Installation, Operation, and Maintenance C-Series Cassette Indoor Units Models: 4 MUC4518A10N0A, 4 MUC4524A10NA, 4 MUC4530A10N0A, 4 MUC4536A10N0A, 4 MUC4542A10N0A, 4 MUC4548A10N0A. SAFETY WARNING. Only qualified personnel should install and service the equipment. The installation, starting up, and servicing of heating, ventilating, and air-conditioning equipment can be hazardous and requires specific knowledge and training. Improperly installed, adjusted or altered equipment by an unqualified person could result in death or serious injury. When working on the equipment, observe all precautions in the literature and on the tags, stickers, and labels that are attached to the equipment. May 2015 MS-SVX039A-EN. DB68-05139A(1). Introduction Read this manual thoroughly before operating or servicing this unit. WARNING. Warnings, Cautions, and Notices Proper Field Wiring and Grounding Safety advisories appear throughout this manual as Required!

Warranty For Trane C-Series Ductless Systems and Related Accessories . . . 31. 4 MS-SVX039A-EN Model Number Description Digit 1: Refrigerant Digit 2: Brand name ... M = Mini-split indoor unit U = Universal match heat pump C = 4-way cassette 4 = Standard model 5 = Flare 18 = 18,000 Btu/h 36 = 36,000 Btu/h

Tags:

  Trane, Split, Ductless

Information

Domain:

Source:

Link to this page:

Please notify us if you found a problem with this document:

Other abuse

Advertisement

Transcription of Installation, Operation, and Maintenance - Trane

1 Installation, Operation, and Maintenance C-Series Cassette Indoor Units Models: 4 MUC4518A10N0A, 4 MUC4524A10NA, 4 MUC4530A10N0A, 4 MUC4536A10N0A, 4 MUC4542A10N0A, 4 MUC4548A10N0A. SAFETY WARNING. Only qualified personnel should install and service the equipment. The installation, starting up, and servicing of heating, ventilating, and air-conditioning equipment can be hazardous and requires specific knowledge and training. Improperly installed, adjusted or altered equipment by an unqualified person could result in death or serious injury. When working on the equipment, observe all precautions in the literature and on the tags, stickers, and labels that are attached to the equipment. May 2015 MS-SVX039A-EN. DB68-05139A(1). Introduction Read this manual thoroughly before operating or servicing this unit. WARNING. Warnings, Cautions, and Notices Proper Field Wiring and Grounding Safety advisories appear throughout this manual as Required!

2 Required. Your personal safety and the proper operation of Failure to follow code could result in death or serious this machine depend upon the strict observance of these injury. All field wiring MUST be performed by qualified precautions. personnel. Improperly installed and grounded field wiring poses FIRE and ELECTROCUTION hazards. To avoid these hazards, you MUST follow requirements for field wiring installation and grounding as described in The three types of advisories are defined as follows: NEC and your local/state electrical codes. Indicates a potentially hazardous WARNING situation which, if not avoided, could WARNING. result in death or serious injury. Personal Protective Equipment (PPE). Indicates a potentially hazardous CAUTIONs situation which, if not avoided, could Required! result in minor or moderate injury. It Failure to wear proper PPE for the job being undertaken could also be used to alert against could result in death or serious injury.

3 Technicians, in unsafe practices. order to protect themselves from potential electrical, Indicates a situation that could result in mechanical, and chemical hazards, MUST follow NOTICE equipment or property-damage only. precautions in this manual and on the tags, stickers, and labels, as well as the instructions below: Important Environmental Concerns Before installing/servicing this unit, technicians MUST put on all PPE recommended for the work Scientific research has shown that certain man-made being undertaken. ALWAYS refer to appropriate chemicals can affect the earth's naturally occurring MSDS sheets and OSHA guidelines for proper PPE. stratospheric ozone layer when released to the atmosphere. In particular, several of the identified When working with or around hazardous chemicals, chemicals that may affect the ozone layer are refrigerants ALWAYS refer to the appropriate MSDS sheets and that contain Chlorine, Fluorine and Carbon (CFCs) and OSHA guidelines for information on allowable those containing Hydrogen, Chlorine, Fluorine and personal exposure levels, proper respiratory Carbon (HCFCs).

4 Not all refrigerants containing these protection, and handling recommendations. compounds have the same potential impact to the If there is a risk of arc or flash, technicians MUST put environment. Trane advocates the responsible handling of on all PPE in accordance with NFPA 70E or other all refrigerants-including industry replacements for CFCs country-specific requirements for arc flash such as HCFCs and HFCs. protection, PRIOR to servicing the unit. Important Responsible Refrigerant Practices Copyright Trane believes that responsible refrigerant practices are This document and the information in it are the property of important to the environment, our customers, and the air Trane and may not be used or reproduced in whole or in conditioning industry. All technicians who handle part, without the written permission of Trane . Trane refrigerants must be certified.

5 The Federal Clean Air Act reserves the right to revise this publication at any time and (Section 608) sets forth the requirements for handling, to make changes to its content without obligation to notify reclaiming, recovering and recycling of certain any person of such revision or change. refrigerants and the equipment that is used in these service procedures. In addition, some states or Trademarks municipalities may have additional requirements that must also be adhered to for responsible management of All trademarks referenced in this document are the refrigerants. Know the applicable laws and follow them. trademarks of their respective owners. 2 MS-SVX039A-EN. Table of Contents Model Number Description .. 4. Preparing for Installation .. 5. Accessories .. 5. Location Considerations .. 5. Unit Dimensions .. 6. Service Clearances .. 7. Installation.

6 8. Mounting the Unit .. 8. Purging the Unit .. 9. Installing Refrigerant Piping .. 10. Leak Testing Pipe Connections .. 12. Installing the Drain System .. 13. Centralized Drainage .. 15. Testing the Drainage .. 15. Insulation .. 16. Refrigerant Pipes .. 16. Drainage Hose .. 16. Wiring the Unit .. 17. Power Wiring .. 17. Communications Wiring .. 17. Electrical Conduit Installation .. 19. Configuration .. 20. Using the Technician Utilities Tool (TUT) .. 20. Using the Wireless Remote Control .. 21. The 2-Digit Segments .. 22. Installation Option #1 .. 23. Operation .. 25. Components .. 25. Operating Tips .. 25. Internal Protections .. 26. Operating Ranges .. 26. Cleaning the Exterior .. 26. Cleaning the Grill and Air Filter .. 27. Periodic Maintenance Checks .. 28. Troubleshooting .. 29. Warranty For Trane C-Series ductless Systems and Related Accessories.

7 31. MS-SVN045A-EN 3. Model Number Description 4 M U C 4 5 1 8 A 1 0 N 0 A. 1 2 3 4 5 6 7 8 9 10 11 12 13 14. Digit 1: Refrigerant 4 = R-410A. Digit 2: Brand name M = Mini- split indoor unit Digit 3: System type U = Universal match heat pump Digit 4: Configuration type C = 4-way cassette Digit 5: Reserved for future use 4 = Standard model Digit 6: Connection type 5 = Flare Digit 7, 8: Nominal capacity (Btu/h x 1,000). 18 = 18,000 Btu/h 36 = 36,000 Btu/h 24 = 24,000 Btu/h 42 = 42,000 Btu/h 30 = 30,000 Btu/h 48 = 48,000 Btu/h Digit 9: Major development sequence A = First development sequence Digit 10: Electric power supply characteristics 1 = 208 230/60/1. Digit 11: Reserved for future use 0 = Not currently used Digit 12: Region of sale N = North America (UL or ETL). Digit 13: Reserved for future use 0 = Not currently used Digit 14: Minor design sequence A = First design sequence 4 MS-SVX039A-EN.

8 Preparing for Installation Accessories In addition to product literature, the following accessories are supplied with this unit. The type and quantity may differ, depending on the model. Flexible hose Template Insulation A Insulation B Insulation C clamp Flexible hose Cable tie Conduit bracket Note: The required panel is not included with the indoor unit. It must be ordered separately (Model #TVEPANPC4 NUSET). Location Considerations When deciding on a location for the indoor unit, the following factors must be considered: The air inlet and outlet must be unobstructed. The wall or ceiling must support the weight of the unit. The wall or ceiling must not be subject to vibration. Pre-plan for easy and short routing of the refrigerant tubing and wiring to the outdoor unit. The air must circulate freely in the area to be cooled/heated. Sufficient clearance must be maintained around the unit.

9 Condensate must be managed correctly and safety away from the unit. The unit should be installed in a way that prevents unauthorized access. The unit must not be installed in an area that is damp or could come into contact with water (such as a laundry room). The unit must not be exposed to direct sunshine or to other direct heat sources. The filter must be able to be removed and cleaned easily. The unit should be placed as far as possible from fluorescent lights so the remote control is not subject to interference. Care should be taken to prevent harmonics generated by loose or unsupported material in close proximity to a running unit. The unit must not be installed in an area that is exposed to salt, machine oil, sulfide gas, or corrosive environmental conditions. MS-SVX039A-EN 5. Preparing for Installation Unit Dimensions Unit: inch (mm). (890 910) ceiling opening (950) (735) suspension position (890 910) ceiling opening (735) suspension position (950).

10 (55) (840). (370). (346) (55) (840) (55). (96). (185). (120). B. A. (45). (164). (216). 13 (330) (240) (86). Sub duct connection (270). (300). Model 4 MUC4530A10N0A. 4 MUC4536A10N0A. 4 MUC4542A10N0A. Dimension/Weight/Diameter 4 MUC4518A10N0A 4 MUC4524A10N0A 4 MUC4548A10N0A. A 8 (204) (288). B 10 (253) (337). Net dimension 33 x 8 x 33 (840 x 204 x 840) 33 x x 33 (840 x 288 x 840). Net weight lb ( kg) lb (19 kg). Liquid pipe connection 1/4 ( ) 1/4 ( ) 3/8 ( ). Gas pipe connection 1/2 ( ) 5/8 ( ) 5/8 ( ). Drain hose connection OD: (25), ID: (20). 6 MS-SVX039A-EN. Preparing for Installation Service Clearances 59 (1500) minimum C. (17). (2500) min. (20). Obstruction Model 4 MUC4530A10N0A. Clearance 4 MUC4536A10N0A. 4 MUC4518A10N0A 4 MUC4542A10N0A. 4 MUC4524A10N0A 4 MUC4548A10N0A. C 10 (253) (337). MS-SVX039A-EN 7. Installation Review Installation Considerations before proceeding with installation.