INSTALLATION, OPERATION & MAINTENANCE MANUAL

DVB series . Gas Fired Boilers For Forced Hot Water INSTALLATION, OPERATION &. MAINTENANCE MANUAL . Utica Boilers 2201 Dwyer Avenue . Utica New York 13504 USA. An ISO 9001-2008 Certified Company P/N 37615501, Rev. D [08/2011]. GAS FIRED BOILERS FOR FORCED HOT WATER. 3. Boiler Ratings, Capacities & 4. Ventilation & Combustion Air .. 6. Connecting Supply & Return Piping .. 7. Applicable Federal Codes ..11. Vent System Horizontal Vent Pipe Installation Instructions ..12. Vertical Vent Pipe Installation Connecting Gas Service ..28. Electrical Wiring ..29. Lighting Instructions ..31. Sequence Of General Instruction For Seasonal Startup & Replacement Parts ..37. KEEP THIS MANUAL NEAR BOILER AND. RETAIN FOR FUTURE REFERENCE. IMPORTANT: Read the following instructions COMPLETELY before installing! SAFETY SYMBOLS. The following defined symbols are used throughout this MANUAL to notify the reader of potential hazards of varying risk levels.

DVB SERIES Gas Fired Boilers For Forced Hot Water INSTALLATION, OPERATION & MAINTENANCE MANUAL An ISO 9001-2008 Certified Company P/N 37615501, Rev. D [08/2011]

Tags:

  Manual, Series

Information

Domain:

Source:

Link to this page:

Please notify us if you found a problem with this document:

Other abuse

Advertisement

Transcription of INSTALLATION, OPERATION & MAINTENANCE MANUAL

1 DVB series . Gas Fired Boilers For Forced Hot Water INSTALLATION, OPERATION &. MAINTENANCE MANUAL . Utica Boilers 2201 Dwyer Avenue . Utica New York 13504 USA. An ISO 9001-2008 Certified Company P/N 37615501, Rev. D [08/2011]. GAS FIRED BOILERS FOR FORCED HOT WATER. 3. Boiler Ratings, Capacities & 4. Ventilation & Combustion Air .. 6. Connecting Supply & Return Piping .. 7. Applicable Federal Codes ..11. Vent System Horizontal Vent Pipe Installation Instructions ..12. Vertical Vent Pipe Installation Connecting Gas Service ..28. Electrical Wiring ..29. Lighting Instructions ..31. Sequence Of General Instruction For Seasonal Startup & Replacement Parts ..37. KEEP THIS MANUAL NEAR BOILER AND. RETAIN FOR FUTURE REFERENCE. IMPORTANT: Read the following instructions COMPLETELY before installing! SAFETY SYMBOLS. The following defined symbols are used throughout this MANUAL to notify the reader of potential hazards of varying risk levels.

2 DANGER CAUTION. ! Indicates a hazardous situation which, if ! Indicates a hazardous situation which, if not not avoided, WILL result in death or serious avoided, may result in minor or moderate injury. injury. WARNING NOTICE. ! Indicates a hazardous situation which, if Indicates information which should be not avoided, could result in death or serious followed to ensure proper installation and injury. OPERATION . Certified for H. Tested for 100 psi. ASME. Natural gas or Propane Working Pressure 2. INTRODUCTION. WARNING. 7. Install boiler such that gas ignition system components are protected from water, (dripping, spraying, 1. Keep boiler area clear and free from rain, etc.), during appliance OPERATION and service, combustible materials, gasoline and other (circulator replacement, condensate trap, control flammable vapors and liquids. replacement, etc.). 2. DO NOT obstruct air openings to boiler 8.

3 Requirements for Commonwealth of room. Massachusetts: Boiler installation must conform to Commonwealth of Massachusetts code 248 CMR which 3. Modification, substitution or elimination includes but is not limited to installation by licensed of factory equipped, supplied or specified plumber or gas fitter. components may result in property damage, 9. FOR INSTALLATION ON NON-COMBUSTIBLE. ! personal injury or loss of life. FLOORS ONLY. *Boiler must NOT be installed on 4. To owner: Installation and service of this carpeting. boiler must be performed by qualified installer. 10. Minimum clearances to combustible constructions are: 5. To installer: Leave all instructions with TOP ..18 in. (457mm). boiler for future reference. FRONT ..6 in (152mm). 6. Boiler installation must conform to FLUE CONNECTOR ..6 in (152mm). Commonwealth of Massachusetts code 248 in. (102mm). CMR when installed in Commonwealth of CONTROL in.

4 (229mm). Massachusettes. This includes, but is not OTHER SIDE ..3 in. (76mm). limited to, installation by licensed plumber or gas fitter. VENT PIPE ..6 in. (152mm). NOTICE. Greater clearances for access should WARNING. supersede fire protection clearances. ! Improper installation, adjustment, alteration, * For installation on combustible flooring service or MAINTENANCE can cause injury or Special Base MUST BE USED. (See property damage. Replacement Parts Section). 1. Installation must conform to requirements of authority having jurisdiction or, in absence of such requirements, to the National Fuel Gas Code, ANSI 54. and/or Natural Gas and Propane Installation Code, 2. Where required by the authority having jurisdiction, installation must conform to Standard for Controls and Safety Devices for Automatically Fired Boilers, ANSI/. ASME No. CSD-1. 3. This boiler is classified as Category I and III and vent installation shall be in accordance with latest revision of the National Fuel Gas Code, ANSI or applicable provisions of the local building codes.

5 4. LOCATE BOILER on level, solid base as near outside wall as possible and centrally located with respect to heat distribution system as practicable. 5. Allow 24 inches at front and right side for servicing and cleaning. 6. When installed in utility room, door should be wide enough to allow largest boiler part to enter, or to permit replacement of another appliance such as a water heater. 3. BOILER RATINGS, CAPACITIES & DIMENSIONS. WARNING. All installations of boilers and venting should be done only by a qualified expert and in accordance with ! the appropriate utica boilers MANUAL . Installing or venting a boiler or any other gas appliance with improper methods or materials may result in serious injury or death due to fire or to asphyxiation from poisonous gases such as carbon monoxide which is odorless and invisible. Figure 1 -Boiler Dimensions Table 1- DIMENSIONS FOR NATURAL GAS.

6 Dimensions Pump size Natural Model # Supply &. Gas Inlet A B C D E Return Tappings -50 " 11 2 3 6 27 1 ". -100 " 15 4 3 6 27 1 ". -125 " 19 6 3 6 27 1 ". -150 " 19 6 4 6 27 1 ". -200 " 22 8 4 7 28 1 ". NOTE: For altitudes above 2,000 ft. ratings should be reduced at the rate of 4% for each 1,000 ft. above sea level. 4. BOILER RATINGS, CAPACITIES & DIMENSION. Table 2 - RATINGS AND CAPACITIES. Net I=B=R. Heating No. Water Input Rating AFUE. Model # Capacity of Content Btu/hr Water, Mbh (1) Burners (Gals.). Mbh (1) (2). -50 50,000 42 37 1 -100 100,000 82 71 2 -125 125,000 103 90 3 -150 150,000 122 1060 3 -200 199,999 160 139 4 (1). Mbh = 1000 Btu per hour (2). Net I=B=R Water Ratings shown based on piping and pickup allowance of Contact manufacturer before selecting boiler for installations having unusual piping and pickup requirements, such as intermittent system OPERATION , extensive piping systems, etc.

7 STANDARD EQUIPMENT: Boiler Jacket, Cast Iron Boiler Battery, Combination Aquastat Relay, Theraltimeter Gauge, Circulator, Main Gas Burners, Electric Ignition System, relief Valve, Drain Valve, Induced Draft Fan, and Safety Pressure Switch All boilers are design certified for installation on non-combustible floors. For installation on combustible floors, use combustible floor kit. Boiler is Category III Designed Certified appliance which requires a special horizontal through the wall venting system. Only HEAT-FAB SAF-T-VENT , FLEX-L STAR-34 , ProTech FasNSeal, and Z-FLEX Z-VENT vent material products shall be used. Electric service to be 120 Volts, 15 Amps, 60 Hz. 5. VENTILATION & COMBUSTION AIR. Provide combustion air and ventilation air in accordance All Outdoor Air. Provide permanent opening(s). with the section Air for Combustion and Ventilation, of the communicating directly or by ducts with outdoors.

8 National Fuel Gas Code, ANSI 54, or Sections о Two Permanent Opening Method. Provide opening , or of Natural Gas and Propane Installation commencing within 12 inches of top and second Code, CAN/CSA , or applicable provisions of local opening commencing within 12 inches of bottom building codes. enclosure. Provide make-up air where exhaust fans, clothes dryers, Direct communication with outdoors or and kitchen ventilation equipment interfere with proper communicating through vertical ducts. Provide OPERATION . minimum free area of 1 in2 per 4 Mbh of total input rating of all appliances in enclosure. National Fuel Gas Code recognizes several methods Communicating through horizontal ducts. of obtaining adequate ventilation and combustion air. Provide minimum free area of 1 in2 per 2. Requirements of the authority having jurisdiction may Mbh of total input rating of all appliances in override these methods.

9 Enclosure. Engineered Installations. Must be approved by о One Permanent Opening Method. Provide opening authority having jurisdictions. commencing within 12 inches of top of enclosure. Mechanical Air Supply. Provide minimum of Provide minimum clearance of 1 inch on sides cfm per Mbh for all appliances located within space. and back and 6 inches on front of boiler (does not Additional requirements where exhaust fans installed. supersede clearance to combustible materials). Interlock each appliance to mechanical air supply о Combination Indoor and Outdoor Air. Refer to system to prevent main burner OPERATION when National Fuel Gas Code for additional requirements mechanical air supply system not operating. for louvers, grilles, screens and air ducts. All Indoor Air. Calculate minimum volume for all appliances in space. Use a different method if Combination Indoor and Outdoor Air.

10 Refer to minimum volume not available. National Fuel Gas Code for application information. о Standard Method. Cannot be used if known air National Gas and Propane Installation Code Requires infiltration rate is less than air changes per providing air supply in accordance with: hour. See Table 3 for space with boiler only. Use Section and when combination of appliances equation for multiple appliances. has a total input of up to and including 400 Mbh (120. kW). Volume 50 ft3 x Total Input [Mbh]. о Does not have draft control device. о Known Air Infiltration Rate. See Table 3 for space with boiler only. Use equation for multiple Section when combination of appliances has total appliances. Do not use an air infiltration rate input exceeding 400 Mbh (120 kW). (ACH) greater than Refer to Natural Gas and Propane Installation Code Volume 15 ft3/ACH x Total Input [Mbh] for specific air supply requirements for enclosure о Refer to National Fuel Gas Code for opening or structure where boiler is installed, including air requirements between connection indoor spaces.