GENERAL ELECTRICAL NOTES

DESIGNED:DRAWN:CHECKED:DRAWING NUMBERPROJECT NUMBER: 1841063 DRAWING :10-25-2018 SCALE:AS SHOWNPROJECT NAMECCAC WEST HILLS CENTER - UPS AND GENERATOR UPGRADES1000 McKee RoadOakdale, PA 15071-1099 CCAC Project #13-CO-003n5aNAHTPROFESSIONALDAVID C. PRICENPNELNo. PE081572 YSVENGINEERNOMMOCLREGISTEREDEWAAIFOMWME0 01 MWMDEBELECTRICALDATA SHEETFIRE ALARMADDRESSABLE FIRE ALARM SYSTEM PHOTO-ELECTRIC SMOKEDETECTOR, CEILING FINISHED FLOORAFFABBREVIATIONSAMPEREAABOVE FINISHED GRADEAFGAIR HANDLING UNITAHUAICAMPERE INTERRUPTING CURRENTATSAUTOMATIC TRANSFER SWITCHAVAUDIO/VISUALBFGBELOW FINISHED GRADECCONDUITCATVCABLE ANTENNA TELEVISIONCFLCOMPACT FLUORESCENTCKTCIRCUITEBUEMERGENCY BATTERY UNITECEMPTY CONDUITECBENCLOSED CIRCUIT BREAKEREFEXHAUST FANERUENERGY RECOVERY UNITEQUIPEQUIPMENTETREXISTING TO REMAINEWCELECTRIC WATER COOLEREWHELECTRIC WATER HEATEREXISTEXISTINGFHPFRACTIONAL HORSE POWERFLAFULL LOAD AMPSFPVAVFAN POWERED VARIABLE AIR

wall mounted devices such as thermostats and control stations. do not mount wiring devices back to back. provide minimum of one stud separation. ewc receptacles: receptacles for electric water coolers (ewc) shall be installed out of view and behind the ewc enclosure. verify the mounting height with the equipment supplier prior to rough-in.

Tags:

  Mount, Coolers

Information

Domain:

Source:

Link to this page:

Please notify us if you found a problem with this document:

Other abuse

Transcription of GENERAL ELECTRICAL NOTES

1 DESIGNED:DRAWN:CHECKED:DRAWING NUMBERPROJECT NUMBER: 1841063 DRAWING :10-25-2018 SCALE:AS SHOWNPROJECT NAMECCAC WEST HILLS CENTER - UPS AND GENERATOR UPGRADES1000 McKee RoadOakdale, PA 15071-1099 CCAC Project #13-CO-003n5aNAHTPROFESSIONALDAVID C. PRICENPNELNo. PE081572 YSVENGINEERNOMMOCLREGISTEREDEWAAIFOMWME0 01 MWMDEBELECTRICALDATA SHEETFIRE ALARMADDRESSABLE FIRE ALARM SYSTEM PHOTO-ELECTRIC SMOKEDETECTOR, CEILING FINISHED FLOORAFFABBREVIATIONSAMPEREAABOVE FINISHED GRADEAFGAIR HANDLING UNITAHUAICAMPERE INTERRUPTING CURRENTATSAUTOMATIC TRANSFER SWITCHAVAUDIO/VISUALBFGBELOW FINISHED GRADECCONDUITCATVCABLE ANTENNA TELEVISIONCFLCOMPACT FLUORESCENTCKTCIRCUITEBUEMERGENCY BATTERY UNITECEMPTY CONDUITECBENCLOSED CIRCUIT BREAKEREFEXHAUST FANERUENERGY RECOVERY UNITEQUIPEQUIPMENTETREXISTING TO REMAINEWCELECTRIC WATER COOLEREWHELECTRIC WATER HEATEREXISTEXISTINGFHPFRACTIONAL HORSE POWERFLAFULL LOAD AMPSFPVAVFAN POWERED VARIABLE AIR VOLUMEGCGENERAL CONTRACTORGFCIGROUND FAULT CIRCUIT INTERRUPTERGNDGROUNDHIDHIGH INTENSITY

2 DISCHARGEKVAKILO-VOLT AMPEREKWKILO-WATTLCLIGHTING CONTACTORLTGLIGHTINGMAUMAKE UP AIR UNITMCAMINIMUM CIRCUIT AMPSMCMECHANICAL CONTACTORMCMETAL CLADMCBMAIN CIRCUIT BREAKERMFRMANUFACTURERMLOMAIN LUGS ONLYMTDMOUNTEDNECNATIONAL ELECTRICAL CODENFNON-FUSEDNICNOT IN CONTRACTNLNIGHT LIGHTNTSNOT TO SCALEOCON CENTEROFCIOWNER FURNISHEDCONTRACTOR INSTALLEDPPOLEPCPPUMP CONTROL PANELPFPOWER FACTORPLPROPERTY LINEPNLPANELPNLBDPANELBOARD PHASEPRIPRIMARYRECPRTUROOF TOP UNITSESERVICE ENTRANCESECSECONDARYTBBTELEPHONE BACKBOARDTRTTRIPLE TUBE FLUORESCENT LAMPTVSSTRANSIENT VOLTAGETYPTYPICALUONUNLESS OTHERWISE NOTEDVVOLTSVACVOLTS ALTERNATING CURRENTVAVVARIABLE AIR VOLUMEVDCVOLTS DIRECT CURRENTCCTVCLOSED CIRCUIT TELEVISIONCBCIRCUIT BREAKERECELECTRICAL CONTRACTORHPHORSE POWER/HEAT PUMPHVACHEATING, VENTILATING,IGISOLATED GROUNDJBJUNCTION BOXPCPLUMBING CONTRACTORAND AIR CONDITIONINGVFDVARIABLE FREQUENCY DRIVEWWATTS/WIREWGWIRE GUARDWPWEATHERPROOFXFMRTRANSFORMERSURGE SUPPRESSERFPCFIRE PROTECTION CONTRACTORTRTAMPER RESISTANTRECEPTACLESDGENERAL ELECTRICAL NOTES : GENERAL : UNLESS SPECIFICALLY INDICATED OTHERWISE, ALL WORK SHOWN ON THE ELECTRICAL DRAWINGS ISNEW WORK TO BE PROVIDED UNDER THIS.

3 SEE " ELECTRICAL GENERAL DEMOLITION NOTES " SHEET FOR ADDITIONAL : COORDINATE AND COOPERATE WITH ALL TRADES ON THE DRAWINGS: SECURE AN EXTRA SET OF ELECTRICAL DRAWINGS TO BE KEPT ON SITE AND MARK, DAILY, THEDRAWINGS IN RED AS THE PROJECT PROGRESSES IN ORDER TO KEEP AN ACCURATE RECORD OF ALL DEVIATIONSBETWEEN THE WORK SHOWN ON THE DRAWINGS AND THE WORK WHICH IS ACTUALLY INSTALLED. THESE MARKEDDRAWINGS SHALL REFLECT ANY AND ALL CHANGES AND REVISIONS TO THE ORIGINAL DESIGN WHICH EXISTS INTHE COMPLETED WORK. DELIVER THE MARKED DRAWINGS TO THE <ARCHITECT/ENGINEER> AT PROJECT : TEST ALL WIRING FOR CONTINUITY AND GROUNDS BEFORE CONNECTING ANY FIXTURES OR INSULATION RESISTANCE TESTS ON ALL WIRING #8 OR LARGER TO ENSURE THAT ALL PORTIONS ARE FREEFROM SHORT-CIRCUITS AND : ARRANGE ALL NECESSARY INSPECTIONS.

4 DELIVER ALL REQUIRED INSPECTION CERTIFICATES TO : PROVIDE GROUNDING IN ACCORDANCE WITH THE NEC FOR THE ELECTRICAL SYSTEM INCLUDINGEQUIPMENT FRAMES CONDUITS, SWITCHES, CONTROLLERS, WIRE-WAYS, NEUTRAL CONDUCTORS, AND OTHEREQUIPMENT. PROVIDE A GROUNDING CONDUCTOR IN ALL POWER : PROVIDE LABELS FOR ALL PANELBOARDS, CABINETS, SAFETY SWITCHES, MOTOR-DISCONNECT SWITCHES,AND MOTOR CONTROLLERS. LABELS SHALL BE MACHINE ENGRAVED, LAMINATED PLASTIC, PERMANENTLYATTACHED WITH SELF-TAPPING SCREWS OR RIVETS. DO NOT USE SELF-ADHESIVE LABELING: LABEL ALL JUNCTION BOXES WITH PERMANENT MARKER IDENTIFYING CIRCUIT NUMBER ANDPANELBOARD OF CIRCUITS DIRECTORY: PROVIDE TYPEWRITTEN PANELBOARD DIRECTORY CARD IN EACH PANELBOARD INCLUDINGEXISTING PANELBOARDS MODIFIED FOR THIS PROJECT WITH CIRCUIT LOAD INFORMATION AND ROOM NUMBERCLEARLY IDENTIFIED.

5 USE ACTUAL ROOM NUMBERS IN THE BUILDING, NOT THE ROOM NUMBERS SHOWN ON THECONTRACT DRAWINGS, AS THEY ARE OFTEN COORDINATION: MOTORS, MOTOR STARTERS, CONTROLLERS, INTEGRAL DISCONNECT SWITCHES, ANDCONTACTORS SHALL BE PROVIDED WITH THEIR RESPECTIVE PIECES OF EQUIPMENT BY THE EQUIPMENT WITH THE TRADES PROVIDING THE EQUIPMENT, VERIFYING ALL REQUIREMENTS, PROVIDE ALLELECTRICAL CONNECTIONS REQUIRED THEREIN, AND INSTALL MOTOR DISCONNECTS: ALL MOTORS SHALL HAVE DISCONNECTING FUSE PROTECTION: WHERE FUSE PROTECTION IS SPECIFICALLY REQUIRED BY THE EQUIPMENTMANUFACTURER, PROVIDE FUSE SWITCHES IN LIEU OF NON-FUSE SWITCHES OR IN LIEU OF ENCLOSED CIRCUITBREAKERS, OR OTHER DEVICES DETAILS: SECURE APPROVED SHOP DRAWINGS SHOWING WIRING DIAGRAMS, ROUGH-IN AND HOOK UPDETAILS FROM OTHER INVOLVED CONTRACTORS FOR EQUIPMENT WHICH MUST BE CONNECTED DETAILS: MECHANICAL EQUIPMENT WILL BE FURNISHED AND INSTALLED BY THE MECHANICALCONTRACTOR.

6 THE LOCATIONS SHOWN ON THE ELECTRICAL DRAWINGS ARE APPROXIMATE. COORDINATE WITH THEMECHANICAL CONTRACTOR TO DETERMINE THE EXACT LOCATION OF EACH PIECE OF EQUIPMENT AND DETERMINETHE EXACT ROUGH-IN AND CONNECTION MOUNTING: WHERE AN INDIVIDUALLY MOUNTED SAFETY SWITCH, STARTER OR CIRCUIT BREAKER IS SHOWNADJACENT TO ITS RESPECTIVE LOAD AND NOT MOUNTED ON A WALL, PROVIDE ALL SUPPORTS, BRACKETS,ANCHORING, ETC. NECESSARY TO PROPERLY SUPPORT THE ARRANGEMENT: ARRANGE LIGHTING FIXTURES IN ACCORDANCE WITH THE ARCHITECTURAL REFLECTEDCEILING COORDINATION: COORDINATE LIGHTING FIXTURES WITH GRILLES, DIFFUSERS, SPRINKLER HEADS, ANDACCESS PANELS, COORDINATION: VERIFY CEILING AND WALL CONSTRUCTION AND MATERIAL PRIOR TO ORDERING LIGHTFIXTURES OR OTHER DEVICES TO ENSURE PROPER FIXTURES OR DEVICE IS FURNISHED TO MATCH HEIGHTS: MOUNTING HEIGHTS INDICATED ARE FROM THE FINISHED FLOOR TO THE CENTERLINE OF THEWIRING DEVICE UNLESS OTHERWISE NOTED.

7 MOUNTING HEIGHTS OF LIGHTING FIXTURES AND FIRE ALARM DEVICESARE TO THE BOTTOM OF THE FIXTURE OR DEVICE UNLESS OTHERWISE LOCATIONS: COORDINATE LOCATIONS OF SWITCHES, RECEPTACLES, AND TELE/DATA OUTLETS WITH OTHERWALL MOUNTED DEVICES SUCH AS THERMOSTATS AND CONTROL STATIONS. DO NOT mount WIRING DEVICESBACK TO BACK. PROVIDE MINIMUM OF ONE STUD RECEPTACLES: RECEPTACLES FOR ELECTRIC WATER coolers (EWC) SHALL BE INSTALLED OUT OF VIEW ANDBEHIND THE EWC ENCLOSURE. VERIFY THE MOUNTING HEIGHT WITH THE EQUIPMENT SUPPLIER PRIOR TO COORDINATION: THOROUGHLY REVIEW AND COORDINATE ALL CASEWORK, DOOR SWINGS, AND CABINETDRAWINGS AND ARCHITECTURAL ELEVATIONS WITH DEVICE LOCATIONS PRIOR TO ROUGH-IN OF OUTLET : WHERE A MULTIPLE GANG BOX HAS CIRCUITS OF DIFFERENT VOLTAGES OR SYSTEMS WHICH AREREQUIRED TO BE SEPARATED, PROVIDE THE CODE-REQUIRED SEPARATION USING A FULL HEIGHT AND DEPTHBARRIER PROOFING: FOR ANY WALL OR FLOOR PENETRATIONS THROUGH FIRE RATED STRUCTURES PROVIDEFIRE-PROOFING TO SEAL ALL THE PENETRATIONS AFTER THE CONDUIT HAS BEEN INSTALLED.

8 FIRE PROOFING FORPENETRATIONS SHALL BE UL APPROVED PER THE THE PENETRATION MADE IN ORDER TO MAINTAIN FIRE RATEDINTEGRITY OF THE GENERAL DEMOLITION NOTES : GENERAL : DEMOLITION DRAWINGS ARE BASED ON EXISTING PLANS AND FIELDINVESTIGATION PRIOR TO DEMOLITION. VISIT THE EXISTING BUILDING PRIOR TO BID INORDER TO BECOME FAMILIAR WITH THE EXISTING CONDITIONS AND IN ORDER TOAVOID ITEMS: ALL ITEMS SHOWN DASHED ON DEMOLITION PLANS ARE EXISTINGAND SHALL BE REMOVED COMPLETE INCLUDING BOXES, CONDUIT, WIRE, FASTENERS,AND ASSOCIATED APPURTENANCES ITEMS: ALL ITEMS SHOWN SOLID ON DEMOLITION PLANS ARE EXISTING TO REMAIN: EXISTING CIRCUITING TO REMAIN SHALL BE REROUTED ORRECONNECTED, AS REQUIRED, WHERE AFFECTED BY NEW WORK IN ORDER TOMAINTAIN CONTINUITY OF OF EXISTING CIRCUITRY.

9 EXISTING CIRCUITRY SERVING LIGHTING FIXTURESAND/OR RECEPTACLES FOR A GIVEN AREA SHALL BE REUSED WHERE CONVENIENT TOSERVE THE NEW LAYOUT. PROVIDE CIRCUIT MODIFICATIONS INDICATED OR ASOTHERWISE REQUIRED TO MAINTAIN THE CONTINUITY OF THE EXISTING CIRCUITS CONDUIT: ALL EXISTING CONDUITS AND WIRING THAT WILL NOT BE REUSEDSHALL BE REMOVED WHERE THEY WILL BE EXPOSED UPON COMPLETION OF NEWWORK. EXISTING CONDUIT TO REMAIN CONCEALED IN WALLS SHALL BE CONDUIT TO REMAIN BELOW FLOOR SLAB SHALL BE CUT OFF ONE INCHBELOW ROUGH FLOOR AND GROUTED FLUSH. ALL EXISTING WIRING IN CONDUITS TOBE ABANDONED SHALL BE DISCONNECTED FROM POWER SOURCE AND DAMAGE: EXERCISE CARE IN REMOVAL OF DEMOLITION ITEMS.

10 REPAIR, AT NOADDITIONAL COST TO OWNER, ANY DAMAGE CAUSED TO EXISTING CONSTRUCTIONAND/OR EQUIPMENT TO APPURTENANCES: REMOVE ALL ELECTRICAL APPURTENANCES(DISCONNECTS, STARTERS, WIRING, CONDUIT, ETC.) ASSOCIATED WITH EQUIPMENT TOBE REMOVED BY PLUGS AND COVERS: ALL CONDUIT REMOVED SHALL BE REMOVED IN ITSENTIRETY, INCLUDING FITTINGS, MOUNTING DEVICES, MOUNTING HARDWARE, CONDUIT PLUGS AND BLANKS FOR ALL OPENINGS CREATED BY THEREMOVAL OF CONDUIT. PROVIDE BLANK COVER PLATES FOR ALL OPENED OUTLETBOXES CREATED BY THE REMOVAL OF THE EQUIPMENT AND/OR MATERIALS: ALL MATERIALS REMOVED UNDER DEMOLITION, NOT TO BERELOCATED OR DESIGNATED TO BE TURNED OVER TO THE OWNER, SHALL BECOMEPROPERTY OF THE CONTRACTOR AND SHALL BE REMOVED COMPLETELY FROM OUTAGES: ALL WORK AND ALL POWER OUTAGES IN THE EXISTINGBUILDING SHALL BE SCHEDULES AT TIMES CONVENIENT TO THE : NOTIFY THE OWNER PRIOR TO TURNING OFF ANY CIRCUITS.