HONEYWELL UDC1200 MICRO-PRO . HONEYWELL UDC1200 . Universal DigitalMICRO-PRO. Controller Start-Up Guide Document #51-52-33-142. 1. Mounting Page 2. 2. Wiring Page 2. 3. Select Mode Page 3. 4. Configuration Mode Page 3. 5. Setup Mode Page 6. 6. Operator Mode Page 7. 7. Automatic Tuning Mode Page 8. 8. Product Information Mode Page 8. 9. Installing Option Modules Page 9. 10. Error Fault Indications Page 10. The full users manual can be downloaded from HONEYWELL IMC Web page UDC 1200 Start-Up Guide Page 1 of 10 Rev 1. 11/03. HONEYWELL UDC1200 MICRO-PRO . Universal Digital Controller CAUTION: Installation and configuration should be performed only by personnel who are technically competent to do so.

UDC 1200 Start-Up Guide Page 3 of 10 Rev 1 11/03 Select mode is used to access the configuration and operation menu functions. It can be accessed at any time by holding down and pressing .

Information

Domain:

Source:

Link to this page:

Please notify us if you found a problem with this document:

Other abuse

Transcription of HONEYWELL UDC1200 MICRO-PRO

1 HONEYWELL UDC1200 MICRO-PRO . HONEYWELL UDC1200 . Universal DigitalMICRO-PRO. Controller Start-Up Guide Document #51-52-33-142. 1. Mounting Page 2. 2. Wiring Page 2. 3. Select Mode Page 3. 4. Configuration Mode Page 3. 5. Setup Mode Page 6. 6. Operator Mode Page 7. 7. Automatic Tuning Mode Page 8. 8. Product Information Mode Page 8. 9. Installing Option Modules Page 9. 10. Error Fault Indications Page 10. The full users manual can be downloaded from HONEYWELL IMC Web page UDC 1200 Start-Up Guide Page 1 of 10 Rev 1. 11/03. HONEYWELL UDC1200 MICRO-PRO . Universal Digital Controller CAUTION: Installation and configuration should be performed only by personnel who are technically competent to do so.

2 Local Regulations regarding electrical installation & safety must be observed. 1. INSTALLATION. Panel-Mounting The mounting panel must be rigid and may be up to ( inches) thick. The cut-out required for the instrument is shown on the right. Instruments may be mounted side-by-side in a multiple installation for which the cut-out width (for n instruments) is (48n-4)mm or ( )inches. Slide mounting clamp over the instrument housing towards rear Panel face of mounting panel until the tongues engage in ratchets and Instrument instrument is clamped in position. Ratchets 45 x 45mm Gasket + Hold instrument firmly in position (apply pressure to bezel only).

3 CAUTION: Do not remove the panel gasket; it is a seal against dust and moisture. 2. WIRING. Rear Terminal Wiring CAUTION: Check information label on USE COPPER CONDUCTORS. housing for correct operating voltage before (EXCEPT FOR T/C INPUT). connecting supply to Power Input Single Strand wire gauge: Fuse: 100 240V ac 1amp anti-surge Max (18 SWG). 24/48V ac/dc 315mA anti-surge UDC 1200 Start-Up Guide Page 2 of 10 Rev 1. 11/03. 3. SELECT MODE. Select mode is used to access the configuration and operation menu functions. It can be accessed at any time by holding down and pressing . Once in select mode, press or to select the required mode.

4 An unlock code is required to prevent unauthorised entry to Configuration, Setup & Automatic Tuning modes. Press or to enter the correct code number, then press to proceed. Mode Upper Lower Description Default Display Display Unlock Codes Operator Optr SLCt Normal instrument operation. None Set Up SetP SLCT Tailor settings to the application.. Configuration Conf SLCT Configures the instrument for use.. Product Info Info SLCT Check manufacturing information. None Auto-Tuning Atun SLCT Invoke Pre-Tune or Self-Tune.. Note: The instrument will always return automatically to Operator mode if there is no key activity for 2 minutes.

5 4. CONFIGURATION MODE. First select Configuration mode from Select mode (refer to section 2). First select Configuration mode from Select mode (refer to section 3). Press to scroll through the parameters, then press or to set the required value. To accept a change must be pressed, otherwise parameter will revert to previous value. To exit from Configuration mode, hold down and press , to return to Select mode. Note: Parameters displayed depends on how instrument has been configured. Parameters marked * are repeated in Setup Mode. Parameter Lower Upper Adjustment range Default Display Display Input Range/Type C)/ See following table for possible codes J T/C.

6 Code Input Type & Range Code Input Type & Range Code Input Type & Range B: 100 1824 C L: C. bC PtRh20% vs 40%: B: 211 3315 F L: F P24F 32 3362 F. bF CC C: 0 2320 C NC N: 0 1399 C PTC Pt100: -199 800 C. CF C: 32 4208 F NF N: 32 2551 F PtF Pt100: -328 1472 F. J: -200 1200 C R: 0 1759 C Pt100: C. JC rC. J: -328 2192 F R: 32 3198 F Pt100: F. JF rF. J: C S: 0 1762 C : 0 20 mA DC. SC. J: F S: 32 3204 F : 4 20 mA DC. SF. KC K: -240 1373 C tC T: -240 400 C : 0 50 mV DC. KF K: -400 2503 F tF T: -400 752 F 10 50 mV DC. K: C T: C : 0 5 V DC. K: F T: F : 1 5 V DC. LC L: 0 762 C PtRh20% vs 40%: : 0 10 V DC. L: 32 1403 F P24C 0 1850 C.

7 LF : 2 10 V DC.. Parameter Lower Upper Adjustment range Default Display Display Scale Range Upper +1' Scale Range Lower Limit +100 to Range Max Range max Limit (Lin=1000). Scale Range Lower +'' Range Min. to Scale Range Upper Limit -100 Range min Limit (Linear=0). Decimal point =) - 0=XXXX, 1= , 2= , 3= 1. position (non-temperature ranges only). Control Type ) -C#' Primary (heat) only -C#' . UDC 1200 Start-Up Guide Page 3 of 10 Rev 1. 11/03. Parameter Lower Upper Adjustment range Default Display Display =1 ' Primary & Secondary (heat/cool) . Primary Output 3.*' +!1 Reverse Acting +!1 . Control Action = + Direct Acting . Alarm 1 Type ' ):$ Process High Alarm ):$.

8 :' Process Low Alarm = Deviation Alarm C= Band Alarm C C No alarm High Alm 1 value* )? Range Min. to Range Max Range Max. Low Alm 1 value* )' in display units Range Min. Band Alm 1 value* ' 1 LSD to span from setpoint in display units . Dev. Alm 1 value* = ' +/- Span from setpoint in display units . Alm 1 Hysteresis* $4 1 LSD to full span in display units . Alarm 2 Type* ' ):' . High Alm 2 value* )? Range Max. Low Alm 2 value* )' Options as for alarm 1. Range Min. Band Alm 2 value* ' . Dev. Alm 2 Value* = ' . Alm 2 Hysteresis* $4 . Loop Alarm ' C = - (disabled) or C (enabled) = , . Loop Alarm Time* ' . 1 sec to 99 mins.

9 59secs (only applies if primary proportional band = 0) .. Alarm Inhibit %C? C C! No alarms Inhibited C C! . ' Alarm 1 inhibited ' Alarm 2 inhibited /? Alarm 1 and alarm 2 inhibited Output 1 Usage 0- )+ Primary (Heat) Power )+ . -!N Secondary (Cool) Power 7:= Alarm 1, Direct :+ Alarm 1, Reverse := Alarm 2, Direct :+ Alarm 2, Reverse '):= Loop Alarm, Direct '):+ Loop Alarm, Reverse +:= Logical Alarm 1 OR 2, Direct +:+ Logical Alarm 1 OR 2, Reverse =:= Logical Alarm 1 AND 2, Direct =:+ Logical Alarm 1 AND 2, Reverse +!/- Retransmit SP Output +!/) Retransmit PV Output Linear Output 1 /4) : 0 5 V DC output 1 : . Range : 0 10 V DC output : 2 10 V DC output : 0 20 mA DC output UDC 1200 Start-Up Guide Page 4 of 10 Rev 1.

10 11/03. Parameter Lower Upper Adjustment range Default Display Display : 4 20 mA DC output Retransmit Output 1 + $ -1999 to 9999 (display value at which output will Range Scale maximum be maximum) max Retransmit Output 1 + ' -1999 to 9999 (display value at which output will Range Scale minimum be minimum) min Output 2 Usage 0- Sec or As for output 1 Al2. Lin. O/P 2 Range /4) : . Retransmit Output 2 + $ -1999 to 9999 (display value at which output will Range Scale maximum be maximum) max Retransmit Output 2 + ' -1999 to 9999 (display value at which output will Range Scale minimum be minimum) min Output 3 Usage 0- 7:= . As for output 1.