INSTALLATION GUIDEInBio Pro Series Access Control PanelsDate: June, 2016 Version: Pro Series Access Control Panels INSTALLATION GUIDEWhat s in the Box4 Diode2 Screws & Anchors 2 Screwdriver3 InBio Pro Series Access Control Panels INSTALLATION GUIDECONTENTC ontentsWhat s in the Box ..2 Optional accessories ..4 Safety PIN Diagram ..6 LED Indicators ..7 Product Dimension ..8 INSTALLATION of Panel & Cabinet ..9 Wiring Legend ..10 Power Wiring Diagram ..11 Without Backup Battery ..11 With Backup Battery ..11RS485 Fingerprint Reader Switch Setting for RS485 Reader ..13 Wiegand Connection ..14 REX Connections.

such as magnet, CRT, TV, monitor or speaker may damage the device. Do not place the device next to heating equipment. Be careful not to let liquid like water, drinks or chemicals leak inside the device. Do not let children touch the device without supervision. Do not drop or damage the device. Do not disassemble, repair or alter the device.

Tags:

  Repair

Information

Domain:

Source:

Link to this page:

Please notify us if you found a problem with this document:

Other abuse

Transcription of INSTALLATION GUIDE - ZKTeco Hong Kong

1 INSTALLATION GUIDEInBio Pro Series Access Control PanelsDate: June, 2016 Version: Pro Series Access Control Panels INSTALLATION GUIDEWhat s in the Box4 Diode2 Screws & Anchors 2 Screwdriver3 InBio Pro Series Access Control Panels INSTALLATION GUIDECONTENTC ontentsWhat s in the Box ..2 Optional accessories ..4 Safety PIN Diagram ..6 LED Indicators ..7 Product Dimension ..8 INSTALLATION of Panel & Cabinet ..9 Wiring Legend ..10 Power Wiring Diagram ..11 Without Backup Battery ..11 With Backup Battery ..11RS485 Fingerprint Reader Switch Setting for RS485 Reader ..13 Wiegand Connection ..14 REX Connections.

2 15 Lock Connection ..16 Connecting a Lock with External to Power Supply ..16 Switching Dry Contact to Wet Contact ..17 Lock Connection ..18 Normally Open Lock Powered From Lock Terminal ..18 Normally Closed Lock Powered From Lock Terminal ..18 Aux. I/O Connection ..19 Aux. Input Connection ..19 Aux. Output Connection ..19 Ethernet Connection ..20 LAN Connection ..20 Direct connection ..20 Restore Factory Setting ..21 INSTALLATION Diagram ..22 ZKpanelWeb ..23 Troubleshooting ..29 Electrical Specifications ..30 Specifications ..31 ZKBioSecurity Software 4 InBio Pro Series Access Control Panels INSTALLATION GUIDEO ptional accessoriesWiegand Card ReaderZK4500 Enrollment readerRS485 Fingerprint ReaderProx CardCR20E Card EnrollerK2 Exit ButtonInBio Pro Cabinet5 InBio Pro Series Access Control Panels INSTALLATION GUIDES afety PrecautionsThe following precautions are to keep user s safe and prevent any damage.

3 Please read carefully before not install the device in a place subject to direct sun light, humidity, dust or not place a magnet near the product. Magnetic objects such as magnet, CRT, TV, monitor or speaker may damage the not place the device next to heating careful not to let liquid like water, drinks or chemicals leak inside the not let children touch the device without not drop or damage the not disassemble, repair or alter the not use the device for any other purpose than the device often to remove dust on it. In cleaning, do not splash water on the device but wipe it out with smooth cloth or your supplier in case of a Pro Series Access Control Panels INSTALLATION GUIDEP roduct PIN Diagram4 Aux Inputs State Indicator#1 Door Card Reader#1 Door Exit ButtonRS485 Fingerprint Reader#2 Door Card Reader#2 Door Exit Button#3 Door Card Reader#3 Door Exit Button#4 Door Card Reader#4 Door Exit Button4 Lock & Door Sensor4 Aux OutputDIP SwitchesEthernet PortLock PowerInBio Pro PowerLINK LEDACT LEDSD Card SlotFigure 17 InBio Pro Series Access Control Panels INSTALLATION GUIDELED Indicators LINK Solid Green LED indicates TCP/IP

4 Communication is normal. Flashing (ACT )Yellow LED indicates data communication is in progress. EXT RS485 (TX/RX) Flashing Yellow & Green LED indicates communication is in progress. Flashing (POWER) Red LED indicates the panel is powered on. Flashing (RUN) Green LED indicates that panel is in normal working state. Flashing (CARD) Yellow LED indicates that the card is read by the 2 Figure 3 Figure 4 Figure 5 Figure 7 Figure 68 InBio Pro Series Access Control Panels INSTALLATION GUIDEP roduct DimensionFigure 9 InBio160 ProInBio260 ProInBio460 ProInBio Pro- Metal CabinetFigure in (226 mm) in (181 mm) in (36 mm) in (106 mm) in (106 mm) in (106 mm) in (400 mm)13 in (330 mm) in ( mm)9 InBio Pro Series Access Control Panels INSTALLATION GUIDEI nstallation of Panel & CabinetCable Conduit(Punch Hole for cables)

5 Temper SwitchInBio Pro Panel Heat Dissipation GrillPower SupplyBackup BatteryMounting HolesState IndicatorsInserting Panel to RailMounting RailWe recommend drilling the mounting plate screws into solid wood ( stud/beam). If a stud/beam cannot be found, then use the supplied drywall plastic mollies (anchors).Step 1 Pass the cable through holes Step 2 Mount the Metal Cabinet Step 3 Insert the InBio Pro Panel as it shownFigure 10 Figure 11 1210 InBio Pro Series Access Control Panels INSTALLATION GUIDEW iring LegendDetectorEthernet CableIR SensorExit ButtonFloodlightWiegand Card ReaderExit ButtonNormally Open LockNormally Close LockWiegand Card Reader12V DC Power Supply12V DC PowerFigure 1211 InBio Pro Series Access Control Panels INSTALLATION GUIDEP ower Wiring Diagram Without Backup Battery With Backup BatterySwitching Power SupplyGroundGroundSwitching

6 Power SupplyFigure 14 Figure 1312 InBio Pro Series Access Control Panels INSTALLATION GUIDERS485 Fingerprint Reader Connection12V DC12V DCETHERNET 1 2 3 8 RS485 Fingerprint ReaderFigure 1513 InBio Pro Series Access Control Panels INSTALLATION GUIDEDIP Switch Setting for RS485 ReaderDIP SwitchFigure 16RS485 Terminal Resistance8421 AddressSwitch SettingsAddressSwitch Settings15263748 Important Notes1. There are six DIP switches on the back of RS485 fingerprint reader, Switches 1-4 is for RS485 address, switch 5 is reserved, switch 6 is for reducing noise on long RS485 Set the odd number for IN reader, and the even number for OUT reader (for eg.)

7 For two readers for one door- the RS485 address 1 is for IN reader, RS485 address 2 is for OUT reader)3. If RS485 fingerprint reader is pow-ered from InBio460 Pro panel ,the length of wire should be less than 100 meters or 330 The External RS485 interface can supply maximum 500mA current, The RS485 fingerprint reader s startup current is 240mA. So InBio-460 Pro only can power two RS485 fingerprint If the cable length is more than 200 meters or 600 ft , the number 6 switch should be ON as below:Distance: More than 200 meters14 InBio Pro Series Access Control Panels INSTALLATION GUIDEW iegand ConnectionWiegand Card ReaderFigure 17 BeeperGreen LEDW iegand D1 Wiegand D0 GNDDC+(6-14V )15 InBio Pro Series Access Control Panels INSTALLATION GUIDEREX ConnectionsZK ABK Exit ButtonK2 Exit SwitchSeparate Power SupplyUnusedNOBUTTONCOMGND12V DC(+)12V DC( - )Figure 1816 InBio Pro Series Access Control Panels INSTALLATION GUIDELock ConnectionConnecting a Lock with External to Power Supply (Dry Contact)

8 FR107 DiodeGNDGNDS ensorSensor12V DCDoor ContactETHERNETF igure 19-+17 InBio Pro Series Access Control Panels INSTALLATION GUIDE Switching Dry Contact to Wet ContactImportant Notes:The factory default jumper setting is set as dry mode. If you want to power the lock from the panel, you must take the following steps:1. Take apart the cover of InBio460 Pro. Push the tab inward (see figure 21)2. Select the appropriate lock relay and find its jumpers3. Take off the jumpers and change to 4. Connect the lock as show in the diagram, (see figure 23 and 24)Back of InBio460 ProSelect one RelayDefault setting1, 2 - 3, 4 Take off jumpersJumpersPlug Jumpers2, 3 - 4, 5 Figure 21 Figure 2018 InBio Pro Series Access Control Panels INSTALLATION GUIDELock Connection Normally Open Lock Powered From Lock Terminal (Wet Contact) Normally Closed Lock Powered From Lock Terminal (Wet Contact)

9 12V DC12V DC12V DC12V DCGNDGNDFR107 DiodeFR107 DiodeGNDGNDETHERNETETHERNETF igure 22 Figure 2316 or 18 AWG shielded cable recommended-+-+19 InBio Pro Series Access Control Panels INSTALLATION GUIDEAux. I/O Connection Aux. Input Connection Aux. Output Connection12V DC12V DCGNDGNDETHERNETF igure 25 Figure 24 ETHERNETUSBUSBUSBUSB Direct connectionTo connect InBio Pro Panel with a PC directly, connect both devices with a straight network cable. As the InBio Pro Panel supports auto MDI/MDIX, it is not necessary to use a crossover type Card IssuerZK4500 Enrollment readerZK4500 Enrollment readerCR20E Card IssuerETHERNETETHERNET20 InBio Pro Series Access Control Panels INSTALLATION GUIDEE thernet Connection LAN ConnectionImportant Notes: 1.

10 Both 10 Base-T and 100 Base-T are supported2. This cable distance must be less than 330 ft. (100m)3. For cable length of more than 330 ft. (100m). use HUB to amplify the 26 Figure 27 CAT5e or CAT6 ethernet cable recommended21 InBio Pro Series Access Control Panels INSTALLATION GUIDER estore Factory SettingRestore Factory Setting Restore factory setting1. If you forget the IP address of the InBio Pro panel or the device does not work normally, you can use the number 7 DIP switch to restore InBio Pro Panel to factory default settings. The parameters which gets reset are device IP address, communication password, gateway, and subnet The switch is OFF by default.