Example: bankruptcy

High Pressure Carbon Dioxide - sunway-sos.com.tw

high Pressure Carbon Dioxide 2001 Chemetron Fire Systems. All rights reserved (6/01). Chemetron Fire Systems and Cardox are registered Valve & Discharge Head (Pilot)CylSizeStockNumber(StandardAssemb lies)FilledCylinderWeight (1)Lb (Kg)Cylinder Assy DimensionsHeight (2)Diameterincmincm25#1048149387(39)29-5 #10481494121(55)39-1 #10480202154(70)55-1 #10480203216(98)60-1 #10480204291(132)62-1 (1) Cylinder weights are approximate. (2) Height is top of cylinder valve to bottom of cylinder, +_ 1/2". OPTION: Winterized cylinder assemblies (90% CO fill pressurized2with Nitrogen to 1050 PSI at 70 F) are available in allcylinder INFORMATIONHIGH Pressure CO EQUIPMENTC hemetron high Pressure Carbon Dioxide fire extinguish-ing systems provide protection for a variety of industrialapplications.

High Pressure Carbon Dioxide © 2001 Chemetron Fire Systems. All rights reserved (6/01). Chemetron Fire Systems and Cardox are registered trademarks. Description

Tags:

  High, Pressure, Carbon, Dioxide, High pressure carbon dioxide

Information

Domain:

Source:

Link to this page:

Please notify us if you found a problem with this document:

Other abuse

Transcription of High Pressure Carbon Dioxide - sunway-sos.com.tw

1 high Pressure Carbon Dioxide 2001 Chemetron Fire Systems. All rights reserved (6/01). Chemetron Fire Systems and Cardox are registered Valve & Discharge Head (Pilot)CylSizeStockNumber(StandardAssemb lies)FilledCylinderWeight (1)Lb (Kg)Cylinder Assy DimensionsHeight (2)Diameterincmincm25#1048149387(39)29-5 #10481494121(55)39-1 #10480202154(70)55-1 #10480203216(98)60-1 #10480204291(132)62-1 (1) Cylinder weights are approximate. (2) Height is top of cylinder valve to bottom of cylinder, +_ 1/2". OPTION: Winterized cylinder assemblies (90% CO fill pressurized2with Nitrogen to 1050 PSI at 70 F) are available in allcylinder INFORMATIONHIGH Pressure CO EQUIPMENTC hemetron high Pressure Carbon Dioxide fire extinguish-ing systems provide protection for a variety of industrialapplications.

2 high Pressure CO systems consist of four2basic components and their associated / Distribution ComponentsCompleter KitsControl PanelsDetection and Alarm DevicesFEATURESThe storage/distribution components consist of the1cylinders and valves, support and racking com-ponents, and discharge Primary Completer Kit includes a pilot discharge2head, pilot solenoid, pilot connection kit, dischargehose, warning sign, and manual operating instruc-tion plate. The Slave Completer Kit includes a slavedischarge head and discharge control panel monitors the detection and3actuation devices and includes timers to delay thedischarge, allowing for safe departure from theprotected detection and alarm devices are the external4components that provide audible or visual signals toalert occupants of pending problems or the possibleneed to evacuate the protected space prior Dioxide systems can be designed for total floodingand local application protection.

3 The guidelines containedin the National Fire Protection Association Standard onCarbon Dioxide (NFPA 12) and OSHA standards, as well asstate and local requirements should be followed for eitherdesign. A total flooding system can be defined as injectingCO into a room, area or compartment that has the struc-2tural integrity to retain the agent once it has been dis-charged. The minimum concentration requirement fortotal flooding systems is 34% by volume. This minimumconcentration is suitable for a wide range of ordinarycombustibles and flammable liquids. Higher concentra-tions may be required for specific flammable liquids and/orhazards that may become deep seated. The local applica-tion method requires that CO be applied to the surface of2the protected hazard for a specified time period thatinsures the fire condition has been CYLINDER AND VALVE ASSEMBLYThe cylinders that are used to store CO are spun2steel containers manufactured to DOT Specifica-tion 3AA-1800 or 3 AAA-1800 or higher.

4 Theyare available in five different capacities - 25 lb.(12 kg), 35 lb. (16 kg), 50 lb. (23 kg), 75 lb. (34 kg)and 100 lb. (45 kg) sizes. Each cylinder is stamp-ed with a serial number and hydrostatic testdate. They also come equipped with a steel capfor the physical protection of the cylinder valveduring shipment and handling. The standard cylinder assembly is composed ofa cylinder, rigid siphon tube, and valve. It is de-signed for vertical mounting DISCHARGEHEADHigh Pressure Carbon Dioxide 2001 Chemetron Fire Systems. All rights reserved (6/01). Chemetron Fire Systems and Cardox are registered View of aPilot Cylinder AssemblyPilot DischargeHead & ValveExploded View of aSlave Cylinder AssemblySlave DischargeHead & Valve* Part of Cylinder AssemblyCylinder: The steel cylinders are manufactured to theArequirements of the Department of Transpor-tation (DOT) for compressed gas storage, specifica-tion 3AA-1800 or 3 AAA-1800 or Tube: A 3/4" (19 mm) threaded stainlessBsteel tube with a wall thickness of.

5 035" (.89 mm)extends from the cylinder valve down to the bottomof the Valve: A Pressure operated cylinder valveCconsisting of a forged brass body with an externaldisc carrier and seat disc held in the normally closedposition by a spring and cylinder Pressure . The valvehas been designed to take advantage of a 7 to 1 seatto piston ratio, which assures consistent body is designed with multiple threaded connec-tions which accommodate the discharge head andcylinder. In addition, the following connections areprovided:Safety Disc (S/N 50610624): A frangible safety1disc is required for connection to the valve bodyand serves as a Pressure relief device to protectthe cylinder and personnel in case of excessiveinternal Pressure . The disc is designed to rupturewhen it is exposed to pressures between 2850and 3000 psi (16,203 to 20,685 kPa) created byhigh Check (S/N 30610033): The filling port con-2tains a check valve type device that also servesas a connection for the attachment of a solenoidpilot valve, as well as a port to fill the threads for attachments are.

6 825-14 NGO-RH-EXT (CGA No. 320).Discharge Head: Each cylinder requires the additionDof a discharge head to open its valve. The dischargehead is attached to the cylinder by means of a swivelnut that engages the threads of the valve. Threedifferent types of discharge heads can be used:a)pilot operated type with handwheel for manualoperation b)pilot operated type without handwheelc) Pressure operated typeEach of the three types includes an internal oper-ating piston connected to a hollow stem that is usedto upset the cylinder seat disc when operated,which allows the agent to exit. A stainless steel ballcheck at the top of the stem provides a safety fea-ture to prevent excessive loss of Carbon dioxidefrom the manifold if the system is discharged Pressure Carbon Dioxide 2001 Chemetron Fire Systems.

7 All rights reserved (6/01). Chemetron Fire Systems and Cardox are registered KitsPrimary20480483 Slave20480484 QuantityQuantityPilot cylinder hose kit 10 Solenoid valve 10 Warning sign101/2" Discharge hose11 Instruction sign10 Pilot discharge head10 Slave discharge head01If cylinders are used in a Main/Reserve system, order decals:Main Decal - S/N 50360753 Reserve Decal - S/N 50360752 COMPLETER KIT - PRIMARYTwo types of completer kits that contain the necessarycomponents required to make the cylinder functional OPERATED HEAD WITH HANDWHEELS tock Number 30610143 This discharge head is designed with a 1/4 (6 mm) NPTconnection for pilot Pressure entry to the top of an internalpiston for valve operation. It is used on the actuationcylinders.

8 This head also operates when Pressure from themanifold is applied to the piston. It contains an internalvent opening to prevent the accumulation of Pressure onthe piston when leakage occurs through the solenoidvalve to prevent accidental discharge head is also provided with a handwheel formanual operation, which is independent of a need forelectric power. The handwheel is turned counterclockwisefor operation. The NFPA 12 Standard on Carbon Dioxiderequires that when three or more cylinders are used, twopilot discharge heads are needed to open the OPERATED DISCHARGE HEADS tock Number 10610715 This head contains the same features as the pilot head;however, it does not have a handwheel and lacks the pilotconnection port. It is operated by manifold Pressure thataccumulates in the discharge outlet during pilot CONNECTOR - DISCHARGES tock Number 50260263A 1/2" (13 mm) braided hose (14-1/2" long) is usedto connect each discharge head to a cylindermanifold or outlet pipe.

9 The hose is Teflon linedwith an outer stainless steel wire braid are 1/2" (13 mm) male pipe threadconnections on one end. One endalso contains a union joint foreasy make-up without twisting,while the other has a couplingwith male adapter for easy PILOT HOSESL engths of 3/16" (5 mm) braided hose are used to inter-connect the solenoid valves to the pilot port on eachdischarge head. They are Teflon lined with an outerstainless steel braided cover. There is a 1/4 (6 mm) swivelflare connection at each Pressure Carbon Dioxide 2001 Chemetron Fire Systems. All rights reserved (6/01). Chemetron Fire Systems and Cardox are registered Pilot HoseStockNumberDescription102602603/16 in. (5 mm) Connector 16 in.

10 ( cm) long102602673/16 in. (5 mm) Connector 20 in. ( cm) long102603033/16 in. (5 mm) Connector 28 in. ( cm) longStockNumberDescription20610015 Solenoid pilot valve assembly 120V-60Hz/24 VDC20610168 Explosionproof Solenoid pilot valve assembly 24 VDCS tockNumberDescription101700892 Pole Pressure Switch indoor use only70170229 Explosionproof 3 Pole Pressure Switch101700654 Pole Pressure Switch in. (13 mm) Selector in. (19 mm) Selector valve106103711 in. (25 mm) Selector in. (38 mm) Selector valve106103702 in. (51 mm) Selector valve106107333 in. (76 mm) Selector valve106107344 in. (102 mm) Selector valveSOLENOID PILOT VALVEA solenoid pilot valve assembly includes a Pressure gaugeand adapter with swivel nut. The adapter has an O-ringsealed connection for attachment to the cylinder SWITCHAn optional Pressure switch is used in the system toimplement the shut down of power to various items ofequipment, such as fans, and for annunciation and alarmpurposes.