Instruction Manual: Fisher 4200 Electronic Position ...

Instruction manual 4200 Transmitters D200354X012 October 2017. Fisher 4200 Electronic Position Transmitters Contents Figure 1. Typical Fisher 4200 Position Transmitters Introduction .. 2. Scope of manual .. 2. Description .. 2. Specifications .. 5. Educational Services .. 5. Installation .. 6. Hazardous Area Classifications and Special instructions for Safe Use and Installations in Hazardous Locations .. 6. Mechanical Connections .. 7. Sliding Stem Actuator Mounting .. 7. Rotary Shaft Actuator Mounting .. 8. Long Stroke Sliding Stem Actuator Mounting Fisher 585C and 470 16 .. 8. Long Stroke Sliding Stem Actuator Mounting Fisher 585 CLS and 490 .. 9. Electrical Connections .. 10. Conduit .. 10. Field Wiring .. 10. Potentiometer Alignment .. 13. Direct or Reverse Action .. 14. Operating Information.

www.Fisher.com Fisher™ 4200 Electronic Position Transmitters Contents Introduction ..... 2 Scope of Manual ..... 2 ...

Tags:

  Manual, Instructions, Electronic, Position, Transmitter, 2004, Fisher, Instruction manual, Fisher 4200 electronic position transmitters, Fisher 4200 electronic position

Information

Domain:

Source:

Link to this page:

Please notify us if you found a problem with this document:

Other abuse

Transcription of Instruction Manual: Fisher 4200 Electronic Position ...

1 Instruction manual 4200 Transmitters D200354X012 October 2017. Fisher 4200 Electronic Position Transmitters Contents Figure 1. Typical Fisher 4200 Position Transmitters Introduction .. 2. Scope of manual .. 2. Description .. 2. Specifications .. 5. Educational Services .. 5. Installation .. 6. Hazardous Area Classifications and Special instructions for Safe Use and Installations in Hazardous Locations .. 6. Mechanical Connections .. 7. Sliding Stem Actuator Mounting .. 7. Rotary Shaft Actuator Mounting .. 8. Long Stroke Sliding Stem Actuator Mounting Fisher 585C and 470 16 .. 8. Long Stroke Sliding Stem Actuator Mounting Fisher 585 CLS and 490 .. 9. Electrical Connections .. 10. Conduit .. 10. Field Wiring .. 10. Potentiometer Alignment .. 13. Direct or Reverse Action .. 14. Operating Information.

2 15. Initial Considerations .. 15. transmitter and Position Switch Conditions .. 15 W4273 1 W4274 1. Normal Operation .. 16 SLIDING STEM ROTARY. Calibration .. 17 ACTUATOR MOUNTING ACTUATOR MOUNTING. Test Equipment Required .. 18. Test Connections to the Field Wiring Compartment .. 19. transmitter Circuit Zero and Span Principle of Operation .. 22. Adjustment .. 20 transmitter Circuit .. 23. High and Low Position Switch Adjustment .. 20 Position Switch Circuit .. 24. Setting the High Position Switch .. 21 Maintenance .. 25. Setting the High Position Switch Troubleshooting Procedures .. 26. Deadband .. 21 transmitter Circuit .. 26. Setting the Low Position Switch .. 21 Position Switch Circuit .. 26. Setting the Low Position Switch Parts Ordering .. 31. Deadband .. 22 Parts Kits .. 31. Position Switch Circuit Shutoff.

3 22 Parts List .. 32. 4200 Transmitters Instruction manual October 2017 D200354X012. Introduction Scope of manual This Instruction manual provides installation, operating, calibration, maintenance, and parts ordering information for Fisher 4200 Electronic Position transmitters (figure 1). Refer to separate Instruction manuals for information on the actuator and valve. Do not install, operate, or maintain a 4200 Electronic Position transmitter without being fully trained and qualified in valve, actuator, and accessory installation, operation, and maintenance. To avoid personal injury or property damage, it is important to carefully read, understand, and follow all of the contents of this manual , including all safety cautions and warnings. If you have any questions regarding these instructions contact your Emerson sales office or Local Business Partner before proceeding.

4 Description 4200 Electronic Position transmitters combine Fisher field proven Electronic and mechanical expertise in a versatile, accurate instrument. They sense the Position of a sliding stem actuator, rotary actuator, vent, damper, or other device and send a standard (4 20 mA) output signal to an indicating device, a process control system or programmable logic controller. 4200 transmitters are available as a transmitter only, as a transmitter with integral high and low Position switches, or with high and low Position switches only. Refer to the nameplate to determine the type of transmitter . Use the Type number and table 2 to determine the output and travel ranges available from the transmitter . When the instrument is mounted, the potentiometer shaft (figure 2) is mechanically connected to the device to sense mechanical motion.

5 Except for the 4215 transmitter , all types of transmitters use a single potentiometer for Position input. The 4215 transmitter uses dual potentiometers mounted on the same shaft. This permits using individual potentiometers for the transmitter and the Position switch circuits, providing additional electrical isolation. For long stroke applications, a multi turn potentiometer attached to a travel transducer assembly senses linear motion of the actuator stem or other device. Figure 2. transmitter Dimensions FIELD WIRING. COMPARTMENT. transmitter . PORT 1/2 NPT COMPARTMENT. (2 PLACES). 102 159. 51 ( ) ( ). ( ). 5/16 18 UNC. 13 DEEP. 51 ( ). 102. ( ) ( ). CAP. (2 PLACES). 35. BOTTOM VIEW ( ). 6 ( ). DIA. 75. ( ). 67 67. POTENTIOMETER. ( ) 21 ( ). SHAFT. ( ) ALLOW 254 mm (10 INCHES). FOR MAINTENANCE (2 PLACES).

6 19A7968-E. B1910-4. END VIEW SIDE VIEW mm (INCH). 2. Instruction manual 4200 Transmitters D200354X012 October 2017. Table 1. Specifications Available Configurations when operating terminal voltage varies between 11. See table 2 and 30 volts DC. Electromagnetic Compatibility for 4211 and 4221: Input Signal Meets EN 61326 1:2013. Source: Single potentiometer is standard or a dual Immunity Industrial locations per Table 2 of potentiometer is available for the 4215 only. Refer to the EN 61326 1 standard. Performance is table 3 for zero and span limits shown in table 4 below. Emissions Class A. Output Signal ISM equipment rating: Group 1, Class A. Range: 4 to 20 milliampere DC transmitter output Operating Conditions (4210, 4211, 4215, 4220, and 4221 transmitters). Load Impedance ( transmitter only): See figure 3 Normal and Transportation Normal Output Current Limit: 30 milliamperes DC maximum Condition Operative and Storage Reference Limits Limits Switches: ON/OFF condition of high and low Position Ambient -40 to 71_C -50 to 80_C (-60 25_C.)

7 Switch relay (SPDT) Temperature (-40 to 160_F) to 180_F) (77_F). Ambient Power Supply Requirements Relative 10 to 95% 10 to 95% 40%. transmitter Terminal Current1 Humidity Voltage (VDC) Required Min Max (mA). Mounting transmitter Only 11 30 20 max. Position Switch with The instrument can be mounted on the actuator of 20 30 80 max. sliding stem or rotary valves or on other devices transmitter Position Switch without 20 30 50 max. transmitter Electrical Classification 1. Values indicate minimum power supply capabilities. CSA Intrinsically Safe, Explosion-proof, Recommended Power Supply Dust Ignition-proof 24 volts DC nominal FM Intrinsically Safe, Explosion proof, Dust Ignition-proof, Non Incendive Position Switch Relays ATEX Intrinsically Safe, Type n, Flameproof Type: Two single pole, double throw relays (SPDT) IECEx Intrinsically Safe, Type n, Flameproof Service Rating: The relay contact rating is 5 amperes at either 30 volts DC or 120 volts AC (resistive load) Other Classifications/Certifications Life Expectancy: 100,000 operations at rated load, or CUTR Customs Union Technical Regulations 50,000 operations at a typical inrush current of 10.

8 (Russian, Kazakhstan, Belarus, and Armenia). amperes with 120 volts AC lamp or motor load KGS Korea Gas Safety Corporation (South Korea). Reference Accuracy PESO Petroleum and Explosives Safety Organization (India). 1% of output span. Includes combined effects of hysteresis, linearity, and deadband Contact your Emerson sales office or Local Business Partner for classification/certification specific Repeatability information of span Housing Operating Influences NEMA 4X; CSA Enclosure 4X; IP66. Ambient Temperature: For a 38_C (100_F) change in normal operating conditions, maximum zero shift is Approximate Weight ; maximum span shift is of span transmitter Without Mounting Bracket: kg Power Supply: Output signal changes less than (4 pounds). NOTE: Specialized instrument terms are defined in ANSI/ISA Standard - Process Instrument Terminology.

9 3. 4200 Transmitters Instruction manual October 2017 D200354X012. Table 2. Available Configurations TRAVEL. ELECTRICAL. Standard Stroke Long Stroke DUAL. TYPE NUMBER transmitter Position . Up to 105 mm(1) Up to 610 mm(1) POTENTIOMETER. SWITCHES. (Up to Inches) (Up to 24 Inches). 4210 X X X --- --- 4211 X --- X --- --- 4212 --- X X --- --- 4215 X X X --- X. 4220 X X --- X --- 4221 X --- --- X --- 4222 --- X --- X --- 1. See table 3 for zero and span limits. Table 3. Zero and Span Limits(1). DEGREES OF SLIDING STEM ACTUATOR TRAVEL. POTENTIOMETER ROTATION mm INCHES. TYPE NUMBER CONNECTION(2). Zero Span Zero Span Zero Span Position Min. Max. Position Min. Max. Position Min. Max. 4210 1 0 to 51 8 51 0 to 2 2. 4211. 0 to 90 15 90. 4212. 2 0 to 105 17 105 0 to 4215. 4220 12 Inch Transducer 0 to 305 105 305 0 to 12 12.

10 4221 0 to 884 150 884. 4222 24 Inch Transducer 0 to 610 305 610 0 to 24 12 24. 1. Zero Position is the range of values over which the transmitter zero can be adjusted. Span is the range of shaft rotation or stem travel the transmitter span can be adjusted. For example, a zero Position of 45 degrees and a span of 15 degrees means the transmitter output is 4 mA DC after 45 degrees of shaft rotation. The output then increases from 4 mA DC to 20 mA DC as the shaft rotates from 45 to 60 degrees. 2. Refer to figures 15, 22, and 23 for locations of connections. Figure 3. Power Supply Requirements 1000. LOAD IMPEDANCE (OHMS). 750. 650. 500 OPERATING. REGION. 250. 0. 0 10 20 30. 11 24 MAXIMUM transmitter TERMINAL VOLTAGE. NOMINAL SUPPLY VOLTAGE. MINIMUM transmitter TERMINAL VOLTAGE. POWER SUPPLY VOLTAGE (VOLTS DC).