1 InstallationOperationMaintenanceUniTrane Fan-Coil Room ConditionersForce Flo Cabinet HeatersSizes 02-12 Low Vertical Fan-CoilsSizes 03-06 UNT-IOM-6 Supercedes UNT-IOM-5 April 2000 Models LO Design Sequence and Later2 UNT-IOM-6 Table of ContentsGeneral Number and the Insulating with Hydronic Coil Connec-tions with Steam Piping Package the Auxiliary Overflow Changeover Electric Heat LockoutSwitch (Fan-coil) ..27 Ductwork Power mounted Control Interconnec-tion Grounding Mode Switch .. Wall mounted Sensor Mode and Module Mode Fan COMM Output ..53 Tracer Communication Communication Zone Human and Heating Sequence of Mode Water TemperatureSampling with Auxiliary Electric Heat(Fan-coils)..94 Fresh Air Damper : Low Temperature : Condensate OverflowDetection : Smoke : External : : Motion Diagnostics.
2 101 Reading the Operating MachineState ..102 Reading the Operating Mode Listed as ..109 Maintenance Maintenance and Cleaning the Coil ..120 Inspecting and Cleaning and Cleaning theInternal Insulation on and Cleaning Board Assembly Piping Wiring Diagrams ..129-134 UNT-IOM-6 3 UniTrane fan-coil and Force Flo cabinet heaters units are singleroom units with load capabilities of 200 to 1200 cfm. See Figure 1for unit components. Fan-coil units are available as 2-pipe with orwithout electric heat (one hydronic circuit) or 4-pipe (two hydroniccircuits). Force Flo units feature 2-pipe hydronic coils, electric heatonly, or steam only. Also, units feature a variety of factory pipingpackages. See the Appendix on page 100 for more information onavailable factory-installed piping control options are available with the UniTrane fan-coil andForce Flo cabinet heater fan mode switch2.
3 Tracer , , terminal unit controller (TUC)All control options are available as unit or wall mounted . Units with aTracer , , or TUC also feature a split combina-tion: unit mounted fan mode switch with a wall mounted setpoint Tracer controllers ( , , and ) utilize binaryoutputs to operate 2-position control valves, supply fan/s, 2-positiondampers, and electric TUC utilizes binary outputs to control the fan and optionalauxiliary heat. In addition, it operates 2-position or 3 wire floatingpoint control valves and the fresh air supply and return openings vary with each cabinet style. Inaddition, a fresh air opening with either a manual or motorized airdamper is an available option. See pages 4-5 for available InformationHydronic coilFan motor(s)Throwaway filterSupply fan(s)Piping packageControl panelFigure 1. Main components of a fan-coil or cabinet heater unit.
4 *Auxiliarydrain pan*Main drain pan*Featured on fan-coils only4 UNT-IOM-6 Model FWall Hung Cabinet**Model BVertical CabinetModel AVertical ConcealedCabinet StylesModel CHorizontal ConcealedModel DHorizontal CabinetModel EHorizontal RecessedUNT-IOM-6 5 Model KLow Vertical Concealed*Model LLow Vertical Cabinet*Model MInverted Vertical Cabinet**Model NInverted Vertical Recessed**Fan-coil only**Force Flo cabinet heater onlyModel JVertical Slope Top CabinetModel HVertical Recessed6 UNT-IOM-6 Figure 2. The unit nameplate ison the fan NumberDescriptionEach UniTrane fan-coil and Force Flo cabinet heater has amultiple character model number unique to that particular unit. Todetermine a unit s specificoptions, reference the modelnumber on the unit nameplateon the fan scroll. The unitnameplate also identifies theserial number, sales ordernumber, and Installation andoperating specifications.
5 SeeFigure 2 for the pages 7-8 for adetailed explanation of themodel the Installation checklist on page 13 to ensure proper andsafe 7 Model Number DescriptionJWith piping, RHKWith piping, LHLWith piping, RH, ext. end pocketMWith piping, RH, ext. end pocketDigits 10 & 11 Design SequenceLODigit 12 InletAFront toe spaceBFront bar grilleCFront stamped louverDBottom stamped louverEBottom toe spaceFBack duct collarGOpen returnHBack stamped louverDigit 13 Fresh Air Damper0 NoneAManual, bottom openingBManual, back openingCManual, top openingDAuto, 2 pos., bottom openingEAuto, 2 pos., back openingFAuto, 2 pos. top openingGAuto, economizer,bottom openingHAuto, economizer, back openingJAuto, economizer, top openingKNo damper, bottom openingLNo damper, back openingMNo damper, top openingDigit 14 OutletAFront duct collarBFront bar grilleCFront stamped louverDFront quad grilleEBottom duct collarFBottom stamped louverGTop quad grilleHTop bar grilleJTop duct collarKBottom bar grilleDigit 15 Color0 None1 Deluxe beige2 Soft dove3 Cameo white4 Driftwood grey5 Stone grey6 Rose mauveDigit 16 Tamperproof Locks& Leveling Feet0 NoneAKeylock panelBKeylock access doorCKeylock panel & access doorDLeveling feetEKeylock panel with leveling feetFKeylock access doorw/leveling feetGKeylock panel & access door w/leveling feetDigit 17 MotorAFree dischargeBHigh staticDigit 18 CoilA2 row cooling/heatingB3 row cooling/heatingC4 row cooling/heatingD2 row cooling.
6 1 row heatingE2 row cooling, 2 row heatingF3 row cooling, 1 row heatingG2 row cooling or heating onlyH3 row cooling or heating onlyJ4 row cooling or heating onlyK2 row cooling/heating, elec. heatL3 row cooling/heating, elec. heatM4 row cooling/heating, elec. heatNElectric heat only, 1 stageP2 row cooling/heating,1 row heatingQ2 row cooling/heating,2 row heatingR3 row cooling/heating,1 row heatingUElectric heat only, 2 stageVElectric heat only, low kw, 1 stageWSteam coilDigit 19 Coil Fin Series2144 Digit 20 Air VentAAutomaticMManualDigits 21, 22, & 23 Electric Heat kW[208 V kW derate in brackets]000 None010 [ ]015 [ ]020 [ ]025 [ ]030 [ ]040 [ ]045 [ ]050 [ ]060 [ ]070 [ ]075 [ ]080 [ ] [ ] [ ] [ ] [ ] [ ]*Force Flo cabinet heater onlyDigits 1 & 2 Unit TypeFCFFD igit 3 ModelAVertical concealedBVertical cabinetCHorizontal concealedDHorizontal cabinetEHorizontal recessedFVertical wall hung*HVertical recessedJVertical slope topKLow vertical concealedLLow vertical cabinetMInverted vertical cabinet*NInverted vertical recessed*Digit 4 Development SequenceBDigits 5 7 Unit Size020 200 cfm030 300 cfm040 400 cfm060 600 cfm080 800 cfm1001000 cfm1201200 cfmDigit 8 Unit Voltage1115/60/12208/60/13277/60/14230/6 0/15208/60/36230/6j0/37480/60/38110-120/ 50/19220-240/50/1A220-240/50/3B380-415/5 0/3 Digit 9 Piping System PlacementAW/o piping, RH conn.
7 , w/o aux. drain panBW/o piping, LH conn.,w/o aux. drain panCW/o piping, RH conn.,w/ aux. drain panDW/o piping, LH conn.,w/ aux. drain panEW/o piping, RH conn.,w/o aux. drain pan, ext. end pocketFW/o piping, LH conn.,w/o aux. drainGW/o piping, RH conn.,w/ aux. drain pan, ext. end pocketHW/o piping, LH conn.,w/ aux. drain pan, ext. endpocket8 UNT-IOM-6R7 falsebackT8 falsebackDigit 40 Main Auto Circuit Setter GPM0 NoneA 41 Auxiliary Auto Circuit Setter GPM0 NoneA 42 Subbase0 NoneA2 heightB3 heightC4 heightD5 heightE6 heightF7 heightDigit 43 Recessed Flange0 NoneARecessed flangeDigit 44 Wallbox0 NoneAAnodizedDigit 24 Reheat0 NoneASteamBHot waterDigit 25 Disconnect Switch0 NoneDWith disconnectDigit 26 Filter0 None11 TA21 TA pltd. media31 TA + 1 extra41 TA pltd. media + 1 extra51 TA + 2 extra61 TA pltd.
8 Media + 2 extra71 TA + 3 extra81 TA pltd. media + 3 extraDigit 27 Main Control Valve0 NoneA2 way, 2 pos., (25 psig)B3 way, 2 pos., (30 psig)C2 way, 2 pos., (25 psig)D3 way, 2 pos., (15 psig)E2 way, 2 pos., (50 psig)F3 way, 2 pos., (50 psig)G2 way, 2 pos., (50 psig)H3 way, 2 pos., (50 psig)J2 way, mod., Cv = (50 psig)K3 way, mod., Cv = (50 psig)L2 way, mod., Cv = (50 psig)M3 way, mod., Cv = (50 psig)N2 way, mod., Cv = (50 psig)P3 way, mod., Cv = (50 psig)Q2 way, mod., Cv = (50 psig)R3 way, mod., Cv = (50 psig)Digit 28 Auxiliary Control Valve0 NoneA2 way, 2 pos., (25 psig)B3 way, 2 pos., (30 psig)C2 way, 2 pos., (25 psig)D3 way, 2 pos., (15 psig)E2 way, 2 pos., (50 psig)F3 way, 2 pos., (50 psig)G2 way, 2 pos., (50 psig)H3 way, 2 pos.
9 , (50 psig)J2 way, mod., Cv = (50 psig)K3 way, mod., Cv = (50 psig)L2 way, mod., Cv = (50 psig)M3 way, mod., Cv = (50 psig)N2 way, mod., Cv = (50 psig)P3 way, mod., Cv = (50 psig)Q2 way, mod., Cv = (50 psig)R3 way, mod., Cv = (50 psig)Digit 29 Piping Package0 NoneABall valve supply & returnBBall valve supply & manual circuit setter returnCBall valve supply & auto circuitsetterDBall valve supply & returnw/strainers & unionsEBall valve supply & manual circuit setter w/strainers & unionsFBall valve supply & auto circuitsetter w/strainers & unionsDigit 30 Control TypeAFan Speed SwitchCTUCDTUC w/ Trane ICSET racer 31 Control OptionsDUnit mtd. fan mode switch (OHML)KWall mtd. fan mode switch (OHML)VUnit mtd. zone sensor, w/SProtary, & fan mode switch(OAHML),WWall mtd.
10 Zone sensor w/SP rotary, & fan mode switch(OAHML),XUnit mtd. fan mode switch, wallmtd. setpoint dial zone sensorDigit 32-34 Future Control OptionsDigit 35 Control Function 30 None2 Condensate overflow detectionDigit 36 Control Function 40 None2 Low temperature detectionDigits 37 & 38 Future Control OptionsDigit 39 Recessed Options0 NoneAStand. 5/8 recessed panelB2 projection projection panelD3 projection projection panelF4 projection projection panelH5 projection projection panelK6 projection panelL2 falsebackM3 falsebackN4 falsebackP5 falsebackQ6 falsebackK 9 Receiving and HandlingUniTrane fan-coil and Force Flo cabinet heaters ship in individualcartons for maximum protection during shipment and for handling andstorage ease. Each carton has tagging information such as themodel number, sales order number, serial number, unit size, pipingconnections, and unit style to help properly locate the unit in the floorplan.