Transcription of INSTALLATION, OPERATING and SERVICE MANUAL
1 installation , OPERATINGandSERVICE MANUALTHE installation OF THE UNIT SHALL BE IN ACCORDANCE WITH THEREGULATIONS OF THE AUTHORITIES HAVING BOILERMODEL: NBR-2001 NBR-2002 HEAD OFFICEMARKETING / PRODUCTIONN ewmac Mfg. AIR INDUSTRIAL PARK,LANCASTER BOX 9, DEBERTNOVA SCOTIA, BOM 1G0 PHONE: 902-662-3840 FAX:902-662-2581 WAREHOUSEN ewmac Mfg. SPRINGBANK AVE., BOX 545 WOODSTOCK, ONTARION4S 7Y5 PHONE: 519-539-6147 FAX:519-539-0048 EMAIL: TO HOMEOWNER:READ THESE INSTRUCTIONSSAVE THESE INSTRUCTIONS2210150 REVISED APRIL 2007 Printed: _____Subject to change without notice1 NBR 2001 / NBR 2002 GENERAL INSTRUCTIONSIt is the responsibility of the consignee of the unit to examine the package for damage and, if found to note the same on theCarrier s Bill of LadingThe boiler is shipped in three (3) **packages:1.
2 Boiler complete with casing. Domestic hot water coil is burner **complete with primary relay, photo-cell, and Standard control package complete with pressure relief valve; aquastat relay drain valve; tridicator;flexible oil line; burner wiring cable; lockout switch wiring cable; aquastat wiring cable; pipe fittings and instruction barometric draft regulator may be included in the control package, but is not used on a Newmac Sealed Vent control package is cartooned and shipped inside the boiler crate*Install Beckett Low Firing Rate Baffle (3708) on AFG70 MDSS. Danfoss AS Nozzle with AFG70 MBSS Burner Nomenclature: NBR denotes NBR-2001. Model numbers suffixed with V are approved for Newmac Sealed Vent denotes NBR-2002.
3 Modelnumbers suffixed with V are approved for Newmac Sealed Vent System.** Riello 40 F3 & 40 F5 burners may have air tube in separate air settings as a guide only. Set burner air to give a trace of smoke. Re-adjust burner air to reduce CO2reading by 1 to measurements with the burner cover & air ducts installed (if any).See burner manufacturer s instructions for more information. If settings differ, use those on the appliance (USGPH)AFUE% NBR-90 VNBR2-90 VBF390,000100,368 ( ) X 60 X 60 ES1453-1/4 ,000108,732 ( )85 . X 60 X 60 ES1453-1/4 25320 NBR-111 VNBR2-111 VBF3111,000125,460 ( ) X 60 X 60 ES1453-1/4 37375 NBR-90 VNBR2-90 VBF590,000100,368 ( ) X 60 X 60 ES1453-1/4 ,000108,732 ( ) X 60 X 60 ES1453-1/4 ,000125,460 ( ) X 60 X 60 ES1453-1/4 ,000142,188 ( ) X 60 X 60 ES1453-1/4 ,000167,280 ( ) X 60 X 60 ES1453-1/4 ,000184,008( ) X 60 X 60 ES1453-1/4 ,000210,494 ( ) X 60 X 60 ES1453-1/4 F391,000101,762 ( ) X 60 X 60 ES1503-1/4 F3100,000111,520 ( ) X 60 X 60 ES1503-1/4 F3113,000128,248 ( ) X 60 X 60 ES1503-1/4 3380 NBR-127 NBR2-12740 F3127,000144,976 ( ) X 60 X 60 ES1503-1/4 F591,000101,762 ( ) X 60 X 60 ES1503-1/4 F5100,000111,520 ( )
4 X 60 X 60 ES1503-1/4 F5113,000128,248 ( ) X 60 X 60 ES1503-1/4 F5127,000144,976 ( ) X 60 X 60 ES1503-1/4 F5145,000170,068 ( ) X 60 X 60 ES1503-1/4 F5160,000188,190 ( ) X 60 X 60ES1503-1/4 F5179,000213,282 ( ) X 60 X 60 ES1503-1/4 2001 / NBR 2002 GENERAL INSTRUCTIONS*Install Beckett Low Firing Rate Baffle (3708) on AFG70 MDSS. DanfossAS Nozzle with AFG70 MBSS Burner Nomenclature: NBR denotes NBR-2001. Model numbers suffixed with V are approved for Newmac Sealed Vent denotes NBR-2002. Model numbers suffixed with V are approved for Newmac Sealed air settings as a guide only. Set burner air to give a trace of smoke. Re-adjust burner air to reduce CO2reading by 1 to measurements with the burner cover & air ducts installed (if any).
5 See burner manufacturer s instructions for more information. If settings differ, use those on the appliance (USGPH)AFUE% SHUTTERSETTINGAIR BANDSETTINGDESIGNGROSSSTACKF NBR-96 VNBR2-96 VAFG70 MBSSAFG70 MDSS*96,000107,338 ( ) X 60 X 60 X 60AS 1404-1/2 *110,000124,066 ( ) X 60 X 60 X 60AS 1404-1/2 ,000140,794 ( ) X 60 X 60 X 60AS 1404-1/2 ,000164,492 ( ) X 45 X 45 X 45 AS1404-1/2 ,000184,008 ( ) X 45 X 45 X 45 AS1754-1/2 ,000203,524 ( ) X 45 X 45 X 45 AS1754-1/2 (USGPH)AFUE% BANDSETTINGDESIGNGROSSSTACKF NBR-120 VNBR2-120 VEZ-1121,000140,794 ( ) X 60 X 60 B1403-1/4 / ,000164,492 ( ) X 60 X 60 B1403-1/4 / 0 NBR-153 VNBR2-153 VEZ-1152,000181,220 ( ) X 60 X 60 B1403-1/4 / ,000206,312 ( )
6 X 60 X 60 B1403-1/4 / (USGPH)AFUE% SETTINGAIR BANDSETTING inches openDESIGNGROSSSTACKF NBR-94 NBR2-94HF-US-2X-593,000104,550 ( ) X 70 B1003-1/4 N/A3/16300 NBR-105 NBR2-105HF-US-2X-5105,000118,490 ( ) X 70 B1003-1/4 N/A1/4320 NBR-119 NBR2-119HF-US-2X-5122,000139,400 ( ) X 70 B1003-1/4 N/A3/8370 NBR-134 NBR2-134HF-US-2X-5134,000153,340 ( ) X 70 B1003-1/4 N/A1/2390 NBR-151 NBR2-151HF-US-2X-5151,000174,250 ( ) X 70 B1003-1/4 N/A3/44303 BOILER INSTALLATIONINSTALLATION REGULATIONSThis unit should be installed in accordance with the regulations of the authority having jurisdiction. InCanada the installation must conform to CSA Standard B139, "The installation Code for Oil BurningEquipment.
7 " In the United States, the National Fire Protection Association Standard NFPA 31 should befollowed. Check with provincial, state, or local codes concerning clearances, venting system requirementsand other regulations governing installation . Some codes may vary from the requirements set forth in ensurethe boiler is on a level foundation and above any possible dampness, a cement pad minimum clearances to combustible construction are as follows:6"Side: 6 Top: 6 Rear: 6 Front: 24"Flue Pipe: 9"Approved Floor Type: CombustibleAllow sufficient room for YOUR SAFETY: Do not store or use gasoline or flammable vapors and liquids in the vicinityof this or any other PRODUCTS OF COMBUSTIONC himneysThe required minimum flue pressure inches of water column.
8 The required minimum overfirepressure inches of water column. Locate the boiler as close to the chimney or flue as maximum draft is obtained by keeping elbows and pipe length to a minimum. Install the flue pipe witha gradual rise of at least 1/4" per foot from the boiler to the flue. Do not extend the flue pipe beyond theinside wall of the chimney. Refer to Table 8 (a) and Table 8 (b) for proper sizing and Figure 19 foroptimizing chimney owner shall provide a chimney constructed to comply with the following specifications:(a) The chimney must be absolutely smoke tight throughout its entire length, and must extend at leastthree feet (3') above a flat roof or two feet above the ridges of peak roofs.
9 (b) If built of a single thickness of brick or of cement blocks, it shall be lined throughout its entire lengthwith fire clay lining, having not less than three-fourths inch (3/4") thickness. Flue lining is to be laid inmortar and made air tight. If the chimney is of the prefabricated type, it must be an approved class "A"chimney or type "L" Vent for interior.(c) The boiler flue must haveno other openings for attaching any fireplace, stove, range, gas or ventilatingconnection unless the equipment is appropriately certified.(d) If it is necessary to offset the flue, it must be done in such a manner as not to reduce the gross cross-sectional area or create a ledge or obstruction, where loose material may lodge.
10 (e) Flue pipe connections must be secured with metal : Oil-fired appliances shall be connected to flues or vents having sufficient draft at alltimes to ensure safeand proper operation of the Draft RegulatorThe Listed/Certified draft regulator must be installed between the appliance and the chimney, within easyreach for adjustment and free from obstruction. Use larger or multiple draft regulators for chimneys withstrong draft. Follow the draft regulator manufacturer's instructions for proper VentingConsult installation codes for requirements and approvals governing power venters and draft the instructions supplied with them for proper Sealed Vent SystemConsult the GENERAL INSTRUCTIONS of this MANUAL for approved burners.