Installation & Service Instructions Kingfisher Mf 40 …

Installation & Service Instructions Kingfisher Mf 40 100 About the BoilerSee inside cover for models covered by these Floor Mounted Fan Assisted Gas Boiler is available as Conventional or Balanced boiler is for use with Natural Gas (G20) Only at 20mbar and for use in GB & SafetyThe Gas Safety ( Installation and Use) Regulations 1994 (As Amended) & The Gas Safety( Installation and Use) (Amendment) Regulations 1996. In your own interest, and that of safety, it is law that all gas appliances are installed bycompetent persons, in accordance with the above regulations. Failure to install appliancescorrectly could lead to prosecution.

Installation & Service Instructions Kingfisher Mf 40 – 100 About the Boiler See inside cover for models covered by these instructions. This Floor Mounted Fan Assisted Gas Boiler is available as Conventional or Balanced Flue.

Tags:

  Services, Installation, Instructions, Kingfisher, Installation amp service instructions kingfisher mf

Information

Domain:

Source:

Link to this page:

Please notify us if you found a problem with this document:

Other abuse

Transcription of Installation & Service Instructions Kingfisher Mf 40 …

1 Installation & Service Instructions Kingfisher Mf 40 100 About the BoilerSee inside cover for models covered by these Floor Mounted Fan Assisted Gas Boiler is available as Conventional or Balanced boiler is for use with Natural Gas (G20) Only at 20mbar and for use in GB & SafetyThe Gas Safety ( Installation and Use) Regulations 1994 (As Amended) & The Gas Safety( Installation and Use) (Amendment) Regulations 1996. In your own interest, and that of safety, it is law that all gas appliances are installed bycompetent persons, in accordance with the above regulations. Failure to install appliancescorrectly could lead to prosecution.

2 Installation must be in accordance with the Installation & Service Instructions and the rules these Instructions with the user for use on future ContentsPublication No. 560100 Contents - Page 2 Technical & Safety of of Supply - Systems - the the the Gas the Water the Power Supply the Optional models covered by these Instructions are:- Kingfisher Mf CF40 - No. 41 589 02 Kingfisher Mf CF50 - No. 41 589 03 Kingfisher Mf CF60 - No. 41 589 04 Kingfisher Mf CF70 - No. 41 589 09 Kingfisher Mf CF80 - No. 41 589 10 Kingfisher Mf CF90 - No. 41 589 11 Kingfisher Mf CF100 - No. 41 589 12 Kingfisher Mf RS40 - No.

3 41 393 88 Kingfisher Mf RS50 - No. 41 393 95 Kingfisher Mf RS60 - No. 41 393 96 Kingfisher Mf RS70 - No. 41 393 97 Kingfisher Mf RS80 - No. 41 393 98 Kingfisher Mf RS90 - No. 41 393 99 Kingfisher Mf RS100 - No. 41 589 the the the & Replacement of Control Pressure , Gas Valve, Injector & Chamber & Flue Discharge Safety Device- TTB (CF Models Only)..28 The boiler model and serial number are given on theboiler data label which is located on the heatexchanger cover List of , PERFORMANCE & QUALITYK ingfisher Mf boilers have been assessed by aGovernment appointed Notified Body and shown tomeet the 'Essential Requirements' of the European GasAppliance Directive lays down requirements for the safety andefficiency of the appliance, together with its design,construction, and use of also requires the production process to be covered byan approved and monitored system of No.

4 56010 Technical Data 3 Technical Data - Page 3 Boiler modelsHeat Input & Efficiency figuresare quoted as gross405060708090100 Maximum ,00050,00060,00070,00080,00090,000100, ,98662,47475,06487,34799,972112,528125,4 25 Gas ratem ,00040,00050,00060,00070,00080,00090, ,38550,73663,49775,47388,132101,149114,0 63 Gas ratem Working (3 bar)Minimum Working Head300mmMinimum Circulating Head - Supply Pressure20mbarGas Supply ConnectionRc. ( in BSP Female)Maximum Flow Temperature82 CFlow Connection28mm CopperReturn Connections - Gravity28mm CopperReturn Connections - Pumped28mm CopperWater litresAppliance Weight Installed - kg RS Model / kg CF ModelElectricity Supply230v ~ 50Hz Fused at 3 AInternal FuseType 2 AT (2 off)Power Consumption80 Watts (excluding pump)ClassificationsCAT 1 HB12BS, C12, C32 (40 - 70) IP20 NOx Class 1 - 40, 50, 60, 80, 90 & 100 modelsNOx Class 2 - 70 model4 Technical DataPublication No.

5 560100 Technical Data - Page 4 Fig 2 Introduction 5 The Gas Safety ( Installation and Use) Regulations 1994(As Amended) & The Gas Safety ( Installation and Use)This appliance must be installed and serviced by acompetent person, in accordance with the the UK 'Corgi' Registered Installers (including the regionsof British Gas Plc) undertake to work to a safe andsatisfactory to install appliances correctly could lead is in your own interest, and that of safety, to ensure thatthe regulations are complied Mf boilers are fully automatically controlled, floorstanding, fan powered, balanced or conventional fluedappliances using a cast iron heat exchanger and areavailable in outputs ranging from - kW (40,000 -100,000 Btu/h)The boilers are designed for use on fully pumped openvented or sealed water systems with an indirect hot watercylinder or open vented gravity systems.

6 THEY MUST NOTBE CONNECTED TO A DIRECT boilers are for use on Natural Gas (G20) of the Potterton Kingfisher MF gas boilers havebeen examined by British Gas Plc, a United KingdomNotified Body. The range is certified to comply with theessential requirements of the Gas Appliance Directive90/396/EEC, the Low Voltage Directive 72/23/EEC andshows compliance with the Electro Magnetic CompatibilityDirective 89/336/EEC and are therefore permitted to carrythe CE & Kits AvailableRS Model is delivered in two packages (1) the boiler withfittings and (2) the flue Model is delivered in one and Safety Information for theInstaller and Service EngineerUnder the Consumer Protection Act 1987 and Section 6 ofthe Health and Safety at Work Act 1974, we are required toprovide information on substances hazardous to quantities of adhesives and sealants used in theproduct are cured and present no known following substances are also and SealsMaterial - Man Made Mineral - Boards, Ropes, Hazards - Some people can suffer reddeningand itching of the skin.

7 Fibre entry into the eye willcause foreign body irritation which can cause severeirritation to people wearing contact lenses. Irritation torespiratory - Dust goggles will protect eyes. Peoplewith a history of skin complaints may be particularlysusceptible to irritation. High dust levels are only likelyto arise following harsh general, normalhandling and use will not present high risk, follow goodhygiene practices, wash hands before, touching eyes,consuming food, drinking or using the Aid - Medical attention must be sought followingeye contact or prolonged reddening of the of PracticeThe boiler must be installed in accordance with: The GasSafety ( Installation and Use) Regulations 1994 (AsAmended) & The Gas Safety ( Installation and Use)(Amendment) Regulations 1996.

8 And the current issue of:-The Building Regulations, Building Standards (Scotland)Regulations, Local Building Regulations, Model and localWater Undertaking Bye-laws, IEE Wiring Regulations andHealth & Safety Document No. 635 "The Electricity at WorkRegulations 1989".IMPORTANTThis appliance has been certified for safety. It is therefore important that no external control device ( fluedampers, economisers, etc.) be directly connected to the appliance unless covered by these Installation & ServiceInstructions or otherwise recommended in writing. Any direct connection of a control device not approved byPotterton Myson Ltd, could invalidate the CE Certification and normal appliance Installation Requirements Publication No.

9 560100 Installation Requirements - Page SupplyThe meter and supply pipes must be capable of deliveringthis quantity of gas in addition to the demand from anyother appliances in the house and must be governed at 90 & 100 models, due to the gas flow rate required,22mm gas supply pipe should be used up to the inletconnection of the gas cock on the complete Installation must be tested for gas soundnessand purged as described in Supply230V ~ 50Hz via a fused double pole switch with a contactseparation of at least 3 mm in both poles adjacent to theboiler. Power consumption is approximately 80W. Theremust be only one common isolator for the boiler and itscontrol system and it must provide complete electricalisolation.

10 A plug (if fitted) must be accessible to the userafter Installation of the the supply at 3 A. The minimum requirement for thepower supply cable is that it should be a PVC sheathedcord at least mm (24 x mm) (code designationHO5 VV-F or HO5 VVH2-F) as specified in table 16 ofBS6500 wiring external to the boiler shall comply with the latestIEE Wiring Regulations, and any local regulations : THIS APPLIANCE MUST BE the event of an electrical fault after Installation of theboiler, preliminary electrical systems checks must becarried out Earth Continuity, Short Circuit, Polarity andResistance to of BoilerThe boiler is not suitable for external Installation .