Hand Held Fire Extinguishers

Hand Held Fire Extinguishers |ABC Dry Chemical|Page 5 Purple K Dry Chemical|Page 6 Standard Dry Chemical|Page 7 Carbon Dioxide|Page 8 Halotron|Page 9 Water & Water Mist|Page 10 Wet Chemical - Class K|Page 11 Dry Powder - Class D|Page 12 High Flow|Page 13 Heavy Duty High Flow|Page 14 Automatic Spot Protection Fire Extinguishers |Horizontal Mini-Guards|Page 15 Vertical Mini-Guards|Page 16 Wheeled Fire Extinguishers |Wheeled Carbon Dioxide|Page 17 Wheeled Dry Chemical|Page 18-20 Wheeled Halotron|Page 23 Offshore Extinguishers |Page 21-22 Restaurant Fire Suppression Systems|Page 24-26 Foam Concentrates & Hardware|Page 27-28 Gas and Flame Detection|Page 29 Recharge Agents|Page 30 Mounting Hardware|Wall Hooks|Page 31 Marine/Vehicle Brackets|Page 32 Frequently Asked Questions|Page 33-3412 American Made Since 1968 For over four decades Buckeye FireEquipmenthas been an internationalleader in the development andmanufacture of reliable fire privately owned and operated companywith its headquarters near Charlotte, NC,Buckeye Fire Equipment has earned anexcellent reputation for quality, reliabilityand value within the commercial andindustrial fire protection offer

and manufacturing processes such as painting, dipping, and coating, including flammable liquid handling. Note:If the lower B rating is installed then the maximum travel distance to the extinguisher is reduced from 50 to 30 feet. To determine the overall A rating necessary for protection of an occupancy, divide the

Tags:

  Processes, Coating, Painting

Information

Domain:

Source:

Link to this page:

Please notify us if you found a problem with this document:

Other abuse

Transcription of Hand Held Fire Extinguishers

1 Hand Held Fire Extinguishers |ABC Dry Chemical|Page 5 Purple K Dry Chemical|Page 6 Standard Dry Chemical|Page 7 Carbon Dioxide|Page 8 Halotron|Page 9 Water & Water Mist|Page 10 Wet Chemical - Class K|Page 11 Dry Powder - Class D|Page 12 High Flow|Page 13 Heavy Duty High Flow|Page 14 Automatic Spot Protection Fire Extinguishers |Horizontal Mini-Guards|Page 15 Vertical Mini-Guards|Page 16 Wheeled Fire Extinguishers |Wheeled Carbon Dioxide|Page 17 Wheeled Dry Chemical|Page 18-20 Wheeled Halotron|Page 23 Offshore Extinguishers |Page 21-22 Restaurant Fire Suppression Systems|Page 24-26 Foam Concentrates & Hardware|Page 27-28 Gas and Flame Detection|Page 29 Recharge Agents|Page 30 Mounting Hardware|Wall Hooks|Page 31 Marine/Vehicle Brackets|Page 32 Frequently Asked Questions|Page 33-3412 American Made Since 1968 For over four decades Buckeye FireEquipmenthas been an internationalleader in the development andmanufacture of reliable fire privately owned and operated companywith its headquarters near Charlotte, NC,Buckeye Fire Equipment has earned anexcellent reputation for quality, reliabilityand value within the commercial andindustrial fire protection offer a complete line of handheld andwheeled fire Extinguishers , extinguishingagents, fire suppressing foam concentratesand hardware, pre-engineered kitchen firesuppression systems, and customizablegas detection ensure our distributors and customersget the highest quality fire protectionequipment, all of our products undergorigorous testing.

2 Both in-house and bythird party testing organizations such asUnderwriters Laboratories, Canada,Factory Mutual, ASME and the are committed to helpful and responsivecustomer service and knowledgeableand dependable technical support. Thiscommitment has earned Buckeye FireEquipment the coveted ISO 9001-2008 Quality us for more information about thewide selection of Buckeye Fire EquipmentCompany products and services. We havetrained personnel who are ready to assistyou with your fire protection Selection GuideTo provide the best protection of life and property from fire, it is critical that the properextinguisher selection be made. The classification and rating of an extinguisher arevital pieces of information for making this National Fire Protection Association (NFPA) has established the requirements forthe number, size, placement, inspection, maintenance,and testingof portable fire Extinguishers .

3 These requirements are contained in NFPA 10, Standard for Portable Fire Extinguishers .Within this standard it is stated that the selection of fire Extinguishers for a givensituation is determined by the following: the character and size of the fires anticipated to be encountered. the construction and occupancy of the property to be protected. the ambient temperature of the area where the extinguisher will be located. other factors that may dictate the selection of a particular type of ClassificationsGenerally fire Extinguishers are selected based on the hazard(s) they are intended toprotect. Classifications have been established to categorize these hazards as follows:Class A: Fires involving ordinary combustible materials such as wood,cloth, paper, rubber and many B:Fires involving flammable liquids, combustible liquids, petroleumgrease, tars, oils, oil based paints, solvents, lacquers, alcohols, and C: Fires that involve energized electrical D: Fires involving combustible metals such as magnesium,sodium, potassium and K.

4 Fires involving combustible cooking media such as vegetableoils, animal oils and HazardsThe NFPA classifies occupancies as eitherLow, Moderate or High hazard occupanciesarelocations where the total amount ofClass A combustible materials and ClassB flammables, including furnishings,decorations, and contents, is of minorquantity. This can include some buildingsor rooms occupied as offices, classrooms,churches, assembly halls, guest roomareas of hazard occupancies arelocations where the total amount ofClass A combustibles and Class Bflammables are present in greateramounts than expected under lowhazard occupancies could consist ofdining areas, mercantile shops and alliedstorage, light manufacturing, researchoperations, auto showrooms, parkinggarages and hazard occupancies arelocations where the total amount of ClassA combustibles and Class B flammablespresent, in storage, production, use,finished product, or combination thereof,is over and above those expected inoccupancies classed as moderate occupancies could consist ofwoodworking; vehicle repair; aircraft andboat servicing.

5 Cooking areas; individualproduct display showrooms; productconvention center displays; and storageand manufacturing processes such aspainting, dipping, and coating , includingflammable liquid :If the lower B rating is installed then themaximum travel distance to the extinguisher isreduced from 50 to 30 determine the overall A rating necessaryfor protection of an occupancy, divide thetotal sq. ft. by the Unit of A in the abovetable. For example if a low occupancybuilding has a total sq. ft. of 30, 30,000 by 3000 (Unit of A) = in this example the buildingwould require a minimum of five 2-Arated Of ExtinguisherOccupanciesMin. RatingUnit of ALow2-A:5/10-B3000 Moderate2-A:10/20-B1500 High4-A:40/80-B1000 Fire ClassificationMaximum TravelDistance To FireExtinguisherClass A75 FeetMaximumarea that oneextinguishercan protectand meet the75 ft.

6 Rule =11,250 sq. B50 FeetMaximumarea that oneextinguishercan protectand meet the50 ft. rule =5,000 sq. CIn accordancewith the ClassA or B hazardit is protectingClass D75 FeetClass K30 FeetMaximumarea that oneextinguishercan protectand meet the30 ft. rule =1,800 sq. RatingsAlong with the classification, the numericalrating of an extinguisher is an importantfactor in the proper selection of anextinguisher. The rating is a measure ofthe extinguishing potential of the fireextinguisher and is developed on thebasis of comparative fire Class Aand Class Bclassificationscarry numerical ratings. Basically thehigher the number associated with theclassification letter, the larger the fire the extinguisher has the potential Afire tests involve two types offire, a wood crib fire test and a woodpanel fire test.

7 For example to achieve a 3-A rating an extinguisher mustsuccessfully extinguish a burning woodcrib measuring 29 x 29 x 27 and awood panel measuring 12 x 12 .Class Bfire tests involve square panscontaining flammable example to achieve a 40-B rating anextinguisher must successfully extinguisha burning pan measuring 100 sq. are no numerical ratings associatedwith Class C, D or Class C, the electrical nonconductingcharacteristics of the agent are verified,not its extinguishing Class D, only the amount of agentand application method needed tocontrol a metal fire of a certain size andtype is Class K, the extinguisher mustextinguish 80 lbs. of burning cooking oil in a commercial deep fat fryer andcause no splashing of flaming oil outsidethe ABC extinguisher is rated3-A:40-B:C.

8 The 3 and the 40indicate the extinguishingpotential for Class A and ClassB fires respectively. The Cindicates that the agent willnot conduct electricity. Thisunit exceeds the minimumrating for Low and Moderateoccupancy GoalOur goal is to provide our customers with quality fire Extinguishers at a great pursuit of this, we are proud to say that we manufacture all our products in We mill and blend our own dry chemical agents, machine the component parts,assemble and then test our units to the highest quality Features Of Buckeye Fire Extinguishers Manufactured to meet UL/ULC s rigorous standards for commercial hazardprotection and backed by our manufacturer s warranty. Dry Chemical and Halotron extinguisher cylinders are constructed out of deep drawn andironed carbon steel.

9 Carbon Dioxide cylinders are constructed out of 6061 TG aluminum. Rechargeable. Anodized aluminum or plated brass valve assemblies for superior strength andcorrosion resistance. The extinguisher nameplate incorporates trilingual operating and maintenanceinstructions, English, Spanish and French. Color-coded gauges show operating status at-a-glance. Extinguishers have model and serial number bar coding for easy and accuratemaintenance history. Metal pull pins, vehicle brackets and wall hooks for extended unit service life. Buckeye Fire Equipment products are environmentally friendly and can be included in projects aiming for LEED Party Approvals For Peace Of MindDOTC ompliantUSCGA pproved5 ABC Dry ChemicalABC Dry Chemical is a multipurposeextinguishing agent that is suitable foruse on Class A, Class B and Class C Uses:For public areas such asoffices, classrooms, churches, parkinggarages, and hotel/motel assembly hallsand guest areas.

10 For businesses such asretail stores, light manufacturing facilities,research facilities, auto dealerships, vehicle/aircraft/marine service centers, andmanufacturing processes such as painting ,dipping, and recommended for use on sensitiveelectronic equipment or aircraft SA80 ABC10 SHISA-ABC20 SHISA-ABC30 SHISB-ABC*5 HISB40-ABC*5 HISB40-ABC*10HI SB80 ABC*20 SHISB-ABC* lb. ABC 5 lb. ABC5 lb. ABC10 lb. ABC10 lb. Short ABC20 lb. ABC30 lb. ABCV ehicle BracketWall MountVehicle BracketWall MountWall MountWall MountWall MountPt. # Alum. Valve133151091425614113401131012120N/APt . # Brass ValveN/A109152561511341N/A1212112905 Agent lb. ( kg)5 lb. ( kg)5 lb. ( kg)10 lb. ( kg)10 lb. ( kg)20 lb. ( kg)30 lb. ( kg)UL/ULC Rating1-A:10-B:C3-A:40-B:C3-A:40-B:C4-A: 80-B:C4-A:60-B:C10-A:120-B:C10-A:160-B:C Temperature Range-65 to 120 F (-54 to 49 C)Discharge Time9 sec14 sec14 sec22 sec18 sec27 sec32 secDischarge Range ft (m)9-15 ( )12-18 ( )12-18 ( )15-21 ( )15-21 ( )15-21 ( )25-30 ( )Operating Pressure100 psi (689 kPa)195 psi (1344 kPa) 195 psi (1344 kPa)195 psi (1344 kPa)195 psi (1344 kPa)195 psi (1344 kPa) 195 psi (1344 kPa)USCG ApprovalType B:C Size IType A Size IIType A Size IIType A Size IIType A Size IIType A Size IIType A Size IIType B:C Size IType B:C Size IType B:C Size IIType B:C Size IIType B:C Size IIIType B:C Size IVShip Weight** lb.