Transcription of GEP65-5 (3-Phase) - Olympian
1 WHERE THE WORLD TURNS FOR POWERE xclusively from your Caterpillar dealerGEP65-5 (3-Phase)50 kVA / kVA / kW60 kVA / kVA / kWFEATURESGENERATING SET Complete system designed and built at ISO9001certified facility Factory tested to design specifications at full loadconditions Fully engineered with a range of optionsand accessoriesENGINE Industrial water cooled diesel engine Governor, mechanical Electrical system, 12 VDC Cartridge type fuel and oil filters Air filter Battery(ies), rack and cablesGENERATOR Self excited brushless generator Insulation system, class H Drip proof generator air intake (IP23) Electrical design in accordance with BS5000 Part 99,IEC60034-1, VDE0530, UTE51100 CONTROL SYSTEM 1001 keystart control panel Vibration isolated sheet steel enclosure with hingedlockable doorMOUNTING ARRANGEMENT Heavy-duty fabricated steel base with lifting points Anti-vibration pads to ensure vibration isolation Engine coupled to generator with flexibledisc coupling Baseframe incorporates heavy-duty fabricated steelfuel tank, 8 hours running capacityEXHAUST SYSTEM Heavy duty industrial capacity exhaust silencer(approximately 10 dB reduction) supplied looseCOOLING SYSTEM Standard ambient temperatures up to 50 C (122 F) Fan, fan drive and charging alternator fully guarded Antifreeze protection coolant CIRCUIT BREAKER 3-pole miniature circuit breaker (mcb) < 160 ampsand 3-pole molded case circuit breaker (mccb)
2 >= 160 amps Vibration isolated sheet steel enclosure withremovable cover plate Outgoing cable stub-up area directly below circuitbreakerAUTOMATIC VOLTAGE REGULATOR Voltage regulation % Provides fast recovery from transient load changesEQUIPMENT FINISH All electroplated hardware Anticorrosive paint protection High gloss polyurethane paint for durability andscuff resistanceQUALITY STANDARDS BS4999, BS5000, BSEN60034, BSEN61000, IEC60034 DOCUMENTATION Operation and maintenance manuals provided Wiring diagrams includedWARRANTY All equipment carries full manufacturer's warranty. DIESELGENERATING SET50 kVA / kVA / kW60 kVA / kVA / kWExclusively from your Caterpillar dealerEngineElectronic governor (fully adjustable)Lube oil drainLube oil drain valveLube oil drain pumpGeneratorAnti-condensation heaterQuadrature droop upgradePermanent magnet generator (PMG)AREP Excitation systemCooling SystemCoolant heaterLow coolant temperature alarmLow coolant level shutdownRadiator transition flangeCoolant drainCoolant drain valve50% Anti-Freeze (Protection to -36 C)Fuel SystemManual fuel pumpLow fuel level shutdownLow fuel level alarmHigh fuel level alarmRemote fuel systemsFuel transfer systemsManual Bypass ValveSilencer System Open UnitLevel 2 silencer with mounting kit (approximately 25 dB reduction)Level 3 silencer with mounting kit (approximately 35 dB reduction)Overhead mounting kit for level 1 silencerLevel 1, 2 and 3 silencer installation kitsEnclosuresSound attenuated (EC) canopy Super sound attenuated (EC)
3 CanopyHandling/TrailersOil field skidSingle point liftFixed height chassis trailerAdjustable height chassis trailerControlsBaseframe mounted terminal box instead of control panelPowerWizard panelPower Wizard panel6000 Series digital synchronising control panelsRemote AnnunciatorsPowerWizard AnnunciatorCircuit BreakerUpgrades from 3-pole to 4-pole breakerTransfer SwitchesTM Series manual load transfer panelsATI Series load transfer panels and bypass switchesCertificationEuropean CE certification (not available on 60 Hz models)*Some options may not be available on all all options are EQUIPMENT*50 kVA / kVA / kW60 kVA / kVA / kWExclusively from your Caterpillar ..Self-excited, brushlessVoltage at steady state fromfrom no load to full for constant load fromno load to full loadWaveform <4%Radio with EN61000-6 Telephone <50, THF <2%Overspeed HTemperature Class H factory for available 3 Displacement L (cu in).. (201)Bore/stroke mm (in).
4 105/127 ( )Compression :1 Engine speed rpm50 Hz ..150060 Hz ..1800 Piston speed m/sec (ft/sec)50 Hz .. ( )60 ( )Maximum power at rated rpm kW (hp)Standby50 ( )60 ( )Prime50 ( )60 ( )BMEP kPa (psi)Standby50 (213)60 (204)Prime50 (193)60 (186)Regenerative power kW (hp)50 ( )60 Hz .. ( ) 8528 G2 SPECIFICATIONSC onsult your Olympian representative for more informationGENERATING SET DIMENSIONS AND WEIGHTSL engthWidthHeightWeight*Modelmm (in)mm (in)mm (in)kg (lb) gep65 -52149 ( )752 ( )1366 ( )960 (2116)*Includes oil and coolantNote: General configuration not to beused for installation. See generaldimension drawings for kVA / kVA / kW60 kVA / kVA / kWExclusively from your Caterpillar dealerGEP65-5 (3-Phase)**With AREP Excited Option AR20A/AR21A**With PMG Excited Option AR18A/AR19 AConsult your Olympian representative for more information**dBA levels are for guidance only**Fuel consumption data at indicated load with diesel fuel with a specific gravity of and conforming to BS2869:1998 Class Hz60 HzGenerator Set Technical DataStandbyPrimeStandbyPrimePackage PerformancePower ratingkVA (kW) ( ) ( ) ( ) ( )Lubricating SystemType: Oil pump & lubrication sumpOil filter: Spin-on, full flowOil cooler: WaterOil type required.
5 API CD 15W-40 Total lube system capacityL ( Gal) ( ) ( )Oil pan capacityL ( Gal) ( ) ( )Fuel SystemFuel Tank CapacityL ( Gal)175 ( )175 ( )Generator set fuel consumption**100% loadL/hr ( g/hr) ( ) ( ) ( ) ( )75% loadL/hr ( g/hr) ( ) ( ) ( ) ( )50% loadL/hr ( g/hr) ( ) ( ) ( ) ( )Engine Electrical SystemVoltage/ground: 12 vDC/negativeBattery charging alternator ampere ratingamps6565 Cooling SystemWater pump type: CentrifugalCooling system capacityL ( Gal) ( ) ( )Maximum coolant static headm H2O (ft H2O)TBATBAC oolant flow rateL/hr ( gal/hr)7530 (1989)9060 (2393)Minimum temperature to engine C ( F)TBATBAT emperature rise across engine C ( F)TBATBAHeat rejected to coolant at rated powerkW (Btu/min) (2144) (2002) (2434) (2332)Total heat radiated to room at rated powerkW (Btu/min) (950) (864) (1018) (967)Radiator fan loadkW (hp) ( ) ( )Air RequirementsCombustion air flowm3/min (cfm) (138) (134) (170) (166)Maximum air cleaner restrictionkPa (in H2O) ( ) ( )Radiator cooling airm3/min (cfm)TBATBAE xternal restriction to cooling airflowPa (in H2O)TBATBAG enerator cooling airm3/min (cfm) (572) (678)Exhaust SystemMaximum allowable backpressurekPa (in Hg) ( ) ( )Exhaust flow at rated powerm3/min (cfm) (367) (357) (441) (417)Exhaust temperature at rated power(dry exhaust) C ( F)571 (1060)557 (1035)564 (1047)534 (993)Generator Set Noise Rating*(without attenuation)
6 At 1 m ( ft)dBATBATBA50 Hz60 HzGenerator Technical Data415/240V 400/230V 380/220V 220/127V 480/277V 440/254V 240/120V 230/115V 380/220V230/115V220/110V240/139V 220/127V 208/120V220/110V200/115 VMotor Starting Capability:Self Excited(kVA)148139128164163140127119109 AREP Excited**(kVA)19418316721421218416715614 3PM Excited**(kVA)19418316721421218416715614 3 Full Load EfficiencyStandby% (per unit) X' " shown to the X" Constants:t'dt"t'dota50 ms5 ms1354 ms8 ms50 kVA / kVA / kW60 kVA / kVA / kWExclusively from your Caterpillar dealer50 HzVoltageStandby PrimeCodeVoltagekVAkWkVAkWVOPT502415 AT AVAILABLE VOLTAGES60 HzVoltageStandby PrimeCodeVoltagekVAkWkVAkWVOPT601480 at 27 C (80 F), m (500 ft), 60% humidity, pfSTANDBYT hese ratings are applicable for supplyingcontinuous electrical power (at variable load) inthe event of a utility power failure.
7 No overloadis permitted on these ratings. When used atstandby rating the alternator will be peakcontinuous rated (as defined in ISO8528-3).PRIME POWERT hese ratings are applicable for supplyingcontinuous power (at variable load) in lieu ofcommercially purchased power. There is nolimitation to the annual hours of operation andthis model can supply 10% overload power for1 hour in 12 2005 CaterpillarAll rights : InternationalPrinted in (05/05)Materials and specifications are subject to change without International System of Units (SI) is used in this kVA / kVA / kW60 kVA / kVA / kWExclusively from your Caterpillar dealer