Guidance FOR THE Design OFMETAL Roofing AND CLADDINGTO COMPLY WITH APPROVEDDOCUMENT L2 : 2001CI/SfBNh2(23)JANUARY 2002 MCRMA Technical Paper No. 14 PageForeword1 Checklist for compliance with approved document approved document Requirements of the approved Energy efficient Design of the building Maximum areas of windows, doors and Thermal bridging at junctions and around BRE IP 17 Building air Methods for calculating heat loss through plane areas of cladding and Roofing The development of U-value calculation Computer Thermal Surface condensation and mould Heat loss through thermal Examples of surface temperature and heat loss through thermal Example of the effect of thermal bridging on overall heat Infra-red Thermal Conditions for a Air Whole building testing of air Air leakage Heat loss due to air Laboratory tests for individual Examples of testing carried out at Example of the effect of individual joint leakage on whole cladding References4141 Contents The Metal Cladding & Roofing Manufacturers Association Limited, January 2002 MCRMA technical papers1.

Page Foreword 1 Checklist for compliance with Approved Document L2 1 1.0 Introduction 3 2.0 Approved Document L2 4 2.1 Requirements of the Approved Document 4

Tags:

  Document, Approved, Approved document l2, Approved document

Information

Domain:

Source:

Link to this page:

Please notify us if you found a problem with this document:

Other abuse

Transcription of Guidance For The Design Of Metal Roofing And …

1 Guidance FOR THE Design OFMETAL Roofing AND CLADDINGTO COMPLY WITH APPROVEDDOCUMENT L2 : 2001CI/SfBNh2(23)JANUARY 2002 MCRMA Technical Paper No. 14 PageForeword1 Checklist for compliance with approved document approved document Requirements of the approved Energy efficient Design of the building Maximum areas of windows, doors and Thermal bridging at junctions and around BRE IP 17 Building air Methods for calculating heat loss through plane areas of cladding and Roofing The development of U-value calculation Computer Thermal Surface condensation and mould Heat loss through thermal Examples of surface temperature and heat loss through thermal Example of the effect of thermal bridging on overall heat Infra-red Thermal Conditions for a Air Whole building testing of air Air leakage Heat loss due to air Laboratory tests for individual Examples of testing carried out at Example of the effect of individual joint leakage on whole cladding References4141 Contents The Metal Cladding & Roofing Manufacturers Association Limited, January 2002 MCRMA technical papers1.

2 approved document L Conservation of fuel andpower, 1995 edition HMSO approved document L2 Conservation of fuel andpower in buildings other than dwellings. DEFRA/DTLR Report: Limiting thermal bridgingand air leakage: Robust construction details fordwellings and similar buildings. The StationeryOffice, October BS EN ISO 6946 : 1997 Building componentsand building elements Thermal resistance andthermal transmittance Calculation BRE IP 17/01 Assessing the effect of thermalbridging at junctions and around openings BREA ugust CIBSE Guide A3 Thermal properties of buildingstructures CIBSE BS EN 12524 : 2000 Building materials andproducts - Hygrothermal properties -Tabulateddesign BRE Information Paper IP 5/98 : Metal cladding :assessing thermal performance9. BS EN ISO 10211-1: 1996, Thermal bridges inbuilding construction - Heat flows and surfacetemperatures, Part 1.

3 General calculationmethods10. BS EN ISO 10211-2: 1996, Thermal bridges inbuilding construction - Heat flows and surfacetemperatures, Part 2 Linear thermal BS 5250 :1989 British Standard Code of practicefor control of condensation in BS EN ISO 13788:2001 : Hygrothermalperformance of building components andbuilding elements - Internal surface temperatureto avoid critical surface humidity and interstitialcondensation Calculation methods13. A practical guide to infra-red thermography forbuilding surveys, BRE Report 176, BRE 199114. A professional s guide to testing housing forenergy efficiency, General Information Report64, Energy Efficiency Best Practice Programme, CIBSE Guide TM23:2000, Testing buildings forair leakage, CIBSE BS EN 13829 : 2001 thermal performance ofbuildings Determination of air permeability Fan pressurisation method 17. BS EN 12114:2000 Thermal performance ofbuildings - Air permeability of buildingcomponents and building elements - Laboratorytest 1 Recommended good practice for daylightingin Metal clad buildingsNo 2 Curved sheeting manualNo 3 Secret fix Design guideNo 4 Fire and external steel-clad walls: guidancenotes to the revised Building Regulations1992No 5 Metal wall cladding Design guideNo 6 Profiled Metal Roofing Design guideNo 7 Fire Design of steel sheet clad external wallsfor building: construction performancestandards and designNo 8 Acoustic Design guide for Metal roof andwall cladding No 9 Composite roof and wall cladding designguideNo 10 Profiled Metal cladding for roof and walls: Guidance notes on revised BuildingRegulations 1995 parts L & FNo 11 Flashings for Metal roof and wall cladding.

4 Design , detailing and installation guideNo 12 Fasteners for Metal roof and wall cladding: Design , detailing and installation guideNo 13 Composite slabs and beams using steeldecking: best practice for Design andconstructionOther publicationsThe Complete Package CDROMM anufacturing tolerances for profiled Metal roof andwall claddingCladSafe latent defects insurance scheme: basicguideLiabilityWhilst the information contained in this designguide is believed to be correct at the time of goingto press, the Metal Cladding and RoofingManufacturers Association Limited, its membercompanies and the Building ResearchEstablishment cannot be held responsible for anyerrors or inaccuracies and, in particular, thespecification for any application must checked withthe individual manufacturer concerned for a diagrams of typical constructions in thispublication are illustrative publication has been produced by the MetalCladding and Roofing Manufacturers Association(MCRMA)

5 In collaboration with BRE, to assist thedesigners, manufacturers and installers of metalwalls and roofs to comply with the requirements ofApproved document L2 of the BuildingRegulations, published in October 2001 to comeinto force in April describes the content of those parts of theApproved document relevant to Metal claddingand Roofing systems and gives Guidance as to: The calculation of U-values Allowing for thermal bridging at junctions andopenings Infra-red surveys Air leakage testingThe Guidance is designed to be relevant to bothtwin skin and composite panel of U-values1. approved document L2 requires that the U-values of Metal site assembled and compositepanel walls and roofs must be less than or equalto W/m2K and W/m2K respectively.(The corresponding values in Scottish TechnicalStandard J are W/m2K and W/m2K).These values include associated componentssuch as gutters and smoke vents however,rooflights, windows and doors have Because the method for calculating U-valuescontained in BS EN ISO 6496 and CIBSE GuideA does not apply to Metal Roofing and claddingsystems, more complex methods must be If the construction is one of those covered inBRE IP 5/98, the U-value can be obtained fromthe graphs or other information in the IP andcorrected for air spaces and compression of theinsulation by the profiles using the equations inthe If the component contains independent linearfeatures that can be represented by a series oftwo-dimensional models, use a two-dimensionalmodel and combine the results from the If the component contains repeating pointthermal bridges, such as clips, develop a three-dimensional model to calculate the heat flowsand then the bridging1.

6 approved document L2 requires that thebuilding fabric should be constructed so thatthere are no significant thermal bridges or gapsin the insulation layer(s) within the variouselements of the fabric, at the joints betweenelements and at the edges of elements such asthose around window and door openings. It isalso necessary to account for penetration of theinsulated envelope by features such as safetyharness posts or rafters which project to supporta canopy or for compliancewith approved document L2 Summary of window and door lintels, jambsand sillsGap between window or doorfmin= and cladding as Figs = W/mKand moved forward in line withfmin= liner = W/mKInsulation included betweenfmin= or door frame and = W/mKstructural steel and cladding, asFig to , but not with insulation includedfmin= window or door frame = W/mKand structural steel and cladding,but sill flashing crossing theinsulation, as Fig Thermal BridgesSome features of industrial buildings in which steelelements penetrate the insulation, exist at onlydiscrete points, and are not linear features like theother details discussed in this Appendix.

7 Althoughtheir analysis is not a requirement of ApprovedDocument L, it should be recognised that they canbe sources of extra heat loss from the building and,more importantly, can locally lower the internalsurface temperature low enough to cause severesurface condensation, especially in high humiditybuildings. These features are much more variablethan the other details discussed above and theexamples below are included for illustration calculations should be done wheneverany of these features are included in a highhumidity building. Two examples are shown in thefigures below:a) a harness attachment post, which is a hollowsteel post, with 2mm thick walls, which isattached to the structural steel inside thebuilding and passes through the roof;b) a girder, which is attached to the structuralsteelwork within the building and passes thoughthe insulated cladding to support, for example acanopy or eaves each example, the value of fminand the extraheat loss in W/K, caused by each is quoted; thetotal heat loss is found by multiplying this by thenumber of these features in the : Harness attachment postFig : Internal surface temperaturefmin= , Heat loss = W/KFig : Canopy girderFig : Internal surface temperaturefmin= , Heat loss = W/K2.

8 It is necessary to consider both the risk ofcondensation on each individual thermal bridgeand the effect of the increased heat loss throughthermal bridges on the overall heat from If a detail contains Metal components crossingthe insulation that would not otherwise bepresent in a plane element, surfacecondensation may occur in humid severity of the bridge, and therefore the riskof condensation, is determined by the f-factor,which is calculated by modelling the structure. Ifthis type of thermal bridge is to be included in abuilding which is likely to have a humid internalenvironment, consideration should be given toredesigning the It is also necessary to calculate the contributionof the thermal bridges to the overall heat lossfrom the building by using the linear thermaltransmittance ( -value) and then following theprocedures specified in BRE IP17/01. If the totalheat loss through the thermal bridges is greaterthan 10% of that through the plane areas,individual details must be modified to reduce theloss through the The parameters needed to comply with Part Lvia IP 17/01 (the f-value and the -value) aregiven in this report for a range of details thatshould cover most Metal clad buildings.

9 Meansof improving the thermal performance of eachdetail are presented. It will be necessary to usea two-dimensional thermal model to calculatethe f-value and the -value for all other surveys1. An infra-red survey, carried out by a competentperson, can be used to demonstrate that theinsulation is reasonably continuous over thewhole visible envelope of the Given the right conditions, infra-red surveys canprovide useful qualitative information aboutthermal bridges and air infiltration but cannotquantify their effect, nor can they be used tomeasure the U-value of walls and Infra-red surveys of the envelope of a buildingshould preferably be done from the inside andideally require calm, dry, cold and cloudyconditions; there may therefore be aconsiderable delay before conditions aresuitable. The conditions for external surveys areeven more For a survey to be successful, the buildingshould be heated for at least 12 hours beforethe survey, there should be no sun and no rainon the external The interpretation of infra-red surveys issubjective requiring experienced staff, especiallyin the presence of Metal components, withemissivities much lower that those of otherbuilding materials.

10 This may lead to disputesconcerning whether an apparent defect issignificant or leakage1. Compliance with the approved document canbe demonstrated for buildings of floor area <1000 m2by providing evidence that appropriatedesign details and building techniques havebeen used and that the work has been carriedout in ways that can be expected to Compliance with the approved document canbe demonstrated for buildings of any size bydemonstrating that the results of air leakagetests are Pressurisation testing of whole buildings gives agood estimate of their energy loss from airinfiltration in The contribution of individual areas of thebuilding envelope to the overall leakage can beidentified and quantified by the use of smoketubes, infra-red surveys and reductive The leakage through individual cladding systemsand the effect of sealing joints etc. can bemeasured in laboratory tests. The effect ofother components installed into the envelope,such as doors, windows, smoke vents 7, 8 and 9.