I-Line™ Circuit Breaker Panelboards

I-Line Circuit Breaker PanelboardsCatalog2110CT9701R07/192019 Class 2110 CONTENTSD escription ..PageProduct Description .. Page 2 Features and Benefits .. Page 6 Accessories .. Page 7 General and Application Information .. Page 8 Dimensions.. Page 13 I-Line Circuit Breaker PanelboardsProduct Description207/2019 1998 2019 Schneider ElectricAll Rights Reserved Product DescriptionSquare D -brand I-Line Circuit Breaker power distribution Panelboards are for use on AC or DC systems. The panels, labeled cULus (compliance to UL and CSA standards certified by UL) are also Underwriters Laboratories (UL ) Listed under File E33139. The following are suitable for use as service entrance equipment: All main Circuit Breaker Panelboards . All main lugs Panelboards with branch -mounted, back-fed main Circuit Breaker . (For Canadian MLO service entrance, use HCP-SU and HCR-U only). All main lugs Panelboards with six disconnects or less. A solid neutral that is insulated, but may be bonded to the box with a grounding strap.

• I-Line panelboards, with branch circuit breakers installed, are short-circuit tested as complete units. • All tests are conducted in accordance with UL 67 and CSA C22.2 (Standards for Panelboards). With I-Limiter main circuit breaker, I-Line main circuit breaker panelboards are UL/CSA Listed for use on systems with up to a 200,000 maximum RMS

Tags:

  Breaker, Circuit, Branch, Circuit breakers, Branch circuit

Information

Domain:

Source:

Link to this page:

Please notify us if you found a problem with this document:

Other abuse

Transcription of I-Line™ Circuit Breaker Panelboards

1 I-Line Circuit Breaker PanelboardsCatalog2110CT9701R07/192019 Class 2110 CONTENTSD escription ..PageProduct Description .. Page 2 Features and Benefits .. Page 6 Accessories .. Page 7 General and Application Information .. Page 8 Dimensions.. Page 13 I-Line Circuit Breaker PanelboardsProduct Description207/2019 1998 2019 Schneider ElectricAll Rights Reserved Product DescriptionSquare D -brand I-Line Circuit Breaker power distribution Panelboards are for use on AC or DC systems. The panels, labeled cULus (compliance to UL and CSA standards certified by UL) are also Underwriters Laboratories (UL ) Listed under File E33139. The following are suitable for use as service entrance equipment: All main Circuit Breaker Panelboards . All main lugs Panelboards with branch -mounted, back-fed main Circuit Breaker . (For Canadian MLO service entrance, use HCP-SU and HCR-U only). All main lugs Panelboards with six disconnects or less. A solid neutral that is insulated, but may be bonded to the box with a grounding strap.

2 Service entrance Panelboards meeting the requirements of CSA are available in Canada factory-assembled Circuit Breaker Panelboards are available as 400 1200 A main lugs only and 100 1200 A main Circuit breakers. I-Line Panelboards are designed to accept the following Circuit breakers: FA, FH, BD, BG, BJ, BK, HD, HG, HJ, HL, HR, QB, QD, QG, QJ, JD, JG, JJ, JL, JR, LA, LD, LG, LJ, LH, LL, LR, MG, MJ, PG, PJ, PK, PL, RG, RJ, RK, and Circuit Breaker Panelboards are designed, manufactured, and tested to comply with the following standards:ServiceI-Line Circuit Breaker Panelboards can be used on the following system voltages: 120/240 VAC; 1-phase, 3-wire 240 VAC; 1-phase, 2-wire 240 VAC; 3-phase, 3-wire 240 VAC Ground, B-phase; 3-phase, 3-wire 208Y/120 VAC; 3-phase, 4-wire 480Y/277 VAC; 3-phase, 4-wire 480 VAC; 3-phase, 3-wire 600Y/347 VAC; 3-phase, 4-wire 600 VAC; 3-phase, 3-wire 125/250 VDC; 3-wire 250 VDC; 2-wireStandardDescriptionUL 50 Standard for enclosures for electrical equipmentUL 67 Standard for panelboardsCSA , Nos.

3 29 and 94 1989 Standard for Panelboards and enclosed panelboardsNFPA 70 National Electrical Code (NEC)NEMA PB 1 Standard for panelboardsW P 115C Type 1 Class 1 Specification for Circuit Breaker panelboards2000 IBCUS standard for seismic requirements1995 NBCCC anadian standard for seismic requirementsType HCR-U 1200 A Main Circuit BeakerType HCR-U 1200 A Main Circuit BeakerI-Line Circuit Breaker PanelboardsProduct Description307/2019 1998 2019 Schneider ElectricAll Rights Reserved Panelboard TypesPanelboard TypeMaximum Mains AmpacityMaximum branch Circuit Breaker Frame Size aEnclosure Dimensions bMain LugsMain Circuit BreakersLeft RightWidth#IN (mm)Depth#IN (mm)HCJ800 A800 AJDJD32 (813) (241)HCP-SU800 A800 A cMG, PG None 26 (600) (241)HCP1200 A800 A cMG, PG JD42 (1067) (241)HCR-U1200 A1200 A cRGJD44 (1118) (241)aFor a complete listing of applicable Circuit Breaker types, refer to the dimensions to the Dimensions section for standard panelboard as a main Circuit Breaker panelboard when provided with a branch mounted back-fed main Circuit HCP 600 A Main Circuit BreakerType HCP-SU800 A Main Circuit BeakerType HCJ 400 A Main LugsI-Line Circuit Breaker PanelboardsProduct Description407/2019 1998 2019 Schneider ElectricAll Rights Reserved Enclosure TypesTypesEnvironments Provides Protection AgainstType 1 IndoorContact with the enclosed equipmentType 2 IndoorFalling water and dirtType 3 ROutdoorFalling rain, sleet.

4 Undamaged by iceType 4/4X Stainless Indoor/OutdoorCorrosion, hose-directed water, dustType 5 IndoorSettling dust, falling dirt, dripping liquidsType 12 IndoorCirculating dust, falling dirt, dripping liquidsFronts:HCJ, HCP, HCP-SU, and HCR-U surface and flush trims available as four-piece construction, standard (door not included). An optional four-piece trim with door is also 1 EnclosuresFinished with gray-baked enamel electrodeposited over cleaned phosphatized steel (ANSI 49).Directory card holders provided with all :Galvanized steel in 26, 32, 42, and 44-inch (660, 813, 1067, and 1118 mm) endwalls without 3R, 5, and 12 EnclosuresGasketed door with vault handle and directory card and side gutter drain screw for Type with gray-baked enamel electrodeposited over cleaned phosphatized steel (ANSI 49).Type 4X Enclosures (Factory-Assembled Only)Corrosion-resistant, stainless and card located on inside of 1 and 2 Enclosure with Optional DoorFlush Lock used on HCJ, and HCP-SU Types 1 and 2 Fronts(Catalog No.)

5 PK4FL)Sliding Vault Lock used on HCP, and HCR-U Types 1 and 2 Fronts (Catalog No. PK5FL)Vault Handle used on all Type 3R, 5, and 12 Enclosures (Catalog No. PK4 NVL)Type 3R, 5, and 12 EnclosuresType 3R, 5, and 12 EnclosuresI-Line Circuit Breaker PanelboardsProduct Description507/2019 1998 2019 Schneider ElectricAll Rights Reserved Main Breaker Panelboards Accept a maximum 1200 A, 80% or 100% rated main Breaker . Available factory-assembled or merchandised.* Factory-assembled main Circuit Breaker interiors are available bottom-feed or top-feed. Suitable for use as service entrance equipment with appropriate barriers, US and Canada. Accepts mechanically restrained I-Line Circuit breakers. Available with a short Circuit current rating (SCCR) up to 200 kA maximum (100 kA @ 600 VAC) when supplied by an I-Limiter Circuit Breaker . Available with a silver-plated or tin-plated copper bus, or tin-plated aluminum bus. Solid neutral is mounted in the mains compartment with the main Circuit Breaker .

6 Merchandised Panelboards are provided as Lugs Only Panelboards Available with main lug only interiors rated up to 1200 A. Available factory-assembled or merchandised. Suitable for use as service entrance equipment when provided with a main Circuit Breaker , US and Canada. Accepts mechanically restrained I-Line Circuit breakers. Available with a short Circuit current rating (SCCR) up to 200 kA maximum (100 kA @ 600 VAC) when supplied by an I-Limiter Circuit Breaker . Available with a silver-plated or tin-plated copper bus, or tin-plated aluminum bus. Solid neutral is mounted in the mains compartment with the main lugs. Hinged cover, isolated main lugs compartment. Main lug interiors are available as top-feed or Neutral Mounts in main lug or main Circuit Breaker compartment. Does not take up interior Circuit Breaker mounting space. UL/CSA Listed for use with Al or Cu conductors. Copper or aluminum neutral available. 200% rated neutral available as a factory-assembled Circuit Breaker and Solid Neutral Compartment (Canada service entrance not shown)Main Lug and Solid Neutral CompartmentTypical Solid NeutralMain neutral lugFull capacity bonding strap for use on service entrance applicationsNeutral with C/T for Use on HCR-U When Ground-Fault Protection is Required (Catalog No.)

7 HCR12 SNCT)I-Line Circuit Breaker PanelboardsFeatures and Benefits607/2019 1998 2019 Schneider ElectricAll Rights Reserved Features and BenefitsFeatured below are just a few of the many features and benefits of Square D -brand I-Line Circuit Breaker BreakersI-Line Circuit breakers, with their exclusive bus connection design, provide superior reliability and performance Breaker Mounting 15 1200 A frame Circuit breakers require only a screwdriver and are firmly attached to the bus stack and mechanically attached to the interior assembly. The connectors are an integral part of the I-Line Circuit Breaker eliminating the assembly of connectors to the bus bar. Pre-assembled hardware means reduced installation time. The unique line side connection requires no routine maintenance. I-Line Bus Structure and Circuit Breaker MountingPush-to-TripPush-to-trip is a standard feature on all I-Line Circuit breakers. It is useful for checking Circuit Breaker operation and for testing auxiliary devices.

8 The Circuit Breaker is mechanically tripped by pressing the push-to-trip button in the Circuit Breaker ConnectionsAll Circuit Breaker connections are blow-on type. Under high-level short Circuit conditions, the magnetic forces developed tend to draw the connector jaws together, gripping the I-Line bus bar more MountingBus phase insulators interlock with the Circuit Breaker insulating shroud and provide high dielectric strength between the bus breakers on right-hand side of the busstructure are completelyindependent of positionand frame size of thoseon left-hand shroud keys into slots in bus support base. Aligns and supports line end of Circuit polyester insulators provide continuous bus bar Breaker connectors are shrouded and braced in molded protective insulator. Circuit Breaker jaws are lubricated and pre-set at the factory and require no Breaker mounting bracket an integral part of each Circuit Breaker ; securely supports and aligns load end of Circuit channels provide additional support for insulator bracing ConnectionsI-Line Circuit Breaker PanelboardsAccessories707/2019 1998 2019 Schneider ElectricAll Rights Reserved Short Circuit Current Rating (SCCR) SCCR is equal to the lowest interrupting capacity of a branch or main Circuit Breaker installed in the panelboard.

9 I-Line Panelboards , with branch Circuit breakers installed, are short- Circuit tested as complete units. All tests are conducted in accordance with UL 67 and CSA (Standards for Panelboards ).With I-Limiter main Circuit Breaker , I-Line main Circuit Breaker Panelboards are UL/CSA Listed for use on systems with up to a 200,000 maximum RMS symmetrical amperes available fault current (100 kA @ 600 VAC).I-Line Plug-on Unit with Surgelogic SPD SPD requires no wiring or conduit, saving labor time and materials. Bus-connected design enhances performance. Meets the requirements of UL and CSA for retrofit applications in existing I-Line Panelboards and switchboards. Integrated and Circuit Breaker disconnects feature compact design, requiring only inches (343 mm) of branch mounting space. SCCR up to 200 kA rating (100 kA @ 600 VAC) meets a wide variety of customer wide variety of accessories are available for field or factory installation ofI-Line Ground BarsEquipment ground bars mount in the panelboard box to provide convenient termination of equipment grounding conductors.

10 They are available in copper or ExtensionsBox extensions provide additional end gutter for feeding cables into the end of the cabinet; they are UL/CSA FillersBlank fillers are required to cover unused mounting space in I-Line Main Breaker BarriersPrimarily for use in Canada, these barriers provide additional protection for backfed main Plug-On Unit with Surgelogic SPDE quipment Ground Bar (Catalog No. PK32 DGTA)Typical Box ExtensionsBlank Fillers (Catalog Nos. HNM4BL and HNM1BL)I-Line Circuit Breaker PanelboardsGeneral and Application Information807/2019 1998 2019 Schneider ElectricAll Rights Reserved General and Application InformationPlease refer to Digest Section 9 for Circuit Breaker ratings Breaker Frame TypeMaximum Voltage RatingNumber of RatingUL/CSA Interrupting Rating RMS Amperes (Symmetrical)AC Volts, 50/60 HzDC Volts120240480600125250FA 240 V240215 10010 K25 K 5 K3FA 480 V277135 10025 K25 K18 K 10 K10 K480215 1003FH a277115 3065 K65 K c25 K 10 K 6002, 335 10025 K c15 100 18 K 50 KBD600 Y1, 2, 315 12525 K25 K18 K14 K BG600 Y1, 2, 315 12565 K65 K35 K18 K BJ600 Y1, 2, 315 125100 K100 K65 K25 K BK600 Y1, 215 30100 K100 K65 K65 K HD6002, 315 15025 K25 K18 K14 K20 K20 KHG6002, 315 15065 K65 K35 K18 K20 K20 KHJ6002, 315 150100 K100 K65 K25 K20 K20 KHL6002, 315 150125 K125 K100 K50 K20 K20 KHR600315 150200 K200 K200 K100 K QB2402, 370 22510 K10 K QD2402, 370 22525 K25 K QG2402, 370 22565 K65 K QJ e2402, 370 225100 K100 K JD6002, 3150 25025 K25 K18 K14 K20 K20 KJG6002, 3150 25065 K65 K35 K18 K20 K20 KJJ6002, 3150 250100 K100 K65 K25 K20 K20 KJL6002, 3150 250125 K125 K100 K50 K20 K20 KJR6002, 3150 250200 K200 K200 K100 K LA6002, 3125 40042 K42 K30 K22 K10 K10 KLH a6002.