Transcription of Hydraulic Concentrate Control Valve
1 CHEMGUARD204 S. 6th Ave Mansfield, Tx 76063 (817) 473-9964 FAX (817) DATA SHEET #D10D03129 REVISION: 09/2005 The standard Hydraulic actuated valveassembly consists of a factory assembled andtested quarter turn full port ball Valve to which ahydraulic actuator has been attached. The ballvalve has a bronze body with 316 stainlesssteel ball and stem, or is of all stainless steelconstruction. Valve seats are glass-reinforcedTFE. Inlet and outlet threads are female NPTand flanges are ANSI Class 150. All valves arerated 600 psi WOG. Stainless steel flangedvalves are rated 285 psi Hydraulic actuator is mounted directly tothe ball Valve using a mounting bracket. Thehousing of the actuator has a corrosionresistant exterior with a two-part epoxy coatingproviding extra protection against aggressiveenvironments. The interior has a long life epoxyor of PTFE finish protecting all body partsagainst wear and corrosion.
2 The hydraulicactuator is equipped with a visual valveposition indicator and has the capability formanual override using a free handle, securedto the Valve body with a length of chain. Waterto drive the Valve open is fed to the hydraulicactuator through -inch to 1/2-inch pipe ortubing. A connection from the sprinkler systemis usually made from a normally unpressurizedport, such as the water motor alarm line on thealarm or deluge Valve to power the hydraulicactuator. The water inlet to the hydraulicactuator is provided with a Y strainer andshut-off Valve to allow depressurizing andresetting of the Valve after use. In the eventelectric operation is required or preferred, asolenoid release is installed in the water supplyline to the actuator, which will, on systemactuation, allow water to flow into the actuatorbody and open the Chemguard Hydraulic Concentrate controlvalve is designed for use with either a bladdertank or a balanced pressure proportioningsystem.
3 The Valve is used to automatically openthe line supplying foam Concentrate to a ratiocontroller. Except for those valves ordered withan electric solenoid, electrical power is notrequired for operation, only water pressure from asystem that has been (6) Six different sizes available. Normal operating pressure range is 40 to 120psi ( to bar). (See Note 1) Maximum actuator overload pressure 200 psi( bar). (See Note 1) Durable epoxy finish Corrosion resistant alloy case Actuator has easy stop adjustments at each endof stroke for accurate seating of the ballHydraulic ConcentrateControl ValveCHEMGUARD204 S. 6th Ave Mansfield, Tx 76063 (817) 473-9964 FAX (817) DATA SHEET #D10D03129 REVISION: 09/2005 ORDERING INFORMATIONPart 1" Hydraulic actuated ball Valve , bronze threaded valve2006 1" Hydraulic actuated ball Valve , stainless steel flanged valve3004 1- Hydraulic actuated ball Valve , bronze threaded valve4004 1- " Hydraulic actuated ball Valve , bronze threaded valve4005 1- Hydraulic actuated ball Valve , stainless steel flanged valve5004 2" Hydraulic actuated ball Valve , bronze threaded valve5005 2" Hydraulic actuated ball Valve , stainless steel flanged valve6004 2- " Hydraulic actuated ball Valve , bronze threaded valve6005 2- " Hydraulic actuated ball Valve , stainless steel flanged valve7004 3" Hydraulic actuated ball Valve , bronze threaded valve7005 3" Hydraulic actuated ball Valve , stainless steel flanged valveOPTION.
4 For solenoid direct mounted on actuator assembly add the following to part number: S24 for 24V DC solenoid S120 for 120V AC solenoid For solenoid sold separately use part number: 7000 for 24V DC solenoid 7002 for 120V AC solenoid For water regulator sold separately use part number: 7001 NOTE 1:If normal water supply pressure to actuator operating the Valve is above 120 psi ( bar), a water regulator (Part Number 7001)Is recommended to reduce actuator inlet pressure so that it does not exceed 120 psi ( bar). Excessive water inlet pressure tothe actuator can cause damage to the Valve Concentrate Control VALVEPart SizeEnd ConnectionActuatorValve Length - A in. (mm)2005 1"Threaded, NPT059-100 1" SS RF Flanged, (ANSI, 150#) 059-100 1-1/4"Threaded, NPT059-100 1-1/2"Threaded, NPT079-100 1-1/2" SS RF Flanged, (ANSI, 150#) 079-100 2"Threaded, NPT079-100 2" SS RF Flanged, (ANSI, 150#) 079-100 2-1/2"Threaded, NPT099-100 2-1/2" SS RF Flanged, (ANSI, 150#) 099-100 3"Threaded, NPT099-100 3" SS RF Flanged, (ANSI, 150#) 099-100 : Dimensions subject to change without notice.