IG-55: Inert Gas Fire Suppression System

IG-55: Inert GasFire Suppression Systemaguileraextinci nIndexWhat is IG-55 Argonaex? 2 Characteristics and application System 2 Storage, regulations, concentration and valve 3 Inert fire extinguishing at a glance 4 Applications, advantages and qualities of Argonaex 6 Our promise: services and guarantees 81 What isIG-55?IG-55 is a gas made up of a mix of equal parts:50% argon (IG-01) and 50% nitrogen (IG-100).Its components are found naturally in theenvironment, so there is no global warmingeffect and it does not destroy the ozone density is similar to that of air and bothargon and nitrogen are clean, non-corrosive,colourless and insipid gases, so they offer greatflexibility in adapting to all actuation systems,since they can be used at normal temperatureswith mater

3 Regulations EN 15004-9: Extinguishing systems using gaseous agents: physical properties and design systems using IG-55. EN 15004-1: Extinguishing systems using gaseous agents: design, installation and maintenance. NFPA 2001: Fire extinguishing systems using clean agents. Storage 300 BAR PRESSURISED CYLINDERS IG-55 LOAD DENSITY CLASS A 0,73 Kg CLASS A+ 0,85 Kg

Tags:

  2010, Nfpa, Nfpa 2001

Information

Domain:

Source:

Link to this page:

Please notify us if you found a problem with this document:

Other abuse

Advertisement

Transcription of IG-55: Inert Gas Fire Suppression System

1 IG-55: Inert GasFire Suppression Systemaguileraextinci nIndexWhat is IG-55 Argonaex? 2 Characteristics and application System 2 Storage, regulations, concentration and valve 3 Inert fire extinguishing at a glance 4 Applications, advantages and qualities of Argonaex 6 Our promise: services and guarantees 81 What isIG-55?IG-55 is a gas made up of a mix of equal parts:50% argon (IG-01) and 50% nitrogen (IG-100).Its components are found naturally in theenvironment, so there is no global warmingeffect and it does not destroy the ozone density is similar to that of air and bothargon and nitrogen are clean, non-corrosive,colourless and insipid gases, so they offer greatflexibility in adapting to all actuation systems,since they can be used at normal temperatureswith materials such as nickel, steel, stainlesssteel, copper, bronze, tin, is stored like a compressed gas in high-pressure cylinders.

2 Which is why the spacerequired for its storage will depend on itspressure and IG-55 System is designed for a pressure of300 bar, which enables us to achieve greatspace propertiesApplication systemTotal floodingStorage is a cylinder or cylinders rack of the required extinguishingagent in order to, by discharging into the space, achieve theextinguishing concentration required for this kind of fire. Thecylinder or cylinders rack is connected to a network of distributionpipes and to a series of discharge and gasification diffusers thatdistribute the extinguishing agent inside the space to Class A: Solid fuel fires, such as wood, plastic, electric current is cut after A+: Solid fuel fires with an electrical risk.

3 The current is not cut after Class B: Superficial fires that are caused in flammableliquid name: Nitrogen / ArgonChemical formula:N2/ArN250% volumeAr50% volumeMolecular Point at bar: -196 CCritical temperature-Critical pressure-Maximum fill pressure: 300 barNOAEL43%LOAEL52%Power to destroy ozone: 0 Potential global warming effect:0 Toxicity: NOVision difficulties due to discharge: NOMaximum discharge time for class A: 120 secondsMaximum discharge time for class B: 60 secondsHow is itactuated?The extinguishing principle of Inert gasesfocuses on reducing oxygen concentration inthe affected a fire starts, IG-55 rapidly penetrates thearea and reduces the oxygen level percentagefrom the usual level of 21% to a limit thatfluctuates between 13% and 11%, the amountsufficient for combustion to stop and to be safefor the people in the room.

4 Thanks to thestratification of the gases (due to their density,argon rises and nitrogen falls) protection isachieved throughout the space, regardless ofhow high the ceiling its discharge, there is excellent visibilityand, since it leaves no residue, there are nodestructive effects to the equipment, whichwill continue functioning normally and, ofcourse, there will be nothing to clean 15004-9: Extinguishing systems using gaseous agents: physical properties and design systems using 15004-1: Extinguishing systems using gaseous agents: design, installation and 2001: Fire extinguishing systems using clean BAR PRESSURISED CYLINDERSIG-55 LOAD DENSITYCLASS A0,73 KgCLASS A+0,85 KgCLASS B0,91 KgCYLINDER CAPACITYKgm380 L32,122,77120 L48,234,15140 L56,239,84 SAFETY MARGINNELNOAELLELLOAEL12%43%Concentratio n of oxygen designed for Inert gases 12%from 10 to 12% from 8 to 10%under 8%Occupation of normal areasPERMITTEDPERMITTED NOT PERMITTED NOT PERMITTEDE xposure time limit5 minutes3 minutes 30 seconds 0 Valve with regulated output pressureTable of exposure times in accordance with EN 15004-1 and nfpa 2001.

5 The valve permits constant regulation of pressure, so the gas is discharged in a controlled manner and at a maximum of 60 pneumatic discharge control permits rational use, in accordance with the needs of the facility, maintaining a constant release of the agent withminimum inlet pressure: 370 outlet pressure: 60 O CONCENTRATIONCLASS ACLASS B40,3% 45,2%47,60%CLASS A+10%52%Pressure (Bar)Time (Seconds)0102030405060708030025020015010 0500 Cylinder pressureOutlet pressureCONSTANT PRESSURE REGULATIONI nert fire suppressionAutonomous CylindersCylinders Rack4 High-pressure autonomous cylinders manufactured in seamless thermallytreated alloy steel, in accordance with instruction MIE AP7 for pressurisedmachines and European Directive 84/525 in three sizes: 80, 120 and :1.

6 Cylinder2. Valve for inerts3. Pressure gauge with presostat 300 bar4. Electric actuator5. Manual actuator6. Pressure regulator7. FittingsHigh-pressure 80, 120 and 140L cylinders rack manufactured in seamlessthermally treated alloy steel, in accordance with instruction MIE AP7 forpressurised machines and European Directive 84/525 racks comprise slave cylinders and a pilot cylinder, except in the case ofsystems with directional valves, where all the cylinders will be slaves and areequipped with a separate small pilot cylinder of cylinders racks can be grouped into: Single row Double row Triple rowComponents:1.

7 Cylinder2. DN12 valve for inerts3. Pressure gauge with presostat 300 bar4. Inert valve electric actuator5. Manual actuator6. Pressure regulator7. Trip user chord8. Pneumatic actuator9. Relief valve10. Inert collector support11. Collector12. U-bolt13. Rear cross-bar14. Cylinder arc fitting15. Discharge user chord16. Non-return valve17. Contactor71235461234567891516171314115 Types of CylindersFinal slave cylinderIntermediate slave cylinderPilot cylinderSlave cylinder in systemswith directionalsSmall nitrogen pilot cylinderComponents:1. 3/4" discharge user chord2. Pressure regulator3. 1/8" joint4. 1/8" trip user chord5.

8 Electric actuatorSmall pilot cylinder components:1. Copper piping2. Valve for inerts3. Cylinder4. Electric actuator5. Manual actuator6. Pressure gauge with presostat7. Small pilot cylinder adaptor8. Metal joint9. 1/8" adaptor10. 1/8" tubing joint to 6 bicone6. Manual actuator7. Pneumatic actuator8. Relief valve9. 1/8" sleeve10. 1/8" male adaptor to 6 bicone11. 6x1 copper piping12. 1/4" female adaptor to 6 bicone13. 3/4" male reducer adaptor 1/4" male14. 3/4" female adaptor 3/4" female6 AdvantagesApplicationsPetrochemicalinsta llationsData centres andelectric boxesMuseums andart galleriesChemicalindustryHospitalsPowerg enerators Clean extinguishing.

9 Leaves NO for occupied not affect global impact on the ozone ODP and ZERO GWPARGONAEX (IG-55) has zero Ozone Depletion Potential (ODP) and zero GlobalWarming Potential (GWP), since it is made up of nitrogen and argon, insert gasesnaturally present in our (IG-55) contains no carbon dioxide (CO2) or halocarbons. There is no chance of toxicdecomposition gases being produced, even in contact with heat or a REFILL COSTARGONAEX (IG-55) is made up of a mix of 50% nitrogen and argon, easily availablefor industrial WITH REGULATED PRESSURE CONTROLThe valve and cylinder set are provided with apatented constant pressure regulation System .

10 TheARGONAEX (IG-55) extinguishing System stored at300 bar or 200 bar in the cylinder, discharges in acontrolled manner at a maximum of 60 bar. Thisenables the use of lower pressure piping VISIONThe discharge of ARGONAEX (IG-55) cases novisibility problems for occupants to proceed toevacuate the space, produces no condensation inthe air as a result of the discharge of the (IG-55) can be used toprotect spaces with precisioncomponents, works of art, items of valueand electronic equipment, since it leavesno residue after being SYSTEMSARGONAEX (IG-55) systems can be designed to protectseveral zones through the installation of directional commitment.


Related search queries