installation , Operation, and Maintenance ManualVELTRON DPT 2500-plusMicroprocessor Based Ultra-Low RangePressure & Flow "Smart" TransmitterVersion , Operation & MaintenanceAir Monitor Corporation provides completetechnical support between the hours of7 and 5 PST, M-FContact our Service DepartmentToll Free: 1-800-AIRFLOWor fax us at 1-707-526-2825 Air Monitor (5/5/11) veltron DPT 2500-plus - IO&M Manual veltron DPT 2500-plusAir Monitor (5/5/11) veltron DPT 2500-plus - IO&M ManualTABLE OF CONTENTSTABLE OF CONTENTSINSTRUMENT iSECTION 1 GENERAL DESCRIPTION .. THEORY OF OPERATION .. 1 SECTION 2 PERFORMANCE transmitter .. INDICATION .. OUTPUTS .. 2 SECTION 3 USER SETUP MENU .. transmitter HOLD .. AUTOMATIC DATA DISPLAY .. HIGH TURNDOWN RATIO MULTIPLE OPERATING POWER 4 RECEIVING AND LOCATION .. MOUNTING .. PROCESS POWER/SIGNAL OUTPUT DISPLAY CONTRAST 5 INTRODUCTION .. START-UP .. NORMAL PUSHBUTTON CONFIGURATION transmitter SCALING & LOW PASS AUTO-zero SPAN transmitter INPUT OUTPUT 21 TABLE OF CONTENTSSECTION 6 REQUIRED PREPARATION.

Installation, Operation, and Maintenance Manual VELTRON DPT 2500-plusMicroprocessor Based Ultra-Low Range Pressure & Flow "Smart" Transmitter

Tags:

  Manual, Operations, Installation, Maintenance, Pressure, Transmitter, And maintenance manual, And maintenance manual veltron, Veltron

Information

Domain:

Source:

Link to this page:

Please notify us if you found a problem with this document:

Other abuse

Transcription of Installation, Operation, and Maintenance Manual …

1 installation , Operation, and Maintenance ManualVELTRON DPT 2500-plusMicroprocessor Based Ultra-Low RangePressure & Flow "Smart" TransmitterVersion , Operation & MaintenanceAir Monitor Corporation provides completetechnical support between the hours of7 and 5 PST, M-FContact our Service DepartmentToll Free: 1-800-AIRFLOWor fax us at 1-707-526-2825 Air Monitor (5/5/11) veltron DPT 2500-plus - IO&M Manual veltron DPT 2500-plusAir Monitor (5/5/11) veltron DPT 2500-plus - IO&M ManualTABLE OF CONTENTSTABLE OF CONTENTSINSTRUMENT iSECTION 1 GENERAL DESCRIPTION .. THEORY OF OPERATION .. 1 SECTION 2 PERFORMANCE transmitter .. INDICATION .. OUTPUTS .. 2 SECTION 3 USER SETUP MENU .. transmitter HOLD .. AUTOMATIC DATA DISPLAY .. HIGH TURNDOWN RATIO MULTIPLE OPERATING POWER 4 RECEIVING AND LOCATION .. MOUNTING .. PROCESS POWER/SIGNAL OUTPUT DISPLAY CONTRAST 5 INTRODUCTION .. START-UP .. NORMAL PUSHBUTTON CONFIGURATION transmitter SCALING & LOW PASS AUTO-zero SPAN transmitter INPUT OUTPUT 21 TABLE OF CONTENTSSECTION 6 REQUIRED PREPARATION.

2 transmitter INPUT transmitter OUTPUT 7 28 SECTION 8 29 SECTION 9 PARTS 30 SECTION 10 CUSTOMER 31 TABLE OF CONTENTSVELTRON DPT 2500-plusAir Monitor (5/5/11) veltron DPT 2500-plus - IO&M ManualVELTRON DPT 2500-plusAir Monitor (5/5/11) veltron DPT 2500-plus - IO&M ManualiINSTRUMENT WARRANTYNOTICE OF PROPRIETARY RIGHTSThis document contains confidential technical data, includingtrade secrets and proprietary information which are the soleproperty of Air Monitor Corporation. The use of said data issolely limited to use as specified herein. Any other use is strictlyprohibited without the prior written consent of Air WARRANTYAir Monitor Corporation (hereinafter referred to as Seller )warrants that at the time of shipment, products soldpursuant to this contract will be free from defects inmaterials and workmanship, and will conform to thespecifications furnished or approved in writing by warranty is given that delivered products will conformto catalog sheets, data sheets, and the like, which aresubject to change without will repair or replace, at its option, any productslisted under this warranty which is returned freight prepaidto Seller within the earlier of three (3) years after start-upor thirty-nine (39) months after shipment that, upon testand examination, proves defective within the terms ofthis warranty.

3 The warranty period for any item repairedor replaced shall be for the time remaining on the warrantyperiod of the original components. Purchaser shall notifySeller in writing of such defect within sixty (60) days ofdiscovery of the warranty does not extend to any product sold bySeller which has been the subject of misuse, neglect,accident, damage or malfunction caused byinterconnection with equipment manufactured by others,improper installation or storage, or used in violation ofinstructions furnished by Seller, nor does it extend to anyproduct which has been repaired or altered by personsnot expressly approved by Seller. Nor does Seller warrantequipment against normal deterioration due toenvironment; nor items such as lamps, glass, and similaritems subject to wear or burnout through for items or equipment not manufacturedby Seller shall be made to the extent of any warranty ofthe manufacturer or supplier shall not be liable for any special or consequentialdamages or for loss of damage, directly or indirectlyarising from the use of the products.

4 Seller's warrantyshall be limited to replacement of defective equipmentand shall not include field removal and warranty set forth above is in lieu of all otherwarranties either express or implied and constitutes thefull extent of Air Monitor Corporation's liability to thecustomer, or any other party for breach of ARE NO EXPRESS WARRANTIES EXCEPT ASSET FORTH HEREIN AND THERE ARE NO IMPLIEDWARRANTIES OF MERCHANTABILITY OF FITNESSFOR ANY PARTICULAR PURPOSE, WHICH AREPARTICULARLY DPT 2500-plusAir Monitor (5/5/11) veltron DPT 2500-plus - IO&M Manual1 SECTION 1 GENERAL INFORMATION1 GENERAL DESCRIPTIONThe veltron DPT 2500-plus is an ultra-low differential pressure "smart" transmitter designed to convert the lowmagnitude pressure signals generated by airflow stations and probes, or static pressure sensors into an output signal(4-20mA, 0-5 VDC or 0-10 VDC) linear to pressure or veltron DPT 2500-plus is equipped with numerous standard features: A multi-line LCD used duringconfiguration/calibration and for display of process; AUTO-zero for elimination of transmitter zero error; user selectableprimary signal noise filter, input power isolation; capability of 10:1 flow or 100:1 pressure turndown; and an optionalNEMA 12 enclosure (NEMA 1 is standard).

5 THEORY OF OPERATIONHigh and low pressure signals generated by airflow stations and probes, or static pressure sensors act upon oppositesides of a flexible diaphragm within the transducer. The differential between the two pressure signals displaces thediaphragm; the magnitude of the displacement being measured creates an electrical DC output from the undergoing A/D conversion, the resulting digital signal representing differential pressure or velocity pressurecan be "manipulated" within the microprocessor: square rooted for velocity or flow application; scaled for units ofmeasure and area for process output; and scaled for local data display. The built-in microprocessor runs the programthat provides the following basic functions: Timing, logic, and mathematical operations , analog input signal multiplexing,analog input/output calibration, automatic zeroing valve operation, User Setup menu system, and display (LCD) DPT 2500-plusAir Monitor (5/5/11) veltron DPT 2500-plus - IO&M Manual2 SECTION 2 PERFORMANCE SPECIFICATIONS2 PERFORMANCE TRANSMITTERA ccuracy.

6 Of Natural Span, including hysteresis,deadband, non-linearity, and Differential pressure , flow, and mass SpansBi-Polar Natural Spans0 to IN to IN to IN to IN to IN to IN to IN to IN to IN to IN to IN to IN to IN to IN to IN to IN to IN Rangeability. The calibrated span can be downranged to 40% of the Natural of Natural Span for six None; corrected by of Natural Span/ Position Effect. None; corrected throughtransmitter automatic and Zero Adjustment. Digital, via internallylocated Pass Filtration. Response time to reach 98% ofa step change is adjustable from to and Static pressure Limit. 25 Within of calibrated Every 1 to 24 hours on 1 hour Limits. 20 to 180 F Storage; +40 to140 F Limits. 0-95% RH, INDICATIOND isplay. A backlit, graphical LCD providing single line ofdata display. Also used for OUTPUTSA nalog Output. Single output linear to pressure , flow,or massflow configurable via jumper to 0-5V , 0-10V, POWERP ower Supply.

7 Standard 24 VAC (16-30 VAC) or 24 VDC(16-40 VDC).Power Consumption. Standard: 8VA at 24 VAC; 6 VAat Protection. Power input is isolated, fused, andreverse polarity DPT 2500-plusAir Monitor (5/5/11) veltron DPT 2500-plus - IO&M Manual3 SECTION 3 FEATURES3 USER SETUP MENUThe microprocessor program contains a User Setup menu system for setting user selectable parameters. Fourpushbuttons, allow the user access to the menu for setting configuration modes and values. Referto the Configuration Programming (Section ) instructions for operation details. Also contained in the User Setupmenu is all input and output calibration. The calibration method is completely digital and contains no analogpotentiometer adjustments which are susceptible to drift. Non-volatile memory is used for storing all setup parametersand calibration values, and will remain unchanged after set, even when power to the unit is transmitter HOLDC ertain operations performed by the microprocessor place the unit into a Hold mode.

8 This occurs when the UserSetup menu system is activated or when an AUTO-zero is performed. When in Hold, all Normal mode processing ishalted and the output is held at its last value prior to Hold. Normal operation is indicated by the "CPU Activated" (dot) in the lower left of the display blinking at a rate of four times per second. A Hold mode is indicated by the "CPUA ctivated" (dot) blinking at a rate of once per AUTOMATIC ZEROINGAt periodic intervals the microprocessor will automatically execute an AUTO-zero cycle consisting of the followingsequence: The transmitter output and display signals are put onHold; a valve is activated which disconnects theprocess high pressure from the high port of the transducer and connects the process static pressure to both sides ofthe transducer, creating a true zero differential pressure ; after a brief stabilization period, the transducer zero offsetsignal is measured and stored in memory; the valve is deactivated and after a brief period for process signal stabilization,the Hold is released and Normal process measurement resumes.

9 Will be displayed whenever AUTO-zero cycle is in Normal operation, the zero offset value stored in memory is subtracted from subsequent transducer readingsuntil the next AUTO-zero cycle occurs and repeats the process. For calibration purposes a switch is provided whichallows the user to manually activate the zeroing valve . AUTO-zero On/Off and Interval are available and configurableusing the User Setup DATA DISPLAYThe large integral display is a backlit graphical LCD that displays the current measured process, and is used HIGH TURNDOWN RATIO OPERATIONThe veltron DPT 2500-plus transmitter , with its high level of accuracy and automatic zeroing circuitry, can maintainlinear output signals on applications requiring velocity turndown of 10 to 1 (equal to a velocity pressure turndown of100 to 1). ENCLOSUREThe veltron DPT 2500-plus transmitter is packaged in a NEMA Type 1 enclosure with standard industrial processconnections. A NEMA Type 12 enclosure is optionally MULTIPLE OPERATING POWER SELECTIONSThe veltron DPT 2500-plus can be powered by 24 VAC or zeroXVELTRON DPT 2500-plusAir Monitor (5/5/11) veltron DPT 2500-plus - IO&M Manual44 INSTALLATIONSECTION 4 RECEIVING AND INSPECTION Carefully remove the veltron DPT 2500-plus from the shipping container and inspect for any damage.

10 If anydamage has occurred in transit, contact freight carrier. Save the shipping container for possible future use in returning the veltron DPT 2500-plus to the factory forrecalibration. Review the Factory Set-Up Information Sheet provided with the unit and verify the WO # and Serial # match thoseon the veltron DPT 2500-plus. Verify that the configuration recorded on the Factory Set-Up Information Sheet iscorrect for your application. If not, contact Air Monitor's Customer Service Department at 1-800-AIRFLOW forfurther :The veltron DPT 2500-plus has been configured and calibrated to customer specified parameters (see"Factory Setup Information Sheet" provided with the unit), and requires no additional calibration/verificationprior to LOCATION The standard version of the veltron DPT 2500-plus is a NEMA 1 enclosure suitable for most clean indoorlocations. If additional protection is required, mount unit in an enclosure with adequate NEMA rating. The industrial version of the veltron DPT 2500-plus is housed in a NEMA 12 enclosure (see NEMA ratings fordegree of protection).