Transcription of GENERATOR START CONTROL MODULE - Atkinson …
1 Atkinson ELECTRONICS, 08/17 GENERATOR STARTCONTROL MODULEO perating and Installation InstructionsMany automatic CONTROL features:vvAutomatic starting, load transfer & shutdown of gas/diesel generators , especially for off-grid usesvvAutomatic adjustable voltage set-points for GENERATOR battery charging applications, 0-60V DCvvWorks with 12, 24 or 48V battery systemsvvProvides fault shutdown for low oil pressure/high temperature/under-speed/over-speed conditionsvvAll sequences have adjustable time periodsvv30 day exercise with or without load, battery equalize function availablevvRelay driver for emergency shutdown and 30 day exercise remote indicationvv12 hour maximum runtime (with override)
2 For automatic starting applicationsvvTotally sealed for harsh environment operation vvGSCM - Set-up adjustments now accomplished with three push buttons; Change/Store, Menu Up, & Menu Down. Over Hz & Under Hz shut down default set to Disabled. vvGSCM - Added a stop command after each starting attempt to ensure GENERATOR is not already running while trying to START . GENERATOR START CONTROL MODULEGSCMATKINSON ELECTRONICS, 08/17 Web Site: by:FEATURES & APPLICATIONSvvAutomatic starting, load transfer & shutdown ofgas/diesel generators , especially for off-grid usesvvAutomatic adjustable voltage set-points for generatorbattery charging applications, 0-60V DCvvWorks with 12, 24 or 48V battery systemsvvProvides fault shutdown for low oil pressure, hightemperature, under-speed or over-speed conditionsvvAll sequences have adjustable time periodsvv30 day exercise with or without load.
3 Battery equalizefunction availablevvRelay driver for emergency shutdown and 30 dayexercise remote indicationvv12 hour maximum runtime (with override) for automaticstarting applicationsvvTotally sealed for harsh environment operationDESCRIPTION & OPERATIONThe GSCM is a micro-processor based GENERATOR startingcontroller that receives either automatic or manual startcommands and starts a GENERATOR , disconnects the starter whena minimum GENERATOR frequency output is measured and monitorsthe GENERATOR operation, shutting it down if one of several faultconditions is detected. LEDs are flashed to indicate the cause ofthe shutdown.
4 Manually resetting the GSCM removes the lockoutand allows the GENERATOR to restart if called. The GSCM ispowered by 12 to 24V DC from a battery bank and will startgenerators for 12 to 48V systems. For 48V systems the GSCM must be powered by a 24V or less tap on the 48V battery bank. Adjustment for the timing controls is done during the Set -upperiod using three push button switches on the front of the GSCM unit. The Up & Down buttons allows the user to move back &forth through the different timing parameters, and change thevalue when in change mode. The Change/Store button allowsthe user to change and then store the new setting.
5 LEDs indicatewhich setting is being addressed and the stored value can beread on the test points. For example: a Crank Delay voltagesetting of is 50% of the 0 to 60 second timing range or 30seconds (see Adjustment Chart in Section-8). Timing values arestored in memory regardless of power removal until changed. The GSCM comes factory pre-set: Crank Delay @ 5s, MaximumCrank @ 15s, Load Transfer Delay @ 60s, Load Pre-Off Delay@ 90s, Battery Cut-In Volt. @ , Battery Cut-Out Volt. Run/Crank Disconnect @ 30Hz, Under Speed Shutdown& Over Speed Shutdown @ 0 (de-activated)65Hz, and 30 DayExercise Runtime @ 0 (de-activated).
6 The GSCM provides a 30 day exercise function which can besynchronized with a photovoltaic input to only START each 30 dayperiod at the beginning of the solar charge day. A user suppliedDC relay can be energized during the 30 day GENERATOR exerciseto override a battery charger and allow the battery bank toequalize by charging the batteries above the normal charger cut-off point during the exercise period. Besides generators , the GSCM can be used to START and controlgas/propane or diesel driven SIZE & " L x " W x " H, 20 OZ MOUNTING:2 screws through tabs POWER:12V to 30V DC or 24V ACQuiescent current < 10mARelay current < 25mA ea.
7 @ 12V CONNECTIONS:Qty. (29) 1/4" Spade terminals ON-OFF INPUTS:Grounded input = on conditionOpen input = off condition MANUAL INPUT:Grounded = manual start12-24V Outback signal = StartOpen = off VOLTAGE INPUTS:0-60V DC FREQUENCY INPUT: 120-300V AC 0-100 Hz ADJUSTMENTS:Qty. (1) single turn potentiometer(0-5V DC = adjustment range)Crank Delay-0 to 60 secondsMaximum Crank -0 to 60 secondsLoad Transfer Delay-0 to 60 secondsLoad Pre-Off-0 to 120 secondBattery Charge Cut-In Voltage-0 to 60V DC Cut-Out Voltage-0 to 60V DCUnder Speed Shutdown-15 to 75 HzOver Speed Shutdown-15 to 75 HzRun / Crank Disconnect -15 to 75 Hz30 Day Exercise Runtime - 0 to 1 hour OUTPUT RATINGS:Qty.
8 (5) 10 Amp 28V DC Relay contactsQty. (2) Open collector NPNtransistors, Max. 200mA each FAULT DETECTION:5 conditions that lock out GENERATOR MAX. RUNTIME:12 hours in automatic START AMBIENT TEMP:-30 to 708 CGENERATOR START CONTROL MODULEGSCMATKINSON ELECTRONICS, 08/17 Web Site: by:GSCM WIRING DIAGRAM AND CONTROLLER CONFIGURATIONUSE INSULATED TERMINALSTO PREVENT SHORTS! GENERATOR START CONTROL MODULEGSCMATKINSON ELECTRONICS, 08/17 Web Site: by:GSCM STARTING SEQUENCESECTION - 1 The GSCM indicates that it is ready to receive a START signal by blinking the START LED once every 5 seconds. The GSCM is started byshorting terminal 5 to ground (terminal 6) for manual START mode.
9 The MODULE may also START in automatic mode based on a batteryvoltage (see Section-3) or a 30 day exercise cycle. The START LED is lit continuously to indicate that a manual START signal has beenapplied. The various adjustment LED s blink during their respective GENERATOR controller time delay periods. If the GSCM detects an ACfrequency input greater than zero (ie: the GENERATOR is already running) it will not execute a START sequence. But will light the Hz LEDcontinuously. The GENERATOR starting sequence is as follows. START LED blinks once every 5 seconds to indicate that the GSCM is in a Ready to Receive a Command mode.
10 When amanual signal is received, the START LED lights constantly. After a 5 second delay, K1 (glow plug) relay closes to energize a glowplug. K1 (glow plug) relay remains closed until either the GENERATOR starts or the crank shutdown-lockout condition is adjustable 5 to 60 second crank delay period starts when K1 (glow plug) relay is the crank delay period, K2 (crank) relay closes to crank the starter while K3 (ignition) relay closes to energize the ignition. K2(crank) relay remains closed until either the GENERATOR starts or the maximum cranking time period (0 to 60 seconds) is the GENERATOR fails to START after cranking, K2 (crank) relay opens for a resting period equal to twice the maximum cranking timeadjustment, the max.