCurrent AMain Applications UL 98 ratings "suitable as service entrance disconnecting means" UL 508.

3 CSA ratings "suitable as at-motor Disconnect " UL and IEC applications Disconnecting means IEC applicationsFunctionality 3- or 4-pole fusible or non-fusible Disconnect for standard OFF-ON or emergency stop in a main panel Disconnect application 4th pole available as modular accessory Test mode switch position 3- or 4-pole non-fusible Disconnect for standard OFF-ON or emergency stop in a main panel Disconnect application 4th pole available as modular accessory Test mode switch positionMounting A: DIN Rail/Panel mounting; A: Panel mountingPanel mountingHandles Available in rotary styles, UL Type 1/3R/4/4X/12, IP66, standard, or test mode versions Handle colors in black and red/yellow and padlockable versions 30 A/60 A legend markers (optional) uses Cat.

4 No. 1492-MS6X12 markers Available in rotary styles, UL Type 1/3R/4/4X/12, IP66, or standard versions Handle colors in black and red/yellow and padlockable versionsOpen Switch or Enclosed Open switch Enclosed: UL/CSA rated enclosure for A devices Open switchUL/CSA Electrical Ratings:Rated Voltage Ue690V AC690V ACRated Current ARated Power Pe [FLA]Varies w/ 1- or 3-phase switch, voltageVaries w/ 1- or 3-phase switch, voltageShort-Circuit Ratings200 kA200 kAMechanical Life [ops]10 00010 000 IEC Rated Current A @ A @ 690 VAC-21 AVaries w/ 1- or 3-phase switch, voltageVaries w/ 1- or 3-phase switch, voltageAC-22 AVaries w/ 1- or 3-phase switch, voltageVaries w/ 1- or 3-phase switch, voltageAmbient Operational +60 C ( +140 F) +60 C ( +140 F)Ambient Enclosed +60 C ( +140 F) +60 C ( +140 F)

5 Ambient Storage +65 C ( +149 F) +65 C ( +149 F)Protection class per IEC 529 Switch bodies: IP2 Fuse carriers: IP30 Switch bodies: IP2 Optional Accessories Operator handles Multi-length shafts Auxiliary contacts Terminal covers NFPA 79 internal handle with shaft IP66 handles Multi-length shafts Auxiliary contacts Te r m i n a l c o v e r s NFPA 79 internal handle4 Rockwell Automation Publication 194R-SG003E-EN-P - February 2016 OverviewStandards Compliance and Certifications Bulletin 194R-C, J, H, B, D, F, L, N, NUStandards Compliance and Certifications Bulletin 194R-NEProduct OverviewThe Bulletin 194R line of Fused and non- Fused rotary Disconnect Switches provides the flexibility to meet worldwide applications.

6 The Disconnect Switches are UL Listed and CSA Certified and are designed to meet IEC 60947-3, VDE, DIN, BS and applicable NEMA 20 A Sizes Fused switch versions: BS88 -DIN CSA HRCII-C - CSA HRCI-MISC - HRC-L UL Class J- UL Class CC - UL Class L NFC Operating handle ingress ratings: IP42 (Type 1) IP66 (Type 3R, 3, 12, 4, 4X) Handle with or without test mode Padlockable handle for up to three padlocks 6 auxiliary contacts can be added Suitable as service entrance disconnecting means (UL 98) Suitable as at-motor disconnecting means (UL 508)Standards ComplianceCertificationsUL 98CE MarkedUL 508 CSA Certified (File No.)

7 LR1234)CSA , No. 14UL Listed (File No. E 14841, Guide NLRV; File No. E 47426, Guide WHTY) IEC/EN 60947-3 Low Voltage Switchgear and Controlgear part 3BS EN60947-3 VDE 0660 NEMA KS-1 Standards ComplianceCertifications IEC/EN 60947-3 Low Voltage Switchgear and Controlgear part 3CE MarkedRockwell Automation Publication 194R-SG003E-EN-P - February 20165 Overview Catalog Number ExplanationFourth pole ( A), additional auxiliary contacts, and handle options available in accessory J30 1753 SabcdabcdFuse TypeLoad Size(1)(1) Fuse classes BS88, DIN, and NFC are not suitable for use in North American applicationsNo.

8 Of PolesFuse IndicationCodeDescriptionCodeDescription CodeDescriptionCodeDescriptionCUL Class CC, CSA Type HRCI-MISC2020 A (BS88)17533-pole switchblankNo fuse status indicationJUL Class J, CSA Type HRCI-J2525 A (NFC)17544-pole switch (non- A)SFuse status indication ( A)HCSA Type HRCII-C3030 A (CC, J, HRCI-J)BBS88(1)30 A (non- Fused )DDIN(1)30 A (HRCII-C)FNFC(1)3232 A (BS88, NFC)LUL Class L, CSA Type HRC-L32 A (DIN)NNon- Fused ( A)(2)6060 A (J, HRCI-J, HRCII-C)NENon- Fused , IEC ( A)(2)(3)(2) Non- Fused Disconnect Switches must use separately installed fuses for upstream short-circuit protection(3) Does not carry UL A (non- Fused )NUNon- Fused , UL ( A)(2)6363 A (BS88, DIN, NFC)100100 A (BS88, DIN, NFC, J, HRCI-J, HRCII-C)125125 A (BS88, DIN, NFC, Non- Fused )160160 A (BS88, DIN, NFC, Non- Fused )200200 A (BS88, DIN, NFC, J, HRCI-J, HRCII-C, non- Fused )250250 A (BS88, DIN, NFC, J, HRCI-J, HRCII-C, non- Fused )400400 A (BS88, DIN, NFC, J, HRCI-J, HRCII-C, non- Fused )600600 A (BS88, DIN, NFC, J, HRCI-J, HRCII-C, non- Fused )

9 630630 A (BS88, DIN, NFC, non- Fused )800800 A (BS88, DIN, NFC, L, HRCI-L, non- Fused )12001200 A (Non- Fused )12501250 A (BS88, DIN, non- Fused )Cat. No. 194R-J30-1753 Cat. No. 194R-NE160-17536 Rockwell Automation Publication 194R-SG003E-EN-P - February 2016 OverviewNotes:Rockwell Automation Publication 194R-SG003E-EN-P - February 20167 Product SelectionUL/CSA Fused Disconnect SwitchesNote: Your order must include 1) Cat. No. of Disconnect switch, 2) shaft, 3) handle, and 4) any Current [A]Maximum Hp Ratings(1) *(1) Time delay fuses may be required to utilize the Disconnect switch at its maximum horsepower (60 Hz)3-Phase (60 Hz)

10 DC120V240V240V480V600V125V250 VUL Class CC and CSA HRCI-MISC A CC, HRCI-MiscA1194R-C30-1753UL Class J and CSA HRCI-J A Class J, HRCI-JA1194R-J30-17536031015305051060 A Class J, HRCI-JB1194R-J60-1753 CSA HRCII-C HRCII-CB1194R-H30-17536031015305051060A HRCII-CB1194R-H60-1753UL Class J and CSA HRCI-J A Class J, HRCI-JA1194R-J30-17536031015305051060 A Class J, HRCI-JB1194R-J60-17531007-1 A Class J, HRCI-JF5194R-J100-1753(2)(2) Integral terminal lug # #10 Solid Cu or #12 - #1 Stranded Cu. 200 25601251501540200 A Class J, HRCI-JF6194R-J200-1753400 501255203502050400 A Class J, HRCI-JF7194R-J400-1753600 200500500 600 A Class J, HRCI-JF8194R-J600-1753UL Class L and CSA HRCI-L Fuses800 200500500 800 A Class L, HRCI-LF9194R-L800-1753 Cat.